8
Weight empty approx. 28 kg
Operation weight (full with water) approx. 45 kg
3.2 Control unit
The technical data can be found in the enclosed original ope-
rating manual.
3.3 Floating switch
Operating temperature
0 - 50°C
Operating pressure
3,5 bar
P min/max 0,2 - 6 bar
3.4 3-way switch-over valve
Voltage / Frequency
230 V AC / 50 Hz
Power consumption
4 VA (with valve movement)
Protective rating
IP 40
Operating time
7 seconds
Max. pressure difference 4 bar
Cv-values
7,7 (corresponds to a drop in
pressure of about 0.17 bar with a
flow rate of 3 m
3
/h)
Further specific technical data can be found in the enclosed
original operating manual
3.5 Automatic pressure switch
Voltage / Frequency
230 V AC / 50 Hz
Switching capacity
max 10 A or max 1,8 kW
Protective rating
IP 55
Mains connection cable 1,4 m
Network connection
0,3 m
Switch-on point
2,4 bar (uppermost tapping point
is max. 20 metres above the au-
tomatic pressure switch)
Switch-off point
Water consumption ≤ 0,5 l/min or
during dry run
Pressure difference
min 0,7 bar (between switch-on
and switch-off point)
The pump is put back into operation after dry running by
pressing the “RESET” button
Drop in pressure
approx. 0.3 bar with a flow rate of
3 m
3
/h
Manometer
Display range 0 - 10 bar
Pumping medium
Clear water
Dimensions l x w x h in mm 214 x 128 x 154
Inlet nozzle
1ʼʼ Outer thread
Outlet nozzle
1ʼʼ inner thread
Further specific technical data can be found in the enclosed
original operating manual.
3. Technical Data
3.1 Dimensions and weight:
Sauganschluss
Druckanschluss
Trinkwasser-
anschluss
Notüberlauf
596
160
76 80
235
80
160
370
40
76
300
335
463
727
Pipe routing
Suction connection
Pressure connection
Drinking water
connection
Emergency overflow