I N S T R U C T I O N   M A N U A L

KEPCO

An ISO 9001 Company.

HSF-1UR

100W SERIES

KEPCO SINGLE OUTPUT, 1U SIZE, 100 WATT 

HOT SWAP PLUG-IN POWER SUPPLIES

I — INTRODUCTION

The Kepco HSF-1UR 100 Watt Series hot swappable, high
frequency switching, plug-in power supplies with built-in
power factor correction (PFC) employ forward conversion
and are designed to operate in a fault tolerant power sys-
tem with either a-c or d-c input. A thermistor soft-start cir-
cuit limits start-up surge; an input fuse (3A, 250V) protects
against shorts. Built-in OR-ing diodes (all models) and a
forced current share circuit (all models except 3.3V) allow
configuration of all models for hot-swap and parallel-redun-
dant N+1 operation.

The heart of the HSF-1UR Series is a Kepco RTW power
supply allowing them to weigh less and have improved effi-
ciency (input current) specifications over the older HSF-1U
Series. There are three options available: C, X and Y. Fea-
tures for all models are the same except as follows: C
option (-1URC) models include a current sensing resistor,
allowing external current monitoring within ±10% (contact
Kepco if greater accuracy required). X option (-1URX) mod-
els have remote control, the ability to turn the unit on and
off from a remote location. Y option models (-1URY)
include both current monitoring and remote on-off capabili-
ties. 

These power supplies are designed to be used with
Kepco’s Series RA 19-1U rack adapters. The RA 19-1U
rack adapter accepts up to four 50-, 100- or 150-Watt units
(see Figure 1). All input/output connections are through a
24-pin connector that plugs in to the rack adapter. All exter-
nal connections are made through the rack adapter (refer
to the RA 19-1U manual which is available for free down-
load at:

www.kepcopower.com/support/opmanls.htm#ra19-1u

Seven models may be selected for outputs of 3.3, 5, 12, 15,
24, 28 or 48V (see Table 1).

When the input is cut off, the output is maintained for 20
milliseconds minimum. If the power supply shuts down due
to an output overvoltage condition, it is then necessary to
wait 60 seconds minimum before turning the unit on again.
EMI filtering is designed to meet FCC Class B rating and
VDE 0871 Class B rating. Table 1 contains specifications
that vary for each model of the HSF-1UR 100 Watt Series.
Specifications common to all models are listed on page 4.

TABLE 1.   OUTPUT RATINGS AND SPECIFICATIONS, HSF-1UR 100W SERIES

MODEL

HSF 3.3-25-1UR

(1) (2) (6)

HSF 5-20-1UR

(1)

HSF 12-8.4-1UR

(1)

HSF 15-6.7-1UR

(1)

HSF 24-4.2-1UR

(1)

HSF 28-3.5-1UR

(1)

HSF 48-2-1UR

(1)

OUTPUT VOLTS, d-c (NOMINAL)

3.3V

5V

12V

15V

24V

28V

48V

ADJUSTMENT RANGE

2.8 - 3.5V

4.3 - 5.3V

11.4 - 12.6V

13.5 - 16.5V

19.2 - 26.0V

26.5 - 29.5V

44.0 - 52.0V

OUTPUT CURRENT (NOMINAL)

(3)

25A

(3)

20A

8.4A

6.7A

4.2A

3.5A

2A

OUTPUT POWER (MAXIMUM)

(4)

82.5W

100W

100.8W

100.5W

100.8W

100.8W

100.8W

RIPPLE AND 

NOISE (mV p-p)

0-40°C,

10-100% LOAD

switching (typ)

80

80

100

100

150

150

200

spike noise 

(d-c—50MHz)

120

120

150

150

200

200

300

OVERVOLTAGE SETTING

(25 °C, Nom. Input)

3.75 - 4.7V

5.6 - 6.4V

13.3 - 15.4V

16.8 - 18.8V

26.5 - 30.0V

29.7 - 34.7V

54.5 - 59.5V

OVERCURRENT SETTING

w(25 °C, Nom. Input)

Rectangular type characteristic

26.2A min.

21.0A min.

8.82A min.

7.03A min.

4.68A min.

3.8A min.

2.2A min.

Sense Resistor Value (milliohms)

(5)

5

5

10

20

20

30

50

(1) Unless otherwise noted, specifications are identical for all options.
(2) Forced current Share not available for 3.3V Models.
(3) Derates same as Output Power.
(4) See power rating curve, Figure 4. Exceeding maximum power rating may result in 

oscillation or a drop in output current or voltage.

(5) C and Y Models only (see “Current Monitor.” on page 2 for details). 
(6) Natural convection cooled; see Figure 5.

Содержание HSF 3.3-25-1UR

Страница 1: ...exter nal connections are made through the rack adapter refer to the RA 19 1U manual which is available for free down load at www kepcopower com support opmanls htm ra19 1u Seven models may be selecte...

Страница 2: ...operate at less than maximum reducing stress and increasing reliability of the system If one unit fails the remaining units will continue to supply the load and the load current will be divided equal...

Страница 3: ...eering Remote sensing is recommended For master slave operation to work properly each unit should be adjusted to 40 mV optimum less than the next paral leled unit unit 1 is adjusted to VOUT unit 2 to...

Страница 4: ...20 ms min DIELECTRIC STRENGTH at 15 to 35 C ambient 10 to 85 relative humidity Between input and output 3KV a c for one minute cutout current 10ma Between input and ground 2KV a c for one minute cuto...

Страница 5: ...ERATURE 40o C to 75o C RELATIVE HUMIDITY Operating and storage 10 to 95 wet bulb temp 35o C non condensing FUSE Quick acting 5 0A 250V 5 2 x 20mm Littelfuse P N 215005PF Kepco P N 541 0134 DIMENSIONS...

Страница 6: ...CAUTION DO NOT repeatedly toggle the POWER on off switch as this may cause unit to fault When output voltage is available the VDC ON LED is on green For 100W and 150W 5V through 48V models the VDC ON...

Страница 7: ...ERS 5 TOLERANCES UNLESS OTHERWISE SPECIFIED 3 PLACES 0 005 2 PLACES 0 01 FRACTIONS 1 64 SEE DETAIL B 1 732 44 0 0 010 0 3 4 295 109 1 0 140 3 6 0 076 1 9 1 131 28 7 0 471 12 0 0 780 19 8 3 960 100 6 0...

Отзывы: