K4C COMPACT-MULTI – INSTALLATION/OPERATION MANUAL 

 

K4C Compact-multi

 

Feb

-06

 

9

 

UNIT WIRING 

Caution:  

Disconnect the electrical power when wiring the unit. 

INSTRUCTIONS 

Wire the blocked vent switch in accordance with The National 
Electrical Code and applicable local codes.  Wire the safety switch 
in series with the burner limit control or aquastat.  See the 
appliance-wiring diagram in the manual or wiring label.  Route the 
wiring with an accepted wiring enclosure in accordance with The 
National Electrical Code and applicable local codes. 

SYSTEM TEST PROCEDURE

 

1.  With the power re-established, block the chimney or vent pipe down stream of 

the switch. 

2.  Adjust the thermostat to call for heat. 
3.  Once the heating system has started the blocked vent switch should shut down 

the burner with 10 minutes or sooner. 

4.  Once the system has cooled, the blocked vent switch can manually be reset. 
5.  This procedure should be tested a second time. 
6.  After testing the blocked vent switch the chimney should be cleared of 

obstruction and the heating system tested on a long run cycle. 

7.  If the block vent switch shuts down the system check to ensure there is enough 

draft in the chimney and venting pipes. 

 

3.15  FAN CONTROL 

 

LIMIT   

200°F - Factory set 

FAN ON

 

130°F 

FAN OFF 

100°F 

 

3.16  COMBUSTION & VENTILATION AIR

 

 

Install openings and ductwork to the furnace room to provide

 

fresh outside combustion 

air and circulation air for cooling the furnace casing as installation code requires (USA: 
NFPA 31, Canada: CSA B139).  If installed in a closed room, provide two free air 
ventilation openings of at least 8” x 12” (96sq. in.) free flow area near ceiling and floor.  
Oil burners must have sufficient air to allow vent systems to operate properly.  Not 
applicable to Direct Vent. 

 

3.17 OFF CYCLE AIR CIRCULATION 

 

#4 LO SPEED 

All furnace models have the #4 Lo speed switch for optional 
constant air circulation during the furnace off cycle. 

 

“FAN ON” 

When “FAN ON” is selected on the T87F thermostat, the blower will 
run constantly at the #1 Hi speed providing heat, cooling or neither 
as selected. 

 
 
 
 
 
 

Содержание COMPACT-multi

Страница 1: ...AL CODES THAT MAY DIFFER FROM THIS MANUAL Please read this complete manual before beginning installation These instructions must be kept with the furnace for future reference CERTIFIED TO CAN CSA Std...

Страница 2: ...acement Venting Ventilation 4 3 6 Installation 5 3 7 Assemble Install Burner 6 3 8 Changing Nozzle 7 3 9 Set Burner for Efficient Operation 7 3 10 Blower Setting 8 3 11 Cooling AC Models 8 3 12 Humidi...

Страница 3: ...intain furnace performance and safety replace dirty filters as required or at least once every heating season Use new approved disposable filters of the same size and type or clean permanent filters a...

Страница 4: ...k that the furnace starts and operates as usual CHECK If the furnace system fails to operate or operates in an unusual manner call your service technician OPERATION If the burner fails to operate at a...

Страница 5: ...conventional upflow mode in horizontal mode or as a downflow furnace The breech is convertible from front to rear by switching the breech pipe and cover plates The burner is always installed in an up...

Страница 6: ...floor Oil burners must have sufficient air to allow vent systems to operate properly See furnace operating label Not applicable to Direct Vent 3 6 INSTALLATION ELECTRICAL Wire according to the Nationa...

Страница 7: ...limit controls should be FAN OFF 100 F FAN ON 130 F If the K4C is used in a down flow position with the Scotty SS a diverter base is available for easier duct connections K4C KA 0400 00 3 7 ASSEMBLE I...

Страница 8: ...e Use two barometric dampers if necessary Not applicable to Direct Vent BURNER SETTING Set the burner to give a stable symmetrical flame After 15 minutes of normal operation check SMOKE for 0 trace re...

Страница 9: ...that no water can drip or run from it into the furnace This would cause deterioration and void the furnace warranty 3 13 THERMOSTAT ANTICIPATOR SETTING 0 2 amps for any burner Check that the thermost...

Страница 10: ...nd time 6 After testing the blocked vent switch the chimney should be cleared of obstruction and the heating system tested on a long run cycle 7 If the block vent switch shuts down the system check to...

Страница 11: ...F Outlet air gets too warm and burner shuts down increase air by changing the blower motor speed to give the specified temperature rise 70 85 F Outlet air is too warm or too cold at the end of the hea...

Страница 12: ...mation is available at www kerrheating com ONE PIPE SYSTEM Where the tank is above the burner and when the oil flows by gravity to the oil pump a single stage fuel unit with a single oil line to the p...

Страница 13: ...26 1180 1090 3 2 0 59 2 23 50 70 45 B 140 55 70 000 21 990 990 4 3 K4CD 090 A3 Beckett AFG PA404 0 71 2 69 60 70 45 B 140 60 84 000 25 1180 1090 3 2 Post purge factory set to two minutes Low firing r...

Страница 14: ...402 404 2 1 2 63 mm AIR BLOWER DATA External static Non AC 0 2 wc External static AC 0 5 wc Cooling 3 tons Maximum air temperature rise 85 F High Limit max design outlet temp 200 F Thermostat anticipa...

Страница 15: ...75 F Certified for use with Kerr Direct Vent Certified for use with Kerr KPV SS1C through the wall mechanical vent system 10 0 TROUBLE SHOOTING GUIDE Furnace will not start Tripped blocked vent switch...

Страница 16: ...unning through Change or insulate ductwork unheated spaces Low speed switch is on Switch off blower low speed FAN OFF set low Fan control Set FAN OFF higher Motor speed set too high Reset motor speed...

Страница 17: ...T UP TEST RESULTS Nozzle ________________________________________ Pressure _______________________________________________ Air ____________________________________________ Turbulator _________________...

Страница 18: ......

Страница 19: ......

Страница 20: ......

Страница 21: ...Cover No Hole K4C 18 Divider Assembly K4C 19 Base Pan K4C 20 Blower Key K4C 21 Delhi GT10 DD Blower K4C 22 Motor Run Capacitor 5 micro farad Not Shown K4C 23 Motor 1 3 G E 5KCP39KGT192S K4C 24 Blower...

Страница 22: ......

Страница 23: ......

Страница 24: ......

Страница 25: ......

Отзывы: