PXL-500 / PXL-510 Tiger Controller
Quick Start Guide
Page 7 of 24
P/N: 01918-001 Rev. A
NOTE: Time and Attendace Terminals ordered with a reader installed come pre-wired.
•
The "A" reader is wired to TB5.
•
The "B" reader is wired to TB6.
Figure 4: Proximity Reader Connections
4.4
Connecting a Wiegand Compatible Reader to a PXL-500W/PXL-510W
The PXL-500W/PXL-510W controller can be configured to accept input from single-line LED, dual-line LED, and Essex
keypad Wiegand input devices (through the
Doors
™ software).
NOTE: The Wiegand Reader must transfer data according to the Security Industry Association's Wiegand Reader
Interface Standard (document number AC-01D-96). Keri Systems, Inc. cannot guarantee the performance or reliability of
Wiegand Readers that do not meet these data transfer guidelines.
NOTE: All Keri Systems proximity readers use 12 VDC power while some Wiegand compatible readers use 5 VDC power.
Check your reader's power requirements and verify jumper JP5 is set correctly per the Verify the Wiegand Reader Supply
Voltage section on page 19.
NOTE: The wire colors called out in Figures 5 and 6 are industry standard wire colors. However, some manufacturers
may not follow these industry standard designations. Before installation, please refer to the Wiegand device’s manual to
see if the device’s wire colors follow the industry standard. If not, then match the wire’s purpose to the call outs in Figures
5 and 6 before installation.
NOTE: Time and Attendace Terminals ordered with a reader installed come pre-wired.
Make the following connections for a single-line LED or Essex Keypad Wiegand device.
•
The "A" input device is wired to TB5.