Test Procedure
Insert the brown test lead into the brown input terminal & the green test lead into the green
terminal. The brown test lead can be substituted by using the red remote test probe supplied.
This allows remote activation of the KT63 PLUS from the safety of the test probe ensuring
that you are always looking at the point of contact and not the KT63 PLUS.
Select insulation on the rotary switch either 250V, 500V or 1000V setting as required.
Connect the brown test lead to the phase conductor and the green test lead to the other
conductor under test and press the test button.
Press the test button, the tester will beep indicating voltage output through the test leads and
the circuit under test. The display will indicate output voltage then display the result of test in
MΩ. 0V output will indicate if finished and no voltage present.
When test is activated the red Voltage/Polarity will flash warning there is voltage on the leads
and circuit under Test.
Test in progress with
voltage output
Test result
MΩ
TESTING
531
V
Vrms
MΩ
500.0
0
V
Vrms
>