background image

3-6

MST-MHT SERIES 071320

Status bit 4 appears in the Questionable register of the MST 488-27HT controller indicat-
ing a catastrophic failure. Upon receiving status bit 4, the Controller removes that Con-
trol Bus address from the look-up table, preventing further commands from being 
directed to the faulty power module.

b. Fault Shutdown with Output disabled - If an open sense lead condition is detected, the fault

shutdown procedure is as follows:

All output power and signal relays are immediately opened, isolating the Power Module 
from the load;

Output voltage and current are programmed to zero;

If open sense caused the failure, status bit 10 appears in the Questionable register of the 
MST 488-27HT controller.

3.7.1

FAULT RECOVERY

Recovery from any fault condition (described above) requires that the user cycle source power
off for a minimum of 5 seconds. After reapplication of source power, a IEEE 488 DCL (device
clear) command must be sent to the controller to restore the module’s Control Bus address to
the look-up table. This procedure eliminates any possibility of casual reapplication of a Power
Module to the system load after symptoms of a catastrophic module failure have been detected. 

3.7.2

FIXED OVERVOLTAGE DETECTOR

The output stabilizer control circuitry of the MST-MHT Power Module includes a fixed overvolt-
age amplifier. This devices monitors the actual output voltage supplied by the Power Module
and compares it to a fixed reference voltage. In the event that a parameter exceeds the fixed
voltage limit by an amount equal to 10% of the Power Module’s rated voltage, the circuit initiates
a fault shutdown procedure as described in PAR. 3.7a. The tolerance of the fixed overvoltage
hardware trigger is the minimum value listed in Table 1-1, +6%. 

3.7.3

OVERCURRENT TRACKING DETECTOR

The output stabilizer control circuitry of the MST-MHT Power Module includes a separate over-
current tracking amplifier. This device monitors the actual output current supplied by the Power
Module and compares it to the programmed current value. In the event that actual current
exceeds the programmed current by an amount equal to 10% of the Power Module’s rated cur-
rent, the circuit initiates a fault shutdown procedure as described in PAR. 3.7a The tolerance of
the current fault threshold is ±3%.

3.7.4

OVERTEMPERATURE DETECTORS

Any one of a number of internal or external conditions (i.e., elevated ambient temperature,
clogged vent holes, cooling fan failure, etc.) can cause elevation of internal heat sink tempera-
tures to unsafe levels. If unattended, the resultant temperature rise of the power devices will
lead to eventual destructive failure. MST-MHT Power Modules incorporate two internal thermo-
static switches to detect unsafe internal operating temperatures. One is located on the heat sink
related to the input preregulator and dc-dc converter, while the second monitors the heat sink
related to the output stabilizer. If the temperature of either heat sink rises above a predeter-
mined safe temperature, the related thermostat will change state, initiating a fault shutdown as
described in PAR. 3.7a. The thermostat will reset upon return of the heat sink to acceptable
operating temperature, however the module recovery procedure (see PAR. 3.7.1) must still be
performed.

Содержание MST 100-2MHT

Страница 1: ...revision for your par ticular model and serial number 3 The contents of this manual are protected by copyright Reproduction of any part can be made only with the specific written permission of Kepco I...

Страница 2: ......

Страница 3: ...ired equipment rack utilizing a three wire grounded mains connection See wiring section of this manual for complete electrical wiring instructions EN61010 1 2001 Cl 6 10 1 4 This power supply has seco...

Страница 4: ...performing any servicing This product is designed for use with nominal a c mains voltages indicated on the rating nameplate The PROTECTIVE EARTHING CONDUCTOR TERMINAL must be properly con nected prio...

Страница 5: ...ounding 2 6 2 6 2 D C Output Grounding 2 6 2 7 Preliminary Check out 2 7 2 7 1 Required Equipment 2 7 2 7 2 Initial Setup 2 7 2 7 3 Checkout Procedure 2 9 2 8 Power Module to Load Interface 2 10 2 9 C...

Страница 6: ...ode Protection 3 7 3 9 Calibration 3 8 3 9 1 Equipment Required 3 8 3 9 2 5 Volts Reference Adjust R49 3 10 3 9 3 Output Voltage EO Zero Adjust R11 3 10 3 9 4 Current Sense Zero Adjust R50 3 10 3 9 5...

Страница 7: ...iguration for Preliminary Checkout 2 9 2 5 Output Impedance vs Frequency 2 11 2 6 Connector Locations and Pin Assignments 2 13 3 1 Calibration Test Set up 3 10 1 1 MST MHT Model Parameters 1 2 1 2 MST...

Страница 8: ...iv MST SERIES 071320 FIGURE 1 1 MST POWER SUPPLY...

Страница 9: ...nts current share hot swap built in polarity reversal constant current mode and greater power 180W to 200W MST MHT power modules employ a switch mode preregulator for high efficiency and power density...

Страница 10: ...x TABLE 1 2 MST MHT GENERAL SPECIFICATIONS SPECIFICATIONS RATING DESCRIPTION CONDITION INPUT A C Voltage nominal 100 250V a c Single phase range 90 264 Va c Brownout Voltage 85Vrms Frequency nominal 5...

Страница 11: ...condition Isolation Output Case 500 V d c Display Voltage 3 5 Digit LED red Front panel For reference only Current 3 5 Digit LED red Status Indicators Voltage Mode Green LED Current Mode Amber LED Cur...

Страница 12: ...ilent HP 66000 Series PHYSICAL Type of Construction Enclosed plug in style includes status LEDs two digital meters handle and ON OFF switch Cooling Internal D C Cooling Fans Exhaust to rear Module Dim...

Страница 13: ...MST MHT SERIES 071320 1 5 FIGURE 1 1 MST MHT POWER SUPPLY MECHANICAL OUTLINE DRAWING...

Страница 14: ...isabling the MST MHT as a current source means shorting the power supply s output terminals Polarity reversal relays are installed but not supported at this time If polarity reversal is needed refer t...

Страница 15: ...Adapter Additional accessories are listed in Table 1 3 TABLE 1 3 ACCESSORIES ACCESSORY PART NUMBER USE OUTPUT LOAD CONNECTOR ADAPTER supplied with RA 55H Rack Adapter KIT 219 0618 Allows output load c...

Страница 16: ......

Страница 17: ...lt age and frequency ranges without adjustment or modification 2 4 COOLING The power transistors and rectifiers in the MST MHT Power Module are maintained within their operating temperature range by m...

Страница 18: ...rce see PAR 3 2 1 CURRENT MODE indicator amber LED Goes on to indicate MST MHT is operating as a current source see PAR 3 2 2 POLARITY REVERSED indicator green LED Goes on when negative output program...

Страница 19: ...h the top of the unit see Figure 2 2 and can be changed in accordance with Table 2 4 This address is set at Kepco to 1 NOTES 1 Although 31 unique addresses are provided the maximum number of instrumen...

Страница 20: ...1 0 0 13 0 1 1 0 1 14 0 1 1 1 0 15 0 1 1 1 1 16 1 0 0 0 0 17 1 0 0 0 1 18 1 0 0 1 0 19 1 0 0 1 1 20 1 0 1 0 0 21 1 0 1 0 1 22 1 0 1 1 0 23 1 0 1 1 1 24 1 1 0 0 0 25 1 1 0 0 1 26 1 1 0 1 0 27 1 1 0 1...

Страница 21: ...in use refer to PAR 2 5 1 to change the address setting NOTE If the Power Module is already installed in a Rack Adapter and it is necessary to change the control bus address the Power Module must firs...

Страница 22: ...formance considerations and safety requirements For optimum performance certain rules must be observed These rules are described in detail in the following paragraphs 2 6 1 SAFETY GROUNDING National a...

Страница 23: ...circuit and returned to ground with a single wire This method is dependent on the specific application 2 7 PRELIMINARY CHECK OUT 2 7 1 REQUIRED EQUIPMENT Host computer w communication cable for select...

Страница 24: ...d i e a c power applied to the Controller first and MST MHT power modules last the operator must send an IEEE 488 Device Clear command via the Host Computer prior to issuing other commands For proper...

Страница 25: ...mands from the host computer to set the MST MHT Power Module to Voltage Mode program output voltage to EMAX current limit to IMAX and enable the output e g for MST 36 5MHT issue the following commands...

Страница 26: ...current MEAS CURR Verify that read back current is IMAX e g 5A for MST 36 5MHT 2 8 POWER MODULE TO LOAD INTERFACE The general function of a voltage or current stabilized Power Module is to deliver rat...

Страница 27: ...put of the Power Module is step programmed The load is reactive Dynamic output response of the Power Module is of concern 2 9 CONNECTION GENERAL All input and output connections between the Power Modu...

Страница 28: ...terminals directly to the load will compensate for voltage drops in the load interconnection scheme up to 0 5V maximum per wire the termination point of the error sensing leads should be at or as clo...

Страница 29: ...071320 2 13 2 14 Blank FIGURE 2 6 CONNECTOR LOCATIONS AND PIN ASSIGNMENTS NOTE To remove Adapter Kit 219 0618 refer to Kit 219 0618 RA 55 Connector Adapter Kit Instruction Sheet see PAR 1 1 for downlo...

Страница 30: ......

Страница 31: ...ST 488 27HT Controller see PAR 1 1 Table 3 1 lists the catastrophic status messages along with the related MST MHT Power Module condi tion 3 1 2 TIMING REQUIREMENTS FOR A VALID STATUS After sending a...

Страница 32: ...n or equal to the critical value indicated above will result in automatic return to normal operation 3 2 2 CURRENT MODE In this mode the Power Module is programmed to behave as a current source The us...

Страница 33: ...Power Modules is limited to a maximum value which may in some cases be inadequate to fully discharge all external load capacitance To ensure dry relay switching for all output conditions the user mus...

Страница 34: ...tage range GL Io VMAX For an ideal current source a no load condition is then defined as infinite conductance zero impedance since this is the only load condition at which the delivered power is zero...

Страница 35: ...true if modules are disabled sequentially 3 6 SERIES OPERATION MST MHT Power Modules are designed to allow series operation to achieve higher output volt age if desired Series operation requires deta...

Страница 36: ...unt equal to 10 of the Power Module s rated voltage the circuit initiates a fault shutdown procedure as described in PAR 3 7a The tolerance of the fixed overvoltage hardware trigger is the minimum val...

Страница 37: ...OUTPUT FAULT indicator to determine recovery action If the indicator is on refer to PAR 3 7 1 for recovery If the indicator is off send RST to recover The open sense power wire protection circuitry ca...

Страница 38: ...d in Table 1 1 IMAX is the maxi mum output current of the unit as listed in Table 1 1 for 45 C 3 9 1 EQUIPMENT REQUIRED Calibration of MST MHT Series Power Modules requires the following equipment Hos...

Страница 39: ...MST MHT SERIES 071320 3 9 FIGURE 3 1 CALIBRATION TEST SET UP O2 S2 CS GND S1 O1...

Страница 40: ...arison amplifier to be zero for a pro grammed output voltage of zero 1 Configure DC OUTPUT connector as shown in Figure 3 1 and open S2 2 With the load disconnected issue commands from the host comput...

Страница 41: ...ge Mode program current limit to IMAX output voltage to EMAX and enable the output 2 Verify VOLTAGE MODE and OUTPUT ENABLED indicators are on 3 Connect the voltmeter to DC output connector see Figure...

Страница 42: ...Current Mode with output disabled to avoid drift due to temperature fluctuations 2 Enable the output and verify that CURRENT MODE and OUTPUT ENABLED indicators are on 3 Record the output current as m...

Отзывы: