TROUBLESHOOTING 
 

Problem 

Solution 

Check wiring; verify that the correct input 
voltage is applied 
Verify that liquid is filling the sensor gap 
Check for dense foam or dried product in 
the gap.  Switch may not function properly 
if either condition exists. 
Check sensor phono plugs for a good 
connection.  Unplug and Re-plug each 
connection. 

No output change with level change 

Check for excessive aeration in process 
fluid.  This is particularly important in 
viscous fluids. 
Check wiring; verify that the correct input 
voltage is applied 
Check for turbulence.  Relocate switch or 
isolate from turbulence 

The output is “chattering” 

Check for excessive aeration in process 
fluid.  This is particularly important in 
viscous fluids. 

 
 
 

INTRINSICALLY SAFE CONTROL DRAWING 

Entity Parameters: 

Vmax = 36Vdc 
Imax = 150mA 

Ci = 0

µ

Li = 54

µ

NOTES: 

1)  Vmax > Voc; Imax > Isc; Ci + Ccable < Ca; Li + Lcable < La 
2)  Dust-tight conduit seal must be used when installed in Class II and Class III environments. 
3)  Control equipment connected to barrier must not use or generate more than 250V. 
4)  Installation should be in accordance with the CEC, Part 1. 
5)  No revision to drawing without prior CSA approval. 
6)  Associated equipment must be CSA Certified. 
7)  Associated equipment manufacturer’s installation drawing must be followed when installing this equipment. 
8)  For wiring refer to installation / operation manual. 

Содержание KUST Series

Страница 1: ... Sensor Material Sensor Length Process Connection Flange Size Flange Material INSTALLATION Unpack the switch carefully Inspect all units for damage Report any damage to carrier immediately Check the contents against the packing slip and purchase order Kenco s Ultrasonic Switches are manufactured to the highest quality standards These switches use electronic components that can be damaged by static...

Страница 2: ... using a wrench on the sensor mounting nut flats Use thread tape or suitable pipe compound on the threads If flanged bolt the sensor to the mating flange with the proper gasket The sensor gap must protrude into the vessel pipe being measured The sensor will not function properly if the detection tip is in a nozzle See the following drawings for mounting guidelines Wiring It is recommended that con...

Страница 3: ...t Two wire Isolated 4mA Dry 20mA Wet Switch 20 F to 170 F Temperature Range Sensor 40 F to 300 F 316SS Vacuum to 1000psig Pressure Range Tefzel Vacuum to 100psig Sensitivity Signal to noise Ratio 500 1 Repeatability 2mm Response Time on Alarm 0 5 sec non adjustable Relay Terminals Media Level Fail Safe Setting Relay Condition NC to C NO to C HLFS De Energized Closed Open Above Setpoint LLFS Energi...

Страница 4: ...te from turbulence The output is chattering Check for excessive aeration in process fluid This is particularly important in viscous fluids INTRINSICALLY SAFE CONTROL DRAWING Entity Parameters Vmax 36Vdc Imax 150mA Ci 0µF Li 54µH NOTES 1 Vmax Voc Imax Isc Ci Ccable Ca Li Lcable La 2 Dust tight conduit seal must be used when installed in Class II and Class III environments 3 Control equipment connec...

Отзывы: