Polarity Test Pad
In No-trip mode the tester can be used with the mains lead KAMP12
when testing at 13A socket outlets, or the distribution board lead
set ACC063 for testing at other points in the circuit. In No-trip mode
the 3 colour coded prods/crocodile clips of the test lead should be
connected to the corresponding Line, Neutral and Earth terminals.
Your Kewtech KT63 PLUS tester has a special polarity test function.
It is a little known fact that a system can be reverse
wired with Live (Phase) to earth/neutral and earth/
neutral to Live (Phase) The sockets will all work and
conventional loop testers will show and test that
everything is correct despite this very dangerous wiring
condition.
Although extremely rare, this dangerous condition can
exist so if your test shows this fault do not proceed - if
in any doubt advise your customer to contact their
supply company immediately.
Touch the touchpad area next to the test button. There
should be no change in the indication given. If the
Voltage/Polarity LED flashes Red and a warning tone
is emitted when the touchpad is touched a potentially
dangerous polarity reversal exists. Do not proceed. If in
any doubt advise the customer to contact the electricity
supply company immediately.