background image

06-235793-001

December 2001

Scorpio

5

INSTALLATION NOTES:

1.

End of line resistors are 10K ohm. 1/2 watt. These
resistors are not supplied with panel, but available as
part no. 06-129520-001 (kit of 50).

2.

Maximum number of smoke detectors per circuit is
15.

3.

Release devices: See Figures 4 and 5 for wiring.

4.

The non-supervised aux power supply circuit is only
intended to supply up to 0.25 A to power a single 24
VDC notification appliance when installed in the same
room and with all wiring in conduit.

The connection to this device must include a N.O.
Alarm contact relay closure.

5.

The trouble contacts are marked with the panel either
de-energized (no power) or in trouble condition. The

Figure 3. Installation Wiring Diagram

relay is energized and the contacts change state on
application of power to the panel. The relay is de-en-
ergized in trouble condition.

6.

If there are no devices connected to the release cir-
cuit, connect a 300 ohm, 2 watt resistor between ter-
minals 28 and 31.

7.

Circuits marked with a circle (

o

) are power limited; all

field wiring must be routed away from ac in and bat-
tery wiring.

8.

If using a power limited power source, follow note 7. If
using a non-power limited source, maintain a mini-
mum 1/4” spacing from all power limited wiring.

9.

For ULC installations, all extended circuits shall not
exceed 120 V nominal (150 V max to ground).

06-129800-002

W1

W2

S4

F

F

O

ON

ISOLATE

+

BATT

XFMR

ON

S2

8

7

6

5

4

3

2

1

1

2

3

4

5

6

7

8

+

9 10

+

11 12

+

13 14 15

NO

16

C

17

NC

18

NO

19

C

20

NC

21

NO

22

C

23

NC

24 25 26

+

27 28

+

29 30 31

1

1

1

1

1

2

2

1

ALARM 1

ALARM 2

TROUBLE

CONTACTS RATED AT

2A; 30VDC, 250VAC

N/CN/C

N/CN/C

ABORT

CIRCUIT

MANUAL

RELEASE

CIRCUIT

SUPERVISORY

CIRCUIT

DETECTOR 1

CIRCUIT

17.3 - 26.0 VDC

MAX LINE RESISTANCE 50 OHMS

MAX LINE RESISTANCE 50 OHMS

17.3 - 26.0 VDC

CIRCUIT

DETECTOR 2

RELEASE CIRCUIT

BELL CIRCUIT

24VDC

REGULATED

MAX CURRENT 0.5A

AUX. PS CIRCUIT

24VDC

MAX CURRENT 0.25A

MAX STANDBY CURRENT 0mA

MAX RIPPLE 1.5Vpp

24VDC

1.2A-H

25VRMS

TO MAIN CIRCUIT

120VAC, 0.5A, 50/60 HZ
240VAC, 0.25A, 50/60 HZ

MAXIMUM WIRE SIZE #14AWG.

GROUND

0.485A MAX CHARGING CURRENT
SUPERVISED, USE ONLY KIDDE-FENWAL
BATTERY CAT. NO. 06-115915-020
(CONSISTS OF ONLY ONE BATTERY)

MAX LINE RESISTANCE 50 OHMS

MAX LINE RESISTANCE 50 OHMS

MAX LINE RESISTANCE 50 OHMS

TO TERMINAL

15 OR 18

16 OR 19

TO TERMINAL

WHEN USED MUST
CONNECT TO ALARM1
OR ALARM2 CONTACTS
SEE NOTE 4

3

3

SPV

ACT

ON

ALM

ALM

ABT

2

ZONE

ZONE

ALM

REL

MNL

ON

PWR

RESET

1

TBL

OUT

REL

SPV

TBL

ABT

TBL

TBL

REL

MNL

TBL

2

ZONE

TBL

ZONE

TBL

SYS

1

+

SIG SIL

SIG
SIL

+

BATT

XFMR

24VDC

1.2A-H

FOR CANADIAN SYSTEMS, CONNECT BATTERIES
TO BATTERRY CUTOUT CIRCUIT AS SHOWN ABOVE.

4

3

2

1

(+)

(-)

(+)

(-)

BT

BT

MB

MB

BA

TTER

Y

CUT

OUT

S2 PROGRAM SWITCH

SEE TEXT FOR DEFINITIONS

S4 RELEASE CIRCUIT ISOLATE SWITCH

JUMPERS W1 & W2 MUST BE OUT
TO ALLOW ISOLATE FUNCTION

RESET SWITCH

HOLD FOR 5 SECONDS TO CLEAR ALARM

INDICATES SUPERVISED CIRCUIT

INDICATES POWER LIMITED CIRCUIT

firealarmresources.com

Содержание 151FE1

Страница 1: ...Scorpio Fire Control Panel Installation Operation Maintenance Manual December 2001 TM Fire Systems P N 06 235793 001 UL Listing File No S2422 firealarmresources com...

Страница 2: ...firealarmresources com...

Страница 3: ...not interfere with battery and printed circuit board location Do not over tighten screw terminals over tightening may damage threads resulting in reduced terminal contact pressure and difficult with s...

Страница 4: ...y trained distributors technicians The entire manual should be read and fully understood prior to installation TEST EQUIPMENT Make certain test equipment is in good operating condition Do not touch li...

Страница 5: ...first alarm and is a steady output on second alarm An independent form C dry con tact is associated with each of the two alarm levels when programmed for two zone release Alarm Relay 2 may also be con...

Страница 6: ...instructions LAMP TEST Use the following steps to test all LEDs on the Control Panel 1 Hold the RESET Switch down All LEDs should light up 2 Release the RESET Switch All LEDs should return to Normal T...

Страница 7: ...nction S2 6 OFF Disables the abort function S2 7 S2 8 Switches 2 7 and 2 8 allows the installer to pro gram the desiredAbort mode for the installation There are three modes of Abort as explained in a...

Страница 8: ...RY POWER Batteries provide 24 hour standby supervision plus 5 minute alarm load at the end of that time contingent upon detection and output limitations stated herein Panel load ing and battery standb...

Страница 9: ...002 W1 W2 S4 F F O ON ISOLATE BATT XFMR ON S2 8 7 6 5 4 3 2 1 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 NO 16 C 17 NC 18 NO 19 C 20 NC 21 NO 22 C 23 NC 24 25 26 27 28 29 30 31 1 1 1 1 1 2 2 1 ALARM 1 ALARM...

Страница 10: ...etracted or SET position Electric control head P N 48650001 is designed for installation on a 487 or ECS series control head only Installation of this control head to any other device e g pressure ope...

Страница 11: ...d on terminals 28 31 Open circuit fault impedance 1 7K ohms UL Compatibility Identifier Number C30FE1 Two Detection Circuits Output voltage 17 3 26 0 Vdc Max number of 2 wire smoke detectors per circu...

Страница 12: ...December 2001 06 235793 001 Scorpio 8 THIS PAGE INTENTIONALLY LEFT BLANK firealarmresources com...

Страница 13: ...RREV DATE 5 SYSTEM EQUIPMENT 6 PRIORITY OF COMMENT 7 USEREVALUATION MANUALIS qEXCELLENT qGOOD qFAIR qPOOR qCOMPLETE qINCOMPLETE 8 qPROBLEM qQUESTION qSUGGESTION qCOMMENT check one 9 RECOMMENDEDCHANGET...

Страница 14: ...KIDDE FENWAL Inc 400 Main Street Ashland MA 01721 Attn Documentation Manager Place Stamp Here FOLD FOLD firealarmresources com...

Страница 15: ...firealarmresources com...

Страница 16: ...hat this product is free from defects in material and workmanship and it will repair or replace any product or part thereof which proves to be defective in workmanship or material for a period of twen...

Отзывы: