INSTALLATION NOTES:
1.
End of line resistors are 10K ohm. 1/2 watt. These
resistors are not supplied with panel, but available as
part no. 06-129520-001 (kit of 50).
2.
Maximum number of smoke detectors per circuit is
15.
3.
Release devices: See Figures 4 and 5 for wiring.
4.
The non-supervised aux power supply circuit is only
intended to supply up to 0.25 A to power a single 24
VDC notification appliance when installed in the same
room and with all wiring in conduit.
The connection to this device must include a N.O.
Alarm contact relay closure.
5.
The trouble contacts are marked with the panel either
de-energized (no power) or in trouble condition. The
Figure 3. Installation Wiring Diagram
relay is energized and the contacts change state on
application of power to the panel. The relay is de-en-
ergized in trouble condition.
6.
If there are no devices connected to the release cir-
cuit, connect a 300 ohm, 2 watt resistor between ter-
minals 28 and 31.
7.
Circuits marked with a circle (
o
) are power limited; all
field wiring must be routed away from ac in and bat-
tery wiring.
8.
If using a power limited power source, follow note 7. If
using a non-power limited source, maintain a mini-
mum 1/4” spacing from all power limited wiring.
9.
For ULC installations, all extended circuits shall not
exceed 120 V nominal (150 V max to ground).
06-129800-002
W1
W2
S4
F
F
O
ON
ISOLATE
+
BATT
XFMR
ON
S2
8
7
6
5
4
3
2
1
1
2
3
4
5
6
7
8
+
9 10
+
11 12
+
13 14 15
NO
16
C
17
NC
18
NO
19
C
20
NC
21
NO
22
C
23
NC
24 25 26
+
27 28
+
29 30 31
1
1
1
1
1
2
2
1
ALARM 1
ALARM 2
TROUBLE
CONTACTS RATED AT
2A; 30VDC, 250VAC
N/CN/C
N/CN/C
ABORT
CIRCUIT
MANUAL
RELEASE
CIRCUIT
SUPERVISORY
CIRCUIT
DETECTOR 1
CIRCUIT
17.3 - 26.0 VDC
MAX LINE RESISTANCE 50 OHMS
MAX LINE RESISTANCE 50 OHMS
17.3 - 26.0 VDC
CIRCUIT
DETECTOR 2
RELEASE CIRCUIT
BELL CIRCUIT
24VDC
REGULATED
MAX CURRENT 0.5A
AUX. PS CIRCUIT
24VDC
MAX CURRENT 0.25A
MAX STANDBY CURRENT 0mA
MAX RIPPLE 1.5Vpp
24VDC
1.2A-H
25VRMS
TO MAIN CIRCUIT
120VAC, 0.5A, 50/60 HZ
240VAC, 0.25A, 50/60 HZ
MAXIMUM WIRE SIZE #14AWG.
GROUND
0.485A MAX CHARGING CURRENT
SUPERVISED, USE ONLY KIDDE-FENWAL
BATTERY CAT. NO. 06-115915-020
(CONSISTS OF ONLY ONE BATTERY)
MAX LINE RESISTANCE 50 OHMS
MAX LINE RESISTANCE 50 OHMS
MAX LINE RESISTANCE 50 OHMS
TO TERMINAL
15 OR 18
16 OR 19
TO TERMINAL
WHEN USED MUST
CONNECT TO ALARM1
OR ALARM2 CONTACTS
SEE NOTE 4
3
3
SPV
ACT
ON
ALM
ALM
ABT
2
ZONE
ZONE
ALM
REL
MNL
ON
PWR
RESET
1
TBL
OUT
REL
SPV
TBL
ABT
TBL
TBL
REL
MNL
TBL
2
ZONE
TBL
ZONE
TBL
SYS
1
+
SIG SIL
SIG
SIL
+
BATT
XFMR
24VDC
1.2A-H
FOR CANADIAN SYSTEMS, CONNECT BATTERIES
TO BATTERRY CUTOUT CIRCUIT AS SHOWN ABOVE.
4
3
2
1
(+)
(-)
(+)
(-)
BT
BT
MB
MB
BA
TTER
Y
CUT
OUT
S2 PROGRAM SWITCH
SEE TEXT FOR DEFINITIONS
S4 RELEASE CIRCUIT ISOLATE SWITCH
JUMPERS W1 & W2 MUST BE OUT
TO ALLOW ISOLATE FUNCTION
RESET SWITCH
HOLD FOR 5 SECONDS TO CLEAR ALARM
INDICATES SUPERVISED CIRCUIT
INDICATES POWER LIMITED CIRCUIT
firealarmresources.com
Содержание 151FE1
Страница 2: ...firealarmresources com...
Страница 12: ...December 2001 06 235793 001 Scorpio 8 THIS PAGE INTENTIONALLY LEFT BLANK firealarmresources com...
Страница 15: ...firealarmresources com...