background image

HSF (M) 600W 042315

9

3.3

KEYING

Keying of the HSF 600W is established at the factory. The output voltage determines which key
pins are installed (see Figure 3, Detail A). When the proper holes in the rack adapter are blocked
by keying screws installed by the user, only a power supply of the correct voltage can be inserted
in the rack adapter slot. Refer to the RA 19-4C Manual for rack adapter keying instructions.

3.4

OUTPUT VOLTAGE CONTROL

Output Voltage can be controlled from either the front panel (PAR. 3.4.1) or externally using a
trimpot or voltage source (PAR. 3.4.2).

3.4.1 FRONT PANEL VOLTAGE CONTROL

Output voltage can be manually adjusted with the voltage adjustment control, Vadj (see Figure 5
for location) when DIP switches SW1 and SW2 (see Figure 4 for location) are configured as
shown in Figure 6A (factory default) To adjust voltage, first place the unit under an operating load.
Then monitor the (+) and (–) test points on the front panel with a precision voltmeter and turn the
voltage control to the desired operating value. Refer to Table 2 for the recommended Output
Adjustment Range of all HSF 600W M and MZ Models. 

3.4.2 REMOTE VOLTAGE CONTROL 

For remote voltage control, set positions 1, 2 and 7 for SW1 and SW2 as shown in Figure 6B. This
removes control from the front panel Vadj control and allows the output voltage to be adjusted by
either an external trimmer pot (resistance) or by an external variable voltage source connected
across the rack adapter I/O connector pin 12 (RV, Remote Voltage) and pin 10 (–COM, Common)
as shown in Figure 7. At the rack adapter I/O connector use a shielded wire 6.6 feet (2M) maxi-
mum in length, for connection of REF (pin 2), RV (pin 12), and –COM (pin 10) to the trimmer con-
trol or external voltage source.

NOTE:If remote voltage control is not implemented, the factory default for positions 1, 2 and 7 of DIP
switches SW1 and SW2 must be restored (Figure 6A).

FIGURE 6.  DIP SWITCH SETTINGS FOR CONTROL OF OUTPUT VOLTAGE

It is possible that overvoltage protection may be triggered if the output voltage is decreased to a low
level very quickly when the power supply is at a low load condition. 

3043281

COM  7

REF  1

RV  2

1  REF

2  RV

ON

ON

USING Vadj CONTROL

FRONT PANEL VOLTAGE CONTROL

A

B

(FACTORY DEFAULT)

REMOTE VOLTAGE CONTROL

OR VOLTAGE SOURCE

USING EXTERNAL TRIMPOT

COM  7

REF  1

RV  2

2  RV

1  REF

SW2

SW1

7

7

TAB

OFF

OFF

1

1

2

2

ON

SW2

SW1

7

7

OFF

1
2

ON

1

2

OFF

Содержание HSF 12-53M

Страница 1: ...del and serial number 3 The contents of this manual are protected by copyright Reproduction of any part can be made only with the specific written permission of Kepco Inc Data subject to change withou...

Страница 2: ...le Power Supplies 15 5 1 Adjusting the Voltage 15 5 2 Parallel Connections M Models 16 5 3 Parallel Connections MZ Models 16 5 3 1 Minimum Load 16 5 3 2 Voltage Set Restrictions 16 1 HSF Rear Panel Co...

Страница 3: ...tion for hot swap and parallel redundant N 1 operation RoHS compliant models are indicated by HSF e g HSF 28 23M The HSF M Models use the HSF output to power the VDC ON indicator internal alarm relay...

Страница 4: ...PAR 3 8 2 1 AL COM 14 Common contact of alarm relay see PAR 3 8 2 1 REF 15 Reference voltage When used with RV pin 18 allows all output voltages of paralleled slave supplies to be controlled by one v...

Страница 5: ...002 0 005 0 01 0 01 0 02 Unless otherwise noted specifications apply to both M and MZ models 1 M Models only To adjust output voltage down to approximately 0V use external voltage source or resistance...

Страница 6: ...3 2 Transient Recovery excursion characteristic 4 maximum 50 to 100 load transient time 50 sec recovery time 1 ms maximum Stabilization NOTE Refer to Table 2 ripple and noise and Note 8 for minimum ou...

Страница 7: ...1ms 5 msec non operating 1 2 sine pulse three shocks on each axis Power Supply is fixed on its bottom side Safety UL 60950 1 1st Edition 2007 10 31 CSA C22 2 No 60950 1 03 1st Edition 2006 07 EN 60950...

Страница 8: ...n external trimpot or voltage source see PAR 3 4 Positions 3 and 4 of SW1 and SW2 either allow the front panel reset button to be used to reset the unit after a fault or allow Remote on off via mechan...

Страница 9: ...the POWER switch is set to OFF CAUTION DO NOT repeatedly toggle the power ON OFF switch as this may cause unit to fault NOTE The ON OFF switch must be set to OFF before removing unit from rack adapte...

Страница 10: ...c output voltage OUTPUT RESET switch Used to recycle power in the event of an alarm condition see PAR 3 7 Not functional when remote on off control is enabled see PAR 3 5 POWER ON OFF switch Applies p...

Страница 11: ...HSF 600W M and MZ Models 3 4 2 REMOTE VOLTAGE CONTROL For remote voltage control set positions 1 2 and 7 for SW1 and SW2 as shown in Figure 6B This removes control from the front panel Vadj control a...

Страница 12: ...A Load effect is 1 maximum To use the HSF output voltage to power the VDC ON ALARM indicator set Posi tion 7 of SW1 to OFF and Position 8 of SW2 to ON see Figure 8B Load effect is 0 6 maxi mum however...

Страница 13: ...level the sink current is 1 0mA Positions 3 and 4 of both DIP switches must be restored to the factory default setting Figure 9A if remote ON OFF is not used The RC pins are isolated from DC output p...

Страница 14: ...he temperature returns to within specifications To restart reset the unit set the POWER ON OFF switch to OFF wait until unit cools then set the POWER switch to ON The power supply cannot be reset usin...

Страница 15: ...LARM indicator is enabled to light red the VDC ON ALARM indicator must be powered from the HSF output see PAR 3 4 3 3 8 2 ALARM SIGNALS Either of two options are available for signalling alarms isolat...

Страница 16: ...power fail signal The default state of the alarm is logic low The sink current for the optocoupler is 50mA maximum the maximum collector to emitter saturation voltage is 0 40 Volts and the collector...

Страница 17: ...purposes 4 LOAD CONNECTION Connect the load to and terminals at the rear panel of the Rack Adapter see RA 19 4C Instruction Manual for details 5 CONNECTING MULTIPLE POWER SUPPLIES All connections to...

Страница 18: ...tion 7 as defined below NOTE If the minimum load is maintained voltage set restric tions are not required If position 7 of SW1 is set to off default see PAR 3 1 the VDC ON indicator is powered from th...

Отзывы: