Operating Instructions
5.1 Initial Checks: to be carried out before any testing;
Always inspect your test instrument and lead accessories
for abnormality or damage-
If abnormal conditions exist DO NOT PROCEED WITH
TESTING. Have the instrument checked by Kewtech.
Before pressing the test button, always check the LED's for
the following sequence:
P-E Green LED must be ON
P-N Green LED must be ON
Red LED must be OFF
If the above sequence is NOT displayed or the RED LED is
on for any reason, DO NOT PROCEED AS THERE IS
INCORRECT WIRING. The cause of the fault must be
investigated and rectified.
Voltage Measurement
When the instrument is first connected to the system, it
will display the phase-earth voltage which is updated every
1s. This mode is cancelled the first time the test button is
pressed. If this voltage is not normal or as expected, DO
NOT PROCEED.
NOTE: This is a single phase (230V AC) instrument and
under no circumstances
should it be connected to 2-
phases or a voltage exceeding 10%-15%.
If the input voltage is greater than 260V the display will
indicate ‘VP-E Hi’ and Loop or PSC measurements can not
be made even if the Test button is pressed.
5.2 Measurement of Loop impedance
a. Loop Impedance at Mains Socket Outlet
Select the 20
Ω
, 200
Ω
or 2000
Ω
range as desired