5
Commissioning
The control unit performs the following additional functions automatically:
Checking the battery voltage
The control unit checks the battery voltage 2x daily and signals a battery error (potential-free contact “fault”) if the voltage
falls below a certain level. Optical and acoustic warning signals appear on the control unit every 20 seconds.
SDS Self diagnosis system
The control unit has an automatic self-check, which performs a functional check of the connected components automatically.
Preset test cycle:
every 28 days (freely adjustable)
5.1
Switch on
Open housing (anticlockwise).
Connect battery(ies).
Close housing (clockwise).
Connect to the mains.
Check whether the |
0 System info|
menu appears.
This indicates a successful system test. If the
|0 Sys-
tem info|
menu does not appear, initialise as
described below.
Green LED indicates standby state (ready for operation).
5.2
Carrying out initialisation
During initialisation, the following input is expected:
|Language|
|Date / Time|
|Product type|
|Maintenance interval|
Language
► Press OK.
► Use the cursor keys to select the language and confirm
with OK.
Menu
|Date/Time|
appears.
Date / Time
► Set the respective flashing figure in date and time and
confirm with OK.
Menu
|Product type|
appears.
Product type
► Select product type and confirm with OK.
Selection affects which setting options are available.
Menu
|Maintenance interval|
appears.
Maintenance interval
► Enter the maintenance interval specified in the standard.
Initialisation is completed, control unit is ready for use.
Fig. 3: Navigating in the menu
(1)
Confirm by pressing "OK"
(2)
Scroll down
(3)
“ESC” - back
(4)
Scroll up
The first time pressing of the OK button activates control
mode at the control unit. (The display lights up).