9.0 TECHNICAL DATA
Voltage Range
1…1000 V AC (15…800 Hz),
1…1500 V DC(±)
LED nominal Voltage
120 / 230 / 400 / 690 / 1000 V
LED tolerances
EN 61243-3
ELV indication LED
>50 V AC, >120 V DC
Response time
<1s at 100% of each nominal
LCD Range
1…1000 V, AC (15…800 Hz),
1…1500 V DC(±)
LCD Resolution
0.1 V (1…29.9 V), 1 V
LCD Accuracy
±3% ±1.5 V (1…29.9 V)
±3% ±3dgt (30…1500 V)
LCD Overrange
indication
“OL”
Current Test
0.1…200 A AC(+/-3%+5Dgt)
Resolution 0.1 A
Frequency range 45…65 Hz
Safety current
Is<3.5 mA (at 1000 V AC),
<6 mA at 1500 V DC
Measurement Duty
30 s ON, 240 s OFF
Internal battery
consumption
approx. 120 mA
Single-pole phase
test voltage range
100…1000 V AC (50/60 Hz )
Phase rotation test
170…1000 V phase-to-phase,
AC (40...70 Hz)
Continuity test
0…500 k� + 50%
Resistance
measurement
0…100 k�; accuracy:
±5%±10dgt@25°C;
resolution: 1 � (1-2000 �)
1 k� (2-100 k�)
Frequency
measurement
1…800 Hz ±5%±5dgt;
resolution: 1 Hz
NCV Test
100...1000 V AC (50/60 Hz)
Battery
3 V (IEC LR03 1.5 V x 2)
Temperature
-15…55°C operation;
-20…70°C storage;
No condensation
Humidity
max. 85% RH
Altitude
up to 2000 m
Overvoltage
CAT IV / 600 V, CAT III / 1000 V
Standard
EN/IEC 61243-3:2014
Protection
IP64
10.0 CLEANING AND STORAGE
Tester does not need any special maintenance if
used according to user manual.
Remove tester from all test points before cleaning.
Use a lightly damp cloth with neutral detergent
for cleaning the instrument. Do not use abrasives
or solvents.
Do not expose the instrument to direct sun light,
high temperature and humidity or dewfall.
Remove batteries when the instrument will not be
in use for a long period.
WARRANTY
Our instruments are subject to strict quality control.
However, should the instrument function improperly
during normal use, you are protected by our 2 year
warranty (valid with invoice or receipt).
Within the warranty period we will decide whether
to exchange or repair the defective instrument. We
will repair free of charge any defects in workmanship
or materials, provided the instrument is returned
unopened and untampered with.
Damage due to dropping or incorrect handling are
not covered by the warranty. If the instrument shows
failure following expiry of warranty our service
department can offer you a quick and economical
repair.
Subject to changes without notice.