Man-1152_K25800_series_Power_Supply_Manual_05 Page 4 of 18
*
This denotes variants tested & approved by the LPCB
3.2 Mounting
The unit should be mounted on a dry, flat surface and in a level position such that the enclosure is not distorted.
Screws or bolts of a minimum of 5mm diameter and suitable 40mm long wall fixings must be used to mount the
enclosure in all four mounting positions.
It should be positioned in an accessible place as agreed with the end user.
The unit should not be mounted in another enclosure or near sources of excessive heat.
Cables should be connected using suitable, metal cable glands fitted to the knockouts provided. If additional cable
entry points are required, all swarf and debris caused by drilling of additional cable entries must be cleared before
power is applied to the unit.
The equipment is of Class1 construction so must be permanently and reliably connected to the fixed earth of the
installation.
The primary earth of the end use application must be permanently marked with the protective earth symbol (IEC415
No. 5017). A suitable primary disconnecting device must be provided in the end use application.
Battery and load connections must be considered for connection to SELV (safety extra low voltage) circuits only.
The maximum leakage current of the completed and installed equipment must not exceed 3.5mA.
CL
218
218
300
K25800 03/KD25800 03 FIXING CENTRES
CL
218
218
405
K25800 15/KD25800 15 FIXING CENTRES
333
462
K25800 M3/KD25800 M3 AND K25800 D3/KD25800 D3 FIXING CENTRES