IV — SPECIFICATIONS (C, T, X, Y) - CONTINUED
RECOVERY CHARACTERISTICS:
A step load
change from 50% to 100% produces less than +4% output
excursion. Recovery occurs to 1% of the original
setting in <1 ms (load change t
r
or t
f
equal to or greater
than 50
µ
sec). (3.3V: 200mV max.)
START-UP TIME:
500 ms. maximum @100V a-c
400 ms. typical @100V a-c
300 ms. maximum @240V a-c
200 ms. typical @240V a-c
HOLDUP TIME:
37 ms. typ., 20 ms. min. (100V a-c)
30 ms. typ., 20 ms. min. (240V a-c)
DIELECTRIC STRENGTH:
Between input and output:
2KV a-c for one minute.
Between input and case (ground):
2KV a-c for one minute.
Between output and case (ground):
500V a-c for one minute.
INSULATION RESISTANCE:
Between input and
ground, output and ground, input and output:
100 Megohms min. (500V d-c).
LEAKAGE CURRENT
(per IEC 950 and UL 1950)
0.13mA typ. 0.19 mA maximum, (120V a-c)
0.45 mA maximum (240V a-c)
SAFETY:
Units are designed to meet UL60950 3rd Edi-
tion, CSA 22.2 No. 60950-1, and EN60950:2001 and are
CE marked per the Low Voltage Directive (LVD), 73/23/
EEC and 93/68/EEC. The standards do not apply with DC
input operation.
EMI:
Designed to meet FCC Class B (100-120V a-c) and
VCCI, EN55011-B, EN55022-B.
VIBRATION:
(non-operating, one hour on each one of
the three axes):
5-10 Hz, 10 mm amplitude.
10-55 Hz, 2g acceleration.
SHOCK:
(non-operating, one-half sinusoidal pulse, three
shocks to each axis):
Acceleration: 60g
Duration: 11ms +5ms
OPERATING TEMPERATURE:
See Figure 4.
STORAGE TEMPERATURE:
-30
o
C to +75
o
C.
RELATIVE HUMIDITY:
Operating and storage: up to
95% (wet bulb temp. <35
o
C non-condensing).
FUSE:
Slow Blow, 3.15A, 250V; (5 x 20 mm),
Littelfuse, P/N 2153.15PF;
Kepco P/N 541-0135.
DIMENSIONS:
See Figure 6.
WARRANTY:
5 years.