Loop impedance at the distribution board
Warning: never connect 2 phases to this instrument
Select the 20
Ω
, 200
Ω
or 2000
Ω
range as required
Connect the distribution board lead model ACC016E
to the IEC socket on the instrument
Connect the red phase lead of the ACC016E to 1
phase of the distribution board, the black neutral lead
to the neutral of the distribution board and the green
crocodile clip to the earth
Carry out the initial checks
Press the test button. A beep will sound as the test is
conducted and the value of loop impedance will be
displayed
Wait for the display to indicate the input voltage before
conducting another test or disconnecting from the
distribution board. When disconnecting from the
distribution board, it is good practice to disconnect the
phase first
c
Loop impedance at 3-phase equipment
Use the same procedure as (b) ensuring only
1-phase
is connected at a time
i.e. FIRST test-red prod to
phase 1, black prod to neutral, green crocodile clip to
earth;
SECOND test-red prod to phase 2, black prod to
neutral, green crocodile clip to earth etc.
d.
The ACC016E can also be used for testing at
luminaires
Testing as described in (a), (b), (c) and (d) will measure the
Phase-Earth loop impedance. If you wish to measure the Phase-
Neutral loop impedance in items (b), (c), (d), then same proce-
dure should be followed except the earth clip should be con-