background image

KENCO ENGINEERING COMPANY 

P.O. BOX 470426 TULSA, OK 74147-0426 

 PHONE: (918) 663-4406  FAX: (918) 663-4406 

www.kenco-eng.com  e-mail: [email protected] 

 

MODEL KUST ULTRASONIC SWITCH 

INSTALLATION / OPERATION INSTRUCTIONS 

 

GENERAL DESCRIPTION 

The KUST Series Ultrasonic Level Switches are ideal, low cost solutions for many liquid level control applications.  They 
operate in a wide variety of services. 
 

PRINCIPLE OF OPERATION 

Ultrasonic switches use piezoelectric crystals to transform electrical energy into mechanical motion (sound).  The 
Transmit Crystal sends a pulse of sound through the space between the crystals, to the Receive Crystal.  If the space is 
filled with air, gas, or vacuum, the Receive Crystal does not detect the sound pulse.  However, if the space is filled with 
liquid, 

any liquid

, the pulse is detected by the Receive Crystal, and the switch output changes. 

 

MODEL DESCRIPTION 

 

KUST -     -     -     -     -     -     -     -   

 

 
 

Input Power 

 

Output 

 

Switch Mounting 

 

Sensor Material 

 

Sensor Length 

 

Process Connection 

 

Flange Size 

 

Flange Material 

 
 
 
 
 
 
 
 
 

 
INSTALLATION 

Unpack the switch carefully.  Inspect all units for damage.  Report any damage to carrier immediately.  Check the 
contents against the packing slip and purchase order. 
 
Kenco’s Ultrasonic Switches are manufactured to the highest quality standards.  These switches use electronic 
components that can be damaged by static electricity.  Make sure that you are properly grounded before starting 
installation.  Insure that all electrical connections are properly made, and that there are no “floating” connections. 
 

Sensor Length  

 

Process Connection   

Flange Size 

 

          Flange Material   

 

Description 

Code 

 

Description 

Code 

 

Description 

Code 

 

Description 

Code 

Standard (2.25”) 

00 

 

¾” NPT 

 

None 

 

 

None 

 

*Inches (3” – 120”) 

xxx 

 

150# Flange 

 

1-1/2” 

 

Carbon Steel 

*316SS Sensor Only 

 

300# Flange 

 

 

316SS 

 

 

 

Sanitary Flange 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Input Power 

 

          Output 

 

Description 

Code 

 

Description 

Code 

115Vac 

 

10A DPDT 

230Vac 

 

Two-wire 

24Vdc 

 

 

 

12Vdc 

 

 

 

 

Switch Mounting 

          Sensor Material 

 

Description 

Code 

 

Description 

Code 

Integral 

 

316SS 

*Remote 

 

Tefzel

®

 

 

 

 

*Remote 10ft. (std.) 
100ft. (max) 

 

 

 

 

Содержание KUST Series

Страница 1: ... Sensor Material Sensor Length Process Connection Flange Size Flange Material INSTALLATION Unpack the switch carefully Inspect all units for damage Report any damage to carrier immediately Check the contents against the packing slip and purchase order Kenco s Ultrasonic Switches are manufactured to the highest quality standards These switches use electronic components that can be damaged by static...

Страница 2: ... using a wrench on the sensor mounting nut flats Use thread tape or suitable pipe compound on the threads If flanged bolt the sensor to the mating flange with the proper gasket The sensor gap must protrude into the vessel pipe being measured The sensor will not function properly if the detection tip is in a nozzle See the following drawings for mounting guidelines Wiring It is recommended that con...

Страница 3: ...t Two wire Isolated 4mA Dry 20mA Wet Switch 20 F to 170 F Temperature Range Sensor 40 F to 300 F 316SS Vacuum to 1000psig Pressure Range Tefzel Vacuum to 100psig Sensitivity Signal to noise Ratio 500 1 Repeatability 2mm Response Time on Alarm 0 5 sec non adjustable Relay Terminals Media Level Fail Safe Setting Relay Condition NC to C NO to C HLFS De Energized Closed Open Above Setpoint LLFS Energi...

Страница 4: ...te from turbulence The output is chattering Check for excessive aeration in process fluid This is particularly important in viscous fluids INTRINSICALLY SAFE CONTROL DRAWING Entity Parameters Vmax 36Vdc Imax 150mA Ci 0µF Li 54µH NOTES 1 Vmax Voc Imax Isc Ci Ccable Ca Li Lcable La 2 Dust tight conduit seal must be used when installed in Class II and Class III environments 3 Control equipment connec...

Отзывы: