V — INSTALLATION

MOUNTING THE POWER SUPPLY.  

Refer to Figure

2 and insert power supply into selected slot of RA 19-(X)B
Rack adapter until power supply front panel is flush with
rack adapter chassis and secure with front panel Phillips
head mounting screw. 

CONNECTIONS. 

All connections are made at the rear

panel of the RA 19-(X)B Rack Adapter (see applicable RA
19-(X)B Operator Manual). Connect the load to the appli-
cable ± DC OUTPUT terminals. AC input power to each

slot is applied via two INPUT POWER terminal blocks as
indicated on the rack adapter rear panel. Make sure to
connect the AC input Neutral, Line and Ground wires to
the respective terminals of the terminal blocks.

REMOVAL. 

To remove a power supply, first use the

POWER switch to turn off the unit. Then loosen the
mounting screw and extract the unit from the RA 19-(X)B
Rack Adapter.

VI — OPERATION     

Turn the unit on using the front panel POWER switch (see
Figure 5). 

CAUTION: DO NOT repeatedly toggle the

POWER on/off switch as this may cause unit to fault. 

When output voltage is available, the green VDC ON LED
is on. While monitoring output voltage at the front panel
test points, the Output Voltage Adjust trimmer allows
adjustment of the output voltage. 

Master/slave parallel configurations of one or more power
supplies are covered in the applicable RA 19-(X)B Rack
Adapter manual. 

FIGURE 5.  COMPONENT LOCATIONS

The MASTER ON LED (amber) goes on under any of the
following three conditions:

• Independent operation.

• Operation in a parallel master/slave configuration

to indicate which unit is the master

• Operation in a parallel master/slave configuration

to indicate that a slave unit is no longer within the
proper specifications for paralleled units. Slave 1
should be optimally adjusted to 40mV less than
master, slave 2 adjusted to 40mV less than slave
1, etc. The maximum allowable difference
between paralleled units is 250mv. The minimum
allowable difference between paralleled units is
25mV. If a slave exceeds these limits, the MAS-
TER ON light goes on.

NOTE: MASTER ON LED not used on 3.3V

model: always OFF.

Additional information for various parallel and alarm con-
figurations can be found in the applicable RA 19 Rack
Adapter manual referenced on page 1.

Содержание HSF 3.3-20PFC

Страница 1: ...ard models and Section IV on page 6 suffix C T X and Y OPTIONS Options are identified by suffix T PFCT offers improved efficiency and less weight C PFCC offers current monitoring via an integral curre...

Страница 2: ...se line ac input line failure etc results in an alarm All models include an isolated internal relay offering nor mally closed and normally open contacts referenced to an isolated common These contacts...

Страница 3: ...e operating at between 10 to 100 of rated output current If current to the load goes below 10 for each unit in cur rent share mode all MASTER ON lights may go on see load effect specifications this in...

Страница 4: ...emperature effects 0 9 typ 1 8 max Time Effect 1 2 hr 8 hr at 25o C 0 2 typ 0 5 max RECOVERY CHARACTERISTICS A step load change from 50 to 100 produces less than 4 output excursion Recovery occurs to...

Страница 5: ...c SAFETY Units are designed to meet UL60950 3rd Edi tion CSA 22 2 No 60950 60950 1 and EN60950 and are CE marked per the Low Voltage Directive LVD 73 23 EEC and 93 68 EEC The standards do not apply wi...

Страница 6: ...rature effects 0 9 typ 1 8 max Time Effect 1 2 hr 8 hr at 25o C 0 2 typ 0 5 max TABLE 2 OUTPUT RATINGS AND SPECIFICATIONS HSF PFC 100W SERIES SUFFIX C T X Y ONLY MODEL HSF 3 3 25 1 2 7 PFCC PFCT PFCX...

Страница 7: ...TION RESISTANCE Between input and ground output and ground input and output 100 Megohms min 500V d c LEAKAGE CURRENT per IEC 950 and UL 1950 0 13mA typ 0 19 mA maximum 120V a c 0 45 mA maximum 240V a...

Страница 8: ...TION DO NOT repeatedly toggle the POWER on off switch as this may cause unit to fault When output voltage is available the green VDC ON LED is on While monitoring output voltage at the front panel tes...

Страница 9: ...ORD AVENUE FLUSHING NY 11355 U S A TEL 718 461 7000 FAX 718 767 1102 http www kepcopower com email hq kepcopower com 083013 228 1533 REV 15 9 FIGURE 6 HSF PFC 100W INCLUDING SUFFIX C T X AND Y POWER S...

Отзывы: