Connect the connection cable and probe cable
Open the housing cover
(see "Fig. X").
Cut off the connection plug and dispose of it (optical
probe only).
Pull the connection cable through the cable glands.
Fasten the connection cable to the terminal
strips as shown in the connection diagram (
see
"Anschlussplan"
).
To do so, use a suitable screwdriver to hold down the
respective cable terminal against the spring pressure until
the cable end has been inserted.
Attach strain relief fittings for all cables.
Note the screw torque of 0.5 Nm.
Fit and fasten the housing cover, tightening torque 1.2
Nm.
4.4
Mount the accessory parts
The terminal block "Alarm" has been preset for connec-
tion of the audible alarm unit. If a potential-free contact is
to be used, the terminal block must be cleared for this (see
"Potential-free contact" section).
Prepare housing and cable duct (as explained in Chap. (
"Connecting the probe", page 32
). Use the outside right
cable duct.
EN
016-207_01
Installation and operating instructions
33 / 128
Содержание Aqualift Duo
Страница 67: ...IT 016 207_01 Istruzioni per l installazione e l uso 67 128...
Страница 108: ...PL 108 128 Instrukcja zabudowy i obs ugi 016 207_01...
Страница 123: ......
Страница 124: ...124 128 016 207_01...
Страница 125: ...016 207_01 125 128...
Страница 127: ...016 207_01 127 128...