Adding/Removing Status Indicators & Ancillary Boards 6
Man-1453 Rev.01
Sigma ZXT SI Product Manual
15
4. In the CONNECTED DEVICES screen, select the REMOTE BUS option to open the REMOTE BUS STATUS
screen.
Figure 6-3
Remote Bus
5. The REMOTE BUS STATUS screen provides a synopsis of what devices are connected and whether they have
been installed on the panel.
Figure 6-4
Remote Bus Status
6. Below the screen header is a line showing the status of individual devices, the
left and right
arrow buttons can
be used to scroll through the addresses and see the status of each address.
The addresses 1-7 are shown for each group of Status Indicator/s Units and Ancillary Boards/s (ANC).
Status will be shown as OPERATIONAL, NONE, UNEXPECTED or MISSING. A symbol will be displayed for
each device beneath its corresponding address number.
The table below provides an overview of Remote Bus Status indications:
Symbol
Status
Description
OPERATIONAL
Indicates the device with this address is regis-
tered onto the panel and is working correctly.
NONE
Indicates there is currently no device associated
with this address.
UNEXPECTED
Indicates a new device has been added to the
ZXT panel SI Bus which has not yet been regis-
tered on the panel. Unexpected devices will be
indicated as ageneral fault on the ZXT panel.
MISSING
Indicates a device has been removed or is no
longer communicating with the system.
****connected devices****
>remote bus..
x
BACK goto menu
****remote bus status****
sI AT 1 :UNEXPECTED
-SI-
1 . 3 . 5 . 7
-ANC-
1 . 3 . 5 . 7
x
BACK INSTALL