Kewtech KTD40 Скачать руководство пользователя страница 3

4

5

Operation overview

The KTD40 will test for No-trip loop, High current True Loop Impedance, No-trip PFC/

PSC (Prospective Fault Current), High current PSC using True Loop Impedance, mains 

voltage (L-N, L-E and N-E) and correct socket wiring, in addition to the incoming supply 

polarity check described on the previous page.

Another unique feature of your KTD40  tester is the high current 2-wire measurement of 

the TLI (True Loop Impedance). Regulations and guidance books refer to loop impedance 

measurements but up until now loop testers measured loop resistance which is different 

from loop impedance, particularly when testing close to the main supply transformer.

This function is therefore recommended when testing for external earth fault loop 

impedance (Ze) at distribution boards on non TT systems and similar points on the 

supply side of any Switch/RCD gear and when testing the Line/Neutral loop to determine 

prospective short circuit current.

It is the variation in power factor that makes the TLI measurement of your KTD40 so 

much more accurate than older loop testing techniques. (Because of this there may well 

be variations in readings compared to ordinary loop testers or the no-trip function of this 

tester, particularly when the measurement is made near to the main supply transformer).

The KTD40  also has a No-trip test mode that is guaranteed not to trip a 30mA or higher 

rated RCD providing that the circuit is otherwise healthy.

No-trip vs High current testing

Although the KTD40  High current TLI measurement mode is inherently more accurate 

than conventional techniques when measuring close to the main supply transformer, the 

difference between resistance and true impedance reduces the further away from the 

transformer the measurement is made.

This is why using the No-trip mode is suitable for measurement on final circuits and 

similarly remote points. It should be noted however that whilst No-trip testing at these 

locations will normally function at a similar high level of accuracy, the low current 

measurement technique used is more likely to be adversely affected by external factors 

such as contact resistance (e.g. when testing at seldom used socket outlets) and circuit 

noise (e.g. switched mode power supply on the same circuit). This can result in the 

occasional erroneous reading.

For this reason it is recommended that multiple measurements are made when using the 

No-trip mode and any isolated odd results are ignored. When taking multiple readings the 

tester or the supply should be powered off between consecutive tests. Where practical 

other equipment powered by the same socket should be turned off.

For safety reasons No-trip mode is recommended for all measurements made on TT 

systems.

Test lead configuration

Important

The KTD40  can be used with 2 different types of connecting lead. It is important to 

understand and use the correct lead configuration for each test mode or you may not 

obtain the correct results.

Lead options

Ref: KAMP13  The mains lead (IEC C13 to 13A plug) type connector that is 

supplied with the tester.

Ref: ACC016E  The 3-Pole fused distribution board test lead set which terminates 

in fused prods/crocodile clips. This is supplied as a separate accessory to the 

KTD40.

The lead is an integral part of the tester set-up and should accompany the tester when 

being returned for re-calibration or service. Do not use any other type of mains lead or 

fused test lead set as it would be likely to give incorrect results.

Lead configuration for No-trip testing

This is the default mode that the KTD40 will start in when turned on. This mode is most 

useful for testing at socket outlets, luminaires, wiring terminals, etc. in installations 

where the circuit under test may be protected by an RCD.

In No-trip mode the tester can be used with the mains lead when testing at 13A socket 

outlets, or the distribution board lead set for testing at other points in the circuit. 

When testing with the KTD40 in No-trip mode the 3 colour coded prods/crocodile clips 

of the test lead should be connected to the corresponding Line, Neutral and Earth 

terminals.

This mode can be re-selected at any time by pressing button 5 labelled ‘No-trip’.

Отзывы: