HSMSERIES OPR 052912

3-5

The signal generated by the OVP detector is gated with a signal from the fault detector circuit to
produce a selective overvoltage shutdown function which prevents shutdown of operational
power supplies in a parallel-redundant power system configuration.  The OVP latches of any
working power supplies are disabled, allowing only the faulty modules to be latched off; system
operation can then return to normal, assuming sufficient load capacity in the remaining modules
to support the load. This function is critical in fault-tolerant power systems, otherwise a single
overvoltage failure could ripple through all of the operating supplies and result in a complete
power system loss.

NOTE:

The overvoltage protection circuit senses the voltage 

directly at the output terminals

of the power supply, not at the error sensing point.  When selecting an overvoltage set
point, the user must take into account the expected power lead voltage drop and, if
applicable, the transient response overshoot in order to avoid false shutdowns.  The
HSM design is such that the power supply cannot generate an output voltage high
enough to cause internal damage, regardless of OVP setting.

3.9

CURRENT LIMIT CHARACTERISTIC

HSM power supplies provide two different current limiting modes for different applications;
selection of the desired mode is accomplished via switch S1-3, accessed through the top cover
of the HSM (see Figure 2-1).  The following describes the operational differences and selection
method of each:

a) Continuous Limiting: 

This is the factory-set (default) mode of operation.  When the output

current of the power supply reaches the programmed current limit, the output regulator
switches to current mode operation and maintains the output current by modulating the out-
put voltage; this operating mode is maintained indefinitely, and recovery to voltage regulation
mode is automatic upon reduction of the output current below the current limit point.  This
mode is ideal for high-power battery chargers and applications where operation in current
regulation mode is normal, or where immediate recovery from an overload condition of any
duration is critical.

NOTE:

HSM power supplies are designed to maintain continuous delivery of 110% of rated
current indefinitely.  When operating parallel/redundant power supply configurations in
continuous limiting mode, the user must size the power supply/load interconnection
conductors to withstand the total maximum load current available from all of the paral-
leled power supply modules.   

b) Undervoltage Lockout: 

This mode is enabled when S1-3 is set to ON (Figure 2-1).  The

crossover from voltage- to current-mode operation is the same as for Continuous Limiting;
however, after approximately 15 seconds, the output load regulation circuit is locked off via
the overvoltage protection latch, requiring the user to recycle source power to restart the
power supply (see PAR. 3.8).  This mode permits automatic recovery from short-term over-
loads, but eliminates the danger of overheating and damage to the load and load wiring due
to continuous exposure to high current; this is especially useful in redundant power systems,
where the continuous overload current of all of the paralleled power supply modules can be
in excess of twice the normal load current.  As the circuit is triggered by the occurrence of an
output undervoltage condition, this circuit can also protect circuits which may be unduly
stressed in the presence of an extended undervoltage condition; an example of this are bat-
teries, which can be damaged by discharge voltages below a specified minimum. 

NOTE:

  When undervoltage lockout mode is enabled, it is necessary to also enable the

Remote Reset function (see PAR. 3.12) in order for the Remote Inhibit function to oper-
ate properly.

Содержание HSM 12-84

Страница 1: ...n New York 718 461 7000 requesting the correct revision for your particular model and serial number 3 The contents of this manual are protected by copyright Reproduction of any part can be made only w...

Страница 2: ......

Страница 3: ...7 Wiring Instructions 2 4 2 7 1 Safety Grounding 2 4 2 7 2 Source Power Connections 2 4 2 7 3 D C Output Grounding 2 5 2 7 4 Power Supply Load Interface 2 5 2 7 5 Load Connection General 2 6 2 7 5 1 L...

Страница 4: ...d II Remote Error Sensing 2 8 2 5 Load Connection Method III Series Connection 2 9 2 6 Load Connection Method IV Parallel Redundant Operation wit Hot Swap 2 10 3 1 External Resistance Programming of O...

Страница 5: ......

Страница 6: ...iii Blank iv HSMSERIES OPR 052912 FIGURE 1 1 HSM SERIES POWER SUPPLY...

Страница 7: ...ilures fault detection circuitry monitors performance of the output and critical internal functions providing both visual and electrical indi cators A switch selectable current walk in circuit and opt...

Страница 8: ...output conditions may result in increased output ripple and increased transient response recovery time Output Voltage Range See Table 1 1 Regulation Error Source Effect 0 1 over full source voltage ra...

Страница 9: ...AR 3 11 Voltage Set Programming Mode selected by internal switches See Note 6 See PAR 3 3 Internal Multiturn pot External 1 Resistance 0 50K External 2 0 10V 500 A max Current Limit Programming Intern...

Страница 10: ...1 4 HSMSERIES OPR 052912 FIGURE 1 3 OUTLINE DRAWING...

Страница 11: ...gnals which display programmed output voltage and current limit values These signals are available at the I O connector VSET and ISET Signals are referenced to negative error sense see PAR 3 7 1 4 4 R...

Страница 12: ...er must provide wiring and heat sink One diode required for each power supply See PAR 2 7 5 3 May also be used as optional external blocking diode for redundant applications See PAR 2 7 5 4 124 0601 U...

Страница 13: ...ATIONS AND CONTROLS a Output and Configuration Controls Refer to Figure 2 1 and Table 2 1 b Rear Panel Refer to Figure 2 2 and Table 2 2 FIGURE 2 1 HSM SERIES OUTPUT CONTROLS AND CONFIGURATION SWITCH...

Страница 14: ...NPUT VOLTAGE 0 10V SEE NOTE 3 3 3 19 S NEGATIVE ERROR SENSE INPUT 2 7 5 20 X NO CONNECTION 21 FFS 2 FAN STATUS NORMALLY OPEN CONTACT 3 14 22 FFS C FAN STATUS COMMON CONTACT 3 14 23 ACS 1 SOURCE POWER...

Страница 15: ...s 1 THE POWER SUPPLY WILL NOT OPERATE UNLESS THE REMOTE SENSE LINES ARE PROPERLY CONNECTED TO THE OUTPUT TERMINALS Connect the remote sense ter minals to the output bus bars using the mating I O Conne...

Страница 16: ...al as the interface between other types of electronic equip ment If optimum performance is expected certain rules for the interconnection of source power supply and load must be observed by the user T...

Страница 17: ...lection requires a combination of analysis good judgement and some amount of empirical testing If there is a choice in selecting either the positive or negative output of the power supply for the d c...

Страница 18: ...compensate for reactive effects due to this These dynamic conditions are especially important if the load is constantly modulated or step programmed or has primarily reactive characteristics or where...

Страница 19: ...pply output the regulation loop is essentially unaffected by the impedances presented by the load interconnec tion scheme The main disadvantage is that it cannot compensate for losses introduced by th...

Страница 20: ...als directly to the load will compensate for voltage drops in the load interconnection scheme see Specifications for available headroom based on model the termination point of the error sensing leads...

Страница 21: ...his is NOT the same as the blocking diode used for parallel redundant operation Selection of the clamping diode is entirely dependent upon output volt age current parameters The clamping diode must be...

Страница 22: ...or output blocking diodes and utilize active current sharing circuitry to distribute the load current equally among the paralleled units Redundant operation is achieved by paralleling one or more powe...

Страница 23: ...nearly as possible emulate a single large power supply To this end the following rules apply a If possible remote error sensing should be employed with all error sensing connections ter minated at th...

Страница 24: ...n ments it is recommended that a shielded cable be used with the shield terminated to the sys tem s single point ground a Remote Error Sense Twist positive and negative error sensing lines pins 37 19...

Страница 25: ...up to 0 25V drop in each power lead 0 5V total while 12V through 48V models provide for up to 0 8V drop in each lead 1 6V total The remote error sense leads must be connected to the output power termi...

Страница 26: ...0 2 or for limiting the maximum programmable voltage Operation of range selector is as follows a High Range This is the factory set default mode the maximum programmable output volt age is 110 of nom...

Страница 27: ...AR 3 5 for precise limit adjustment or for limiting the maximum programmable current limit Operation of the range selector is as follows a High Range This is the factory set default mode the maximum p...

Страница 28: ...ip level is preset at the factory for 130 of the nominal output voltage see Table 1 1 however this level can be adjusted from 100 to 140 of the nominal output except Model HSM 48 21 which can be adjus...

Страница 29: ...ge this operating mode is maintained indefinitely and recovery to voltage regulation mode is automatic upon reduction of the output current below the current limit point This mode is ideal for high po...

Страница 30: ...URRENT WALK IN CHARACTERISTIC 3 11 5VAUX FLOATING SUPPLY HSM power supplies are equipped with an internal auxiliary supply which provides 5V at loads up to 100mA It is derived from the internal coolin...

Страница 31: ...es results in an immediate shutdown of the output PWM regulator including reset of the soft start undervoltage and current walk in circuits Operation is inhibited until the appropriate control line is...

Страница 32: ...ilable to sustain rated output for normal operation These signals indicate a fault condition until the bulk voltage is greater than 390V d c Once the bulk voltage reaches 390V d c indicating that the...

Страница 33: ...ying less than 70 of the current required by the circuit as indicated by the load sharing signal while the output voltage is within specification limits A fault condition is not generated for a combin...

Страница 34: ...nerated in the event that either the input or output module heatsink temperature rises above a safe operating level output regulator shutdown occurs simultaneously Recovery occurs automatically upon r...

Отзывы: