background image

Operational Check 

Before installing the switch a simple operational check should be performed, as follows: 
 

1.  Fill a container with water 
2.  Open the electronics housing cover and connect power (see section on “

Wiring

”). 

3.  Set the Fail Safe jumper to the LLFS position (lower two pins). 
4.  Apply power 
5.  Place the sensor gap into the water.   

a.  Relay Version -- The relay will energize (the contacts between (NC) and (C) should open). 
b.  2-wire Version -- The current in the Positive lead will be 20.0mA. 

6.  Remove the sensor from the liquid. 

a.  Relay Version – The relay will de-energize (the contacts between (NC) and (C) should close). 
b.  2-wire Version – The current in the Positive lead will be 4.0mA. 

7.  Disconnect the wiring. 

 

Mounting 

For threaded process connections, screw sensor into the opening using a wrench on the sensor mounting nut flats. Use 
thread tape or suitable pipe compound on the threads.  If flanged, bolt the sensor to the mating flange with the proper 
gasket. 
 
The sensor gap must protrude into the vessel / pipe being measured.  The sensor will not function properly if the detection 
tip is in a nozzle.  See the following drawings for mounting guidelines: 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 
 

 
 
 
 
 
 
 
 
 
 

Wiring 

It is recommended that conduit be installed onto the ¾” NPT connection on the electronics housing.  A seal drain fitting 
should be used to prevent moisture from entering the switch.  All wiring, conduit, and electrical fittings must conform to 
local electrical codes for the location selected.  If the switch is to be used in a Hazardous Area, the applicable codes of the 
National Electrical Code must be followed as well. 

DO NOT

 use  

housing to  
tighten sensor 

Use wrench here 

¾” NPT 

Turn slot 
vertical allowing 
media to fall 
through 

Vessel Wall 

Slot must 
extend at least 
1” (25mm) 
beyond end of 
nozzle 

Содержание KUST Series

Страница 1: ... Sensor Material Sensor Length Process Connection Flange Size Flange Material INSTALLATION Unpack the switch carefully Inspect all units for damage Report any damage to carrier immediately Check the contents against the packing slip and purchase order Kenco s Ultrasonic Switches are manufactured to the highest quality standards These switches use electronic components that can be damaged by static...

Страница 2: ... using a wrench on the sensor mounting nut flats Use thread tape or suitable pipe compound on the threads If flanged bolt the sensor to the mating flange with the proper gasket The sensor gap must protrude into the vessel pipe being measured The sensor will not function properly if the detection tip is in a nozzle See the following drawings for mounting guidelines Wiring It is recommended that con...

Страница 3: ...t Two wire Isolated 4mA Dry 20mA Wet Switch 20 F to 170 F Temperature Range Sensor 40 F to 300 F 316SS Vacuum to 1000psig Pressure Range Tefzel Vacuum to 100psig Sensitivity Signal to noise Ratio 500 1 Repeatability 2mm Response Time on Alarm 0 5 sec non adjustable Relay Terminals Media Level Fail Safe Setting Relay Condition NC to C NO to C HLFS De Energized Closed Open Above Setpoint LLFS Energi...

Страница 4: ...te from turbulence The output is chattering Check for excessive aeration in process fluid This is particularly important in viscous fluids INTRINSICALLY SAFE CONTROL DRAWING Entity Parameters Vmax 36Vdc Imax 150mA Ci 0µF Li 54µH NOTES 1 Vmax Voc Imax Isc Ci Ccable Ca Li Lcable La 2 Dust tight conduit seal must be used when installed in Class II and Class III environments 3 Control equipment connec...

Отзывы: