Loop-PFC/PSC Testing - continued

When using HANDSFREE mode with the distribution board test lead set always 

connect the Earth and Neutral poles before the Line, otherwise it will indicate a 

polarity fault and inhibit further testing.

HANDSFREE testing in No-trip mode. 

The tester will automatically conduct the socket wiring test upon connection to the 

Live supply. If all is well it will immediately initiate a Loop test.

When the test is complete the result will be displayed for a few seconds before the 

display reverts to showing the L-N voltage.

The Loop test result can be recalled by pressing the No-trip button and the PFC/

PSC result can be recalled by pressing the No-trip PFC button.

7

  NO TRIP PFC

  Having carried out a No-trip Earth fault loop test – pressing this 

button calculates the PFC (Prospective Fault Current) by dividing the measured loop 

result into the measured L-E voltage.

8  VOLTAGE

  The default voltage measurement is made between L-N. Using this 

button you can override to measure L-E and as a final safety check measure the 

N-E voltage present.

Ze/DB

 

This button selects the High Current True Loop Impedance mode. Use only 

with the test lead set configured for 2-wire mode (see page 6).

 

Connect the test leads to the two conductors being tested. The supply voltage 

(see step 8) will be displayed. A brief press of the test button will conduct the Loop 

test and the result will be displayed almost immediately.

 

Note: 

In 2-wire mode the voltage displayed will be that measured across the 2 

conductors that the test leads are connected to. The display will show this as L-N 

regardless of whether they are connected across L-N or L-E.

 

HANDSFREE testing in High current 2-wire mode.

 

This function is particularly useful for testing at distribution boards and is activated 

by pressing the test button before connecting to the mains supply. The KTD40 

will then automatically conduct a Loop test upon connection to the live supply 

and display the result. The supply voltage can be recalled by pressing the Voltage 

button and the PFC/PSC result can be recalled by pressing the No-trip PFC button.

10 

PFC/PSC

 

Prospective Fault Current/Prospective Short Circuit Current. Pushing 

this button divides the above TLI (True Loop Impedance) result into the voltage 

measured between the two points under test to give either the prospective short-

circuit current (when L-N is tested) or the prospective earth fault current (when L-E 

is tested).

Specifications

Wiring Test

Detects missing E or N (>15kΩ)
Detects L-E or L-N swap
Detects Live – Earth/Neutral reversal by use of Polarity Test Pad
Phase – Neutral voltage measurement  ± 1% ± 1V
Phase – Earth voltage measurement 

± 1% ± 1V

Neutral – Earth voltage measurement  ± 1% ± 1V

Loop Test

No trip mode 3 wire testing Phase – Neutral – Earth all connected
Test current <15mA at 253V AC

Range 

 

Accuracy

0.00 to 9.99Ω 

± 5% ± 5 digits

10.00 to 99.9Ω 

± 3% ± 3 digits

100.00 to 500Ω 

± 3% ± 3 digits

High current mode 2 wire testing Phase-Neutral or Phase-Earth connected using true 
impedance measurement – auto test (hands free) is selectable.

Range 

 

Accuracy

0.00 to 9.99Ω 

± 3% ± 3 digits

PFC/PSC Measurement

10A – 19.9kA 

This is a calculated result using the loop test measurement but  

 

 

it will be inherently more accurate than traditional methods as  

 

 

the test is of impedance not solely resistance.

Over Voltage Protection

440V AC 

 

No damage – complete recovery

Power

4 × AA batteries (not included)
Battery life (BS EN 61557) > 10,000 test (or shelf life of batteries installed)

Environmental

Operating Temperature Range

0°C to 40°C

Storage Temperature Range

–10°C to +60°C

Operating Humidity

93% RH @ 40°C

Size

157mm × 89mm × 39mm

Weight

400g