Note: 

Further  information  on  protective  conductor  resistance  and  testing  of 

portable appliances can be found in the Code of Practice for In-service Inspection 
and Testing of Electrical Equipment published by the IEE. 
 

 

4. Preparation before a measurement 

 

4.1 Visual inspection 

Before starting a measurement, the user should undertake visual checks on the 
mains lead, case and that the correct type and rated fuse is fitted to the appliance 
under  test.  There  should  also  be  no  evidence  of  damage  of  a  nature  that  may 
impair the electrical safety of the appliance. 
 

4.2 Battery Voltage Check   

(1)  Insert batteries with reference to 

7. Battery/ Fuse Replacement

 in this manual. 

(2)  Hold down Power switch 2 sec. to turn on the Tester. 
(3)  Check the battery indicator displayed in the upper left corner of the LCD. 

If just the last one segment of the indicator remains, the battery voltage is   
extremely low. Refer to 

7. Battery/ Fuse Replacement

 and replace batteries to 

perform further measurements. 

If  an  empty  battery  indicator  is  displayed,  the  battery  voltage  is  lower  than  the 
working  voltage  limit.  Replace  batteries  immediately  to  keep  accurate 
measurement. 

 
Battery recommendation: 
Use of alkaline battery is recommended. Use of other type of batteries may cause 
improper indication of battery level. 
 

4.3 Setting 
4.3.1 Null setting 

The IEE Code of Practice pass level for Protective conductor resistance is 0.1 

Ω

which  is  a  low  value.  So  even  the  resistance  of  Test  Leads  will  affect  the 
measurement result. 

The  Tester

  can  cancel  the  resistance  of  test  lead  by  pressing 

NULL

.  The 

procedure  of  Null  setting  is  shown  below.  The  Null  function  is  held  in  memory 
even when the Tester is turned off, so there

’s no need to Null the lead resistance 

every time. However, when replacing fuses or test leads, it is recommended to do 
a Null setting again.

 

 

Note: 
Null setting is possible at both Class l Test and Extension Lead Test. However, 
only one Null value can be held in memory. For example, when the Null setting 
is carried out at Class l Test, the set value will also be used for Extension Lead 
Test (unless it is reset). 

Содержание EZYPAT

Страница 1: ...EZYPAT EZYPAT SMARTPAT PORTABLE APPLIANCE TESTER INSTRUCTION MANUAL...

Страница 2: ...4 Preparation before a measurement 17 4 1 Visual inspection 17 4 2 Battery Voltage Check 17 4 3 Setting 17 4 3 1 Null setting 17 4 3 2 Voltage setting for insulation resistance measurement 18 How to c...

Страница 3: ...ocedures It is essential to read and to understand the safety rules contained in these instructions and with the safety procedures The symbol indicated on the Tester means that the user must refer to...

Страница 4: ...inspection and repair Never attempt to use the Tester if the Tester or your hands are wet CAUTION When using Test Leads with the crocodile clip be sure to check the crocodile clip is firmly connected...

Страница 5: ...T III environments can endure greater momentary energy than one designed for CAT II O Circuits which are not directly connected to the mains power supply CAT II Electrical circuits of equipment connec...

Страница 6: ...ften described as earthed appliances Class II Appliances which have both functional and additional insulation where any metal parts cannot become Live under fault conditions 2 2 Test Function Availabl...

Страница 7: ...ty test 1 sec Long press Starts CLI test Continuity test 5 sec CLII switch Starts CLII test Extension switch Short press Starts Extension lead test Cont test 1 sec Long press Starts Extension lead tes...

Страница 8: ...250 V and 500 V Default setting 250 V Long press Switches threshold current for CL I leakage current test between 0 75 mA and 3 5 mA Default setting 0 75 mA Light switch Short press Turns on off LCD...

Страница 9: ...t test under actual working condition Rated current for RCD test Measurement in process Switches are locked and Tester is in remote test mode The Tester is being controlled via a tablet device Protect...

Страница 10: ...larity test Crossed L N polarity warning resistance between L N N L is 10 or lower at polarity test Short circuited L N warning resistance between L N is 100 k or lower at insulation test Extension Le...

Страница 11: ...connected to a mains supply via EZYMAIN 3 PE probe terminal Connect the Test Lead with alligator clip to this terminal for the measurement of protective conductor resistance and clip the metal parts o...

Страница 12: ...rchangeable Please use it according to a measurement use 1 Protective finger guard is a part providing protection against electrical shock and ensuring the minimum required air and creepage distances...

Страница 13: ...test Measuring range 0 00 20 00 NULL value included Over range indication 20 00 Resolution 0 01 Open circuit voltage 5 V 0 4 V DC Measuring current 200 mA DC nominal value Accuracy 3 rdg 5dgt Resistan...

Страница 14: ...age current test Measuring range 0 10 12 00 mA rms Over range indication 12 00 mA Resolution 0 01mA Open circuit voltage Freq 30 V 5 V rms 50 Hz 5 Measuring current 1 2 mA AC 0 5 mA when measuring 12...

Страница 15: ...Rate voltage and frequency EZYPAT SMARTPAT Rated voltage 230 V 10 15 Rated frequency 50 Hz Maximum load current at test socket EZYPAT SMARTPAT 3 kVA 15sec Outer dimension and weight Outer dimension 2...

Страница 16: ...treated as household waste but that it must be collected and treated separately 3 3 Threshold and display Function Protective conductor resistance Insulation resistance Leakage current Class l RPE 0...

Страница 17: ...on flexible cable mm2 Length m Resistance at 20 Max carrying current A 0 5 1 0 04 3 2 0 08 3 0 12 4 0 16 0 75 1 0 025 6 2 0 05 3 0 08 4 0 10 5 0 13 1 0 1 0 02 10 2 0 04 3 0 06 4 0 08 5 0 10 1 25 1 0...

Страница 18: ...ries to perform further measurements If an empty battery indicator is displayed the battery voltage is lower than the working voltage limit Replace batteries immediately to keep accurate measurement B...

Страница 19: ...d subtracted from the further measured values 4 If the measured value is less than 3 previous NULL value is cleared and a new value is saved When 3 or higher is measured previous NULL value is just cl...

Страница 20: ...I CL II Extension lead test changes 0 75 mA and 3 5 mA Default setting is 0 75 mA The Code of Practice for In service Inspection and Testing of Electrical Equipment specifies 0 75 mA for portable or h...

Страница 21: ...liance One is RUN leakage current test with the Tester connected to an outlet and another is SUBSTITUTE leakage current SUB leak current test without connecting the Tester to an outlet To perform Clas...

Страница 22: ...3 Leakage current test RUN Leak test Connect Tester to outlet Load current is also measured SUB leak test Not connect Tester to outlet RUN leak test Connect Tester to outlet SUB leak test No need to...

Страница 23: ...continuity test is regarded as PASS Rpe 0 88 FAIL Rpe 0 11 PASS 2 Insulation resistance test 1 Continuity test DUT is ON DUT is OFF Voltage value is displayed while the Tester is connected to an outl...

Страница 24: ...ns 1M PASS Rins 1M FAIL Mains voltage is 100 V or higher Mains voltage is less than 100 V SUB leakage test ILEAK 0 75mA 3 5mA PASS ILEAK 0 75mA 3 5mA FAIL Check screen for RUN leakage test Buzzer soun...

Страница 25: ...nner It is imperative that the appliance is secured safely before the test is carried out Extra care needs to taken with appliances which have heating elements and rotating parts Firmly insert the plu...

Страница 26: ...ss ll Test The Class ll appliances have the indication of DOUBLE INSULATION or the symbol Class II test is performed to confirm insulation resistance and leakage current of the appliance are within th...

Страница 27: ...let Load current is also measured SUB leak test No need to connect Tester to outlet Connect to exposed metal parts but not rotating parts or heating elements Switch ON the power Press CLII switch to p...

Страница 28: ...FF DUT is ON DUT ON Check Insulation resistance test DUT is powered on or CL2 is pressed Press to halt a measurement in process Tester performs next test when CL II switch is pressed while a test is h...

Страница 29: ...st Rins 2 M PASS Rins 2 M FAIL Mains voltage is 100 V or higher Mains voltage is less than 100 V SUB Leakage test ILEAK 0 25mA PASS ILEAK 0 25mA FAIL Check screen for RUN leakage test Buzzer sounds an...

Страница 30: ...hich has a power consumption of 3 kVA or more CAUTION Where DUT ON Check function detects the DUT is off blinking OFF appears in the LCD and the test is stopped Turn on the DUT then the Tester automat...

Страница 31: ...nnection of protective earth Insulation resistance between L N and PE Polarity check of the Line and Neutral terminal of plug and socket 1 Continuity test For PE terminal of Extension Leads 2 Insulati...

Страница 32: ...of continuity test Continuity test 0 11 0 88 tAbL Rpe 0 88 FAIL Rpe 0 10 PASS Press to proceed to the next continuity test is regarded as PASS Insulation resistance test between 1 L N E 2 L N L N E 1M...

Страница 33: ...short EZYEXT lead instead of the MODEL7208 test lead by plugging the EZYEXT into the Extension Lead Adaptor terminal and the UK socket on the front of the unit When the terminal is open or the resist...

Страница 34: ...Tester incorporates a circuit to test PRCD with Rated Tripping Current I n of 10 mA or 30 mA PRCD trip time is measured in sequence 1 0 1 180 5 0 5 180 After each test reset the tripped PRCD to procee...

Страница 35: ...34 RCD Test Flow 30mA 10mA Stand by state Long press switches I n 10 mA and 30 mA RCD test stand by screen 1 0 test 1 0 test result Reset the tripped RCD Press to halt a measurement in process...

Страница 36: ...180 test 1 180 test result Reset the tripped RCD 5 0 test 5 0 test result Reset the tripped RCD 5 180 test Test results are all PASS If any one of test results is FAIL FAIL is displayed PASS is displ...

Страница 37: ...eds 50 V while applying a test current to test a built in type RCD the LCD shows Uf Hi and the test is halted If a voltage exists between the protective conductor and earth it may influence the measur...

Страница 38: ...ay be incurred For further detail please refer to Help for SimplyPats Remote settings To use the remote control function of SMARTPAT enable Wi Fi function and remote mode Hold down the backlight switc...

Страница 39: ...le electric shock remove test leads before opening the battery cover After replacing batteries be sure to tighten up the screws for battery cover CAUTION Do not mix new and old batteries Install batte...

Страница 40: ...ptive and open the battery compartment cover to replace the fuse Fuse type 10A 250V F Fast acting type ceramic fuse 5 x 20mm 3 Screw the battery cover back on before using the Tester 9 Maintenance Use...

Страница 41: ...40 Kewtech Corporation Ltd Midas House Unit 2b Stones Courtyard High Street Chesham Buckinghamshire HP5 1DE www kewtechcorp com 92 2287 06 17...

Отзывы: