HSF(A) 300W 040215

TABLE 3.  POWER SUPPLY RATINGS AND SPECIFICATIONS

CHARACTERISTIC

SPECIFICATION

CONDITION/NOTES

Input Voltage

Nominal: 100-120V a-c, 200-240V a-c 
Range: 85-265V a-c, 120-330V d-c

0 to 100% load, -10 to 50°C
CAUTION: Input voltage exceeding 
specifications may damage the unit.

Input Source Frequency

Nominal: 50-60 Hz
Range: 47-63 Hz

0 to 100% load, -10 to 50°C

Input Current: (Maximum Load At 
25°C with Nominal Output Voltage)

4.2A rms max.

100 - 120V a-c

2.1A rms max. 

200 - 240V a-c

Switching Frequency

200KHz typ.

Forward Converter

Input Protection

The internal power supply is protected against shorts by an input fuse. Fuse value 10A at 250 
Volts

Input Surge  cold start, interval > 30 

sec (First surge only, not including 

current flow into EMI filter )

15A typ., 20A max. first surge

100 - 120V ac

30A typ., 40 max. first surge

200- 240 V ac

Leakage Current: 

0.75mA max. 

240V a-c, 60Hz per IEC 60950 and UL60950

Power Factor

Meets EN 61000-3-2

Rated output, rated input

Transient Recovery

excursion

characteristic

±4% maximum

50% to 100% load, 
transient time >50

sec

recovery time 1 ms maximum

Stabilization

Source Effect (min - max) ±0.1% Typical, ±0.2% Maximum

85 to 132V a-c, 170 to 265V a-c

Load Effect ±0.6% Typical, ±1% Maximum (default)

±0.6% Typical, ±1% Maximum (see PAR. 5.)

Individual Mode: 0%-100% load change
Current Sharing: 10%-100% load change

Temperature Coefficient <0.02% per °C

Combined Effect ±1.2% Typical, ±2.2% Maximum

Source, Load and Temperature

Time Effect 0.2% Typical, 0.5% Maximum

1/2 to 8 hours at 25°C

Start-up Time

525 msec Typical, 900 msec Maximum

100V a-c 

275 msec Typical, 550 msec Maximum

240V a-c

Output Hold-up Time

20 msec Typical (28V model: 15 msec Typical)

Overvoltage Protection

When the Power Supply goes into an overvoltage condition, the output is cut OFF. See PAR. 
3.6.1.

Remote Control ON/OFF:

±RC pins control on/off as follows:
 “High”, 2.4V to 12V (or open), unit OFF- Fan 
Off; 
 “Low”, 0.0V to 0.8V (or shorted), unit ON. 
Source current: 1.6mA maximum at low level 
Sink current: 3.5 mA maximum at high level. 

Must be enabled by DIP switch positions 3 
and 4 (see PAR. 3.5).

Meter (AM Models only) (displays 
voltage or current; front panel 
switch-selectable)

Voltmeter Accuracy: ±3% 
Ammeter Accuracy: ±5% for loads between 
10%-100%

Voltmeter reads sense lines; use remote 
sensing to display voltage at load.
Ammeter accuracy degrades significantly for 
loads less than 10% 

Operating Temperature: 

-10 to 50°C 

(See Figure 2.)

Startup Temperature

-20 to -10°C

(See Figure 2.)

Storage Temperature: 

-30°C to +85°C

Withstanding voltage: (at 15-35°C 
ambient, 10-85% relative humidity)

2500Va-c for 1 minute. Cutout current is 20mA Between input and ground

500Va-c for 1 minute. Cutout current is 100mA Between output and ground

3000Va-c for 1 minute. Cutout current is 20mA Between input and output terminal

!

Содержание HSF A

Страница 1: ...serial number 3 The contents of this manual are protected by copyright Reproduction of any part can be made only with the specific written permission of Kepco Inc Data subject to change without notice...

Страница 2: ...g Latches 15 4 Load Connection 16 5 Connecting Multiple Power Supplies 16 1 HSF A AM Rear Panel Connector and RA 19 4C Rack Adapter I O Connector 1 2 Power Rating Vs Temperature 3 3 Mechanical Outline...

Страница 3: ...nd are designed to operate in a fault tolerant power sys tem Input voltage range is single phase 85 265V a c 47 63Hz or 120 330V d c Input voltage which is out of specification may cause unit damage S...

Страница 4: ...ay see PAR 3 7 2 1 REF 15 Reference voltage When used with RV pin 18 allows all output voltages of paralleled slave supplies to be controlled by one voltage adjustment of a master power supply When RE...

Страница 5: ...es that DIP SW1 position 7 be set to ON Refer to Table 5 for mini mum conditions required to maintain proper operation of alarm relay meter AM Models only and VDC ON ALARM indica tor 2 Using trimpot t...

Страница 6: ...load change Current Sharing 10 100 load change Temperature Coefficient 0 02 per C Combined Effect 1 2 Typical 2 2 Maximum Source Load and Temperature Time Effect 0 2 Typical 0 5 Maximum 1 2 to 8 hours...

Страница 7: ...B VCCI Class B EN55011 B EN55022 B EMC Emission Radiated Designed to meet FCC Class B VCCI Class B EN55011 B EN55022 B EMC Power Factor Harmonic Current PFHC Designed to meet EN61000 3 2 EMC Immunity...

Страница 8: ...4 0 093 2 4 0 127 3 2 0 430 10 9 2 065 52 5 3 353 85 2 0 337 8 5 0 085 2 2 0 204 5 2 0 090 2 3 0 943 23 9 2 408 61 2 0 438 11 1 0 394 10 0 3 216 81 7 0 606 15 4 0 690 17 5 FRONT VIEW REAR VIEW SEE RE...

Страница 9: ...6 CSB 1 OFF Enables Current Share always off ON N A 6 CSB 1 OFF N A ON Enables Current Share always on 7 COM to S OFF Isolates COM from S ON Connects COM to S 7 VADJ to 0 OFF Vadj adjusts output per T...

Страница 10: ...established at the factory The output voltage determines which key pins are installed see Figure 3 Detail A When the proper holes in the rack adapter are blocked by keying screws installed by the user...

Страница 11: ...re unit is removed from the rack adapter Retaining Latches 2 Prevents inadvertent removal of unit from rack adapter see PAR 3 9 AM Models only Voltage Current meter Monitors out put voltage or current...

Страница 12: ...fied in Table 2 To ensure proper operation of the alarm relay meter AM Models only and VDC ON ALARM indicator do not adjust the external voltage below minimum listed in Table 5 Using External Resistan...

Страница 13: ...be isolated from DC output or from PF signal TABLE 5 MINIMUM CONDITIONS FOR RELAY METER AND LED OPERATION HSF A AM MODEL 5 60A AM 12 27A AM 15 22A AM 24 14A AM 28 12A AM 48 7A AM For HSF A and AM mode...

Страница 14: ...wait until unit cools then set the POWER switch to ON The power supply cannot be reset using the remote ON OFF feature unless the power supply remains shut down for at least 40 seconds 3 6 2 OVERCURR...

Страница 15: ...he VDC ON ALARM indicator can be disabled by setting DIP switch 1 position 8 to OFF 3 7 2 ALARM SIGNALS Either of two options are available for signalling alarms isolated relay contacts factory defaul...

Страница 16: ...the transistor cuts off and the collector emitter cir cuit is open Figure 12 is a timing diagram of the power fail signal The default state of the alarm is logic low The sink current for the optocoup...

Страница 17: ...conjunction with the RA 19 4C rack adapters to prevent unauthorized or inadvertent module extraction from an operating power system The latch is engaged by loosening the cap head screw approximately 1...

Страница 18: ...e the difference between voltage settings of parallel con nected units should be less than 0 5 of the nominal voltage value of the units Output voltage adjustment should be done at same load for each...

Отзывы: