Zero Clearance Stove 

 

16 

 

FIRE IS LIT, BUT NOT ENOUGH HEAT 

If gear motor only runs short cycles, timer is working.  When thermostat calls for 
heat, gear motor should run steady.  If gear motor is running steady, but fire is 
small, increase coal feed.  (See pages 11 & 12).  If gear motor is not running 
steady, check for loose wire in Thermostat or in Relay.  Check for broken 
thermostat wire between thermostat and Relay. 
 

GEAR MOTOR RUNS CONSTANTLY MAKING TOO MUCH HEAT 

 

Gear motor can only be activated by thermostat or timer.  Remove 

thermostat wires from T.T. terminals in Relay, if gear motor shuts off, replace 
thermostat wire or Thermostat.  Check timer to see if yellow wheel is turning, if 
not replace timer motor.  Check timer switch.  (See page 11 Timer) 
 

CONVECTION BLOWER NOT BLOWING MUCH AIR

 Clean screen and fan 

blades on blower. 
 

GEAR MOTOR SHUTS OFF ON HI-LIMIT 

High Limit pointer in Fan Limit Switch is designated to shut gear motor off when 
internal air temperature reaches 200 degrees.  If internal air temperature stays on 
200 degrees, Convection Blower is not cooling stove off quickly enough.  Clean 
screen and fan blades on blower (or See Page 13, Fan Limit Control). 
 

BIG FIRE BUT NOT MUCH HEAT 

Fan blades on combustion motor dirty.  Brush off. Accumulated fly ash under 
grate.  Remove combustion motor and clean under grate.  Holes blocked in grate.  
Open holes with 1/8 center punch (See Page 9 Diagram (1). 
 

TO CLEAN UNDER OR REPLACE GRATE

 See Page 3 (Cleaning & 

Lubrication) 
 

NYLON CAM MELTS 

Under normal operating conditions, nylon cam will not melt.  Melting of nylon 
cam can only be caused by a draft problem. 
A blockage in chimney, chimney connector, stove pipe, or stove.  Inspect and 
clean. 
Or excessive draft, caused by high chimney, large flue, or high winds.  Clean and 
adjust barometric damper.  (Set barometric damper with a draft gauge to obtain a 
draft reading of -.02 to -.03, See Page 3 Draft Check) 
 

 

Содержание Stoker Zero Clearance

Страница 1: ...personal injury or even death A carbon monoxide detector has been supplied with your stove You must plug it in Danger risk of fire or explosion Do not burn garbage gasoline drain oil or other flammab...

Страница 2: ...trol is required After determining the location of stove cut a hole through exterior wall 1 larger than the outer diameter of stove pipe Seal the base plates inner and outer with a bead of high temper...

Страница 3: ...hrough grate to create a hotter fire Fire bed should be close to lower end of grate after a continuous run of 20 to 30 minutes If fire bed hot coals is too small increase coal feed Loss of fire may oc...

Страница 4: ...overing it To fine tune the coal feed turn the white feed adjuster nut clockwise for more coal feed or counter clockwise for less Turn adjuster nut one or two full turns per day until best results are...

Страница 5: ...d forced out exhaust system The combustion air is taken from outside drawn in preheated then forced into fire chamber and returned outside through exhaust system To meet U L REQUIREMENTS FOR MOBILE HO...

Страница 6: ...opening that gasses could re enter home 5 Less than 4 feet below windows 6 Less than 1 foot horizontally of door or window 7 Less than 3 feet above any forced air inlet located within 10 feet 8 Less t...

Страница 7: ...Limit Control Serves dual purpose 1 As a high limit will shut off the stoker unit to prevent overheating If internal stove temperature reaches 200 degrees control will shut off stoker unit until temp...

Страница 8: ...he end of heating season Open ash door vacuum area thoroughly Remove exhaust motor clean fan blades and vacuum air chamber Clean and inspect exhaust system and pipe from stove to outside of home Oil e...

Страница 9: ...st once a year for looseness evidence of corrosion and for flue gas leakage Replace seal or tighten pipe as necessary It may be necessary to clean exhaust system and stove pipe during heating season R...

Страница 10: ...l be in continuous run but if the fire bed remains small increase the coal feed by turning white adjustment nut clock wise Under normal draft conditions when fire bed has reached its maximum length wi...

Страница 11: ...more coal feed Turn counterclockwise for less coal feed NYLON ADJUSTING SCREWS To eliminate metal on metal contact There are 8 nylon screws on the pusher bar 4 on each side The 4 nylon screws picture...

Страница 12: ...eat from thermostat or when timer turns it on COMBUSTION MOTOR Combustion motor will run all the time to force air through holes in grate to burn coal hotter The constant running of motor will assure...

Страница 13: ...d be the width of the grate and about 1 to 2 in length If the burning coals get any less than 1 the fire may go out SOLUTION Increase coal feed A weak draft can also cause the fire to go out if fire a...

Страница 14: ...ir temperature reaches this setting normally set around 160 degrees but is adjustable 3 LOW POINTER turns convection blower off when internal air temperature falls to this setting normally set around...

Страница 15: ...d you pusher bar will also come out with gear motor While pusher bar is out of its chute clean chute area and remove any obstructions Check nylon screws on pusher bar 2 on each side for wear or breaka...

Страница 16: ...g Lubrication STOKER UNIT DOESN T FEED COAL See page 10 Pusher Bar PUSHER BAR IS NOT MOVING STRAIGHT See page 10 Pusher Bar CONVECTION BLOWER RUNS TOO OFTEN See Page 13 CONVECTION BLOWER RUNS CONSTANT...

Страница 17: ...ON HI LIMIT High Limit pointer in Fan Limit Switch is designated to shut gear motor off when internal air temperature reaches 200 degrees If internal air temperature stays on 200 degrees Convection B...

Страница 18: ...s from entering the home certain precautions must be taken Ash tub must be emptied on a regular basis to prevent ashes from overflowing into ash pit area Excessive ash accumulation may impede air flow...

Страница 19: ...Zero Clearance Stove 18...

Страница 20: ...ipt are required Customer must provide a credit card which will be charged for the full retail price for the product plus shipping and handling When defective part is returned to the company and found...

Страница 21: ...ng Brush Manual Charcoal Thermostat Carbon Monoxide detector Glass Cleaner Ash Tub 4 Stainless Tee 24 X 4 Stainless Pipe 4 Stainless Rain Cap 6 galv Cap with 4 hole 6 X 12 Black Pipe 2 Wall Plates Pac...

Отзывы: