Man-1152_K25800_series_Power_Supply_Manual_05 Page 17 of 18
*
This denotes variants tested & approved by the LPCB
12. Cabling
Only fire rated and shielded cable should be used.
Note: For LPCB approved installations use only FP200*, 1.5mm
2
2 core cable.
Mains
The Mains cable should be a minimum cable size of 1mm² and rated at 250V.
A suitable primary disconnecting device must
be provided in the end use application. Maximum cable size is limited to 4mm².
Keep all mains wiring separate from the Extra Low Voltage (ELV) battery cables and power supply output cables
Extra Low voltage wiring
Cable for low voltage wiring should be a minimum size of 1.0mm
2
and rated for at least 30V DC. Keep all Extra Low
voltage wiring separate from mains wiring.
All cable entries to the enclosure must be via suitable cable terminating kits such as Pirelli AXT20SK or equivalent.
The earth or drain wire must be securely clamped to the cable gland as shown below or trapped between the lock nut
and the enclosure with a cut washer.