Kendrion Kuhnke Automation GmbH
Construction and Functionality
Vico MT
50
6.3 Applicable Standards and Limits
EMC Standards
EMC noise emission pursuant to IEC 61000-6-4 (industrial environments)
EMC noise immunity pursuant to IEC 61000-6-2 (industrial environments)
Admissible Ambient Conditions
Storage and transport
Temperature ........................................ -20...+70 °C
Relative humidity ................................. 10% to 95% at 25°C (no condensation)
Operation
Place of use ......................................... industrial environment
indoor use only, front of unit supports wet environment, degree
of contamination 2 pursuant to IEC 61010-1
Atmosphere: ....................................... fee from corrosive or explosive gases
Altitude ................................................ max. 3000 m
Ambient temperature ........................... vertical installation:
0...55 °C
Relative humidity ................................. 10% to 95% at 25°C (no condensation)