background image

Wiring 

It is recommended that conduit be installed onto the ¾” NPT connection on the back of the sensor.  A seal drain fitting 
should be used to prevent moisture from entering the switch.  All wiring, conduit, and electrical fittings must conform to 
local electrical codes for the location selected.  The wiring color code is shown in the following table

 

Color 

Function 

Blue 

Normally Open Contact (Relay version) 

White 

Common Contact (Relay version) 

Brown 

Normally Closed Contact (Relay version) 

Black Power 

(-) 

Red Power 

(+) 

Green Ground 
Silver (Bare) 

Shield 

 

Connect the Black and Red wires to the power source (6 – 24Vdc).  If this is the 2-wire loop version, measure the current 
in the red wire to determine the output condition (4.0mA ± 1.0mA = Dry; 16.0mA ± 1.0mA = Wet).  For the Relay version, 
you must also connect the Blue (NO), White (C), and Brown (NC) wires.  The Green and Silver (Bare) wires are chassis 
ground, and should be connected to earth ground. 
 
The following table shows the relay condition for each switch state: 
 

Relay Terminals 

Switch 

State 

Relay 

Condition 

NC to C 

NO to C 

Dry De-energized Closed 

Open 

Wet Energized  Open  Closed 

 

Specifications 

 

Description 

Specification 

Input Power 

DC 

6 – 24Vdc, 5Vdc (Optional) 

Relay 1A 

SPDT 

Output 

Two-wire (Isolated) 4mA = Dry; 16mA = Wet 

Temperature Range 

-20°F to 160°F; up to 212°F (Special) 

316SS  

Vacuum to 1000psig 

Pressure Range 

Tefzel

®

 

Vacuum to 100psig 

Cable Length 

12”; For longer lengths consult factory 

Mounting 

¾” NPT; For flanges consult factory 

Sensitivity (Signal-to-noise Ratio) 

500:1 

Repeatability ±2mm 
Response Time 

0.5 sec.  non-adjustable 

 
TROUBLESHOOTING 
 

Problem 

Solution 

Check wiring; verify that the correct input 
voltage is applied 

Verify that liquid is filling the sensor gap 

No output change with level change 

Check for dense foam or dried product in 
the gap.  Switch may not function properly 
if either condition exists. 
Check wiring; verify that the correct input 
voltage is applied 
Check for turbulence.  Relocate switch or 
isolate from turbulence 

The output is “chattering” 

Check for excessive aeration in process 
fluid.  This is particularly important in 
viscous fluids. 

 

Отзывы: