MODEL KUSO ULTRASONIC SWITCH 

INSTALLATION / OPERATION INSTRUCTIONS 

 

GENERAL DESCRIPTION 

The KUSO Series Ultrasonic Level Switches are ideal, low cost solutions for many liquid level control applications.  They 
operate in a wide variety of services. 
 

PRINCIPLE OF OPERATION 

Ultrasonic switches use piezoelectric crystals to transform electrical energy into mechanical motion (sound).  The 
Transmit Crystal sends a pulse of sound through the space between the crystals, to the Receive Crystal.  If the space is 
filled with air, gas, or vacuum, the Receive Crystal does not detect the sound pulse.  However, if the space is filled with 
liquid, 

any liquid

, the pulse is detected by the Receive Crystal, and the switch output changes. 

 

MODEL DESCRIPTION 

 
 

KUSO -     - 

 
Style 
 
Cable Length 
*(In Feet) 
 
*Standard is 1FT. 
 
INSTALLATION 

Unpack the switch carefully.  Inspect all units for damage.  Report any damage to carrier immediately.  Check the 
contents against the packing slip and purchase order. 
 
Kenco’s Ultrasonic Switches are manufactured to the highest quality standards.  These switches use electronic 
components that can be damaged by static electricity.  Make sure that you are properly grounded before starting 
installation.  Insure that all electrical connections are properly made, and that there are no “floating” connections. 
 

Operational Check 

Before installing the switch a simple operational check should be performed, as follows: 
 

1.  Fill a container with water 
2.  Connect the wiring (see the section on “

Wiring

”) 

3. Apply 

power 

4.  Place the sensor gap into the water.   

a.  Relay Version -- The relay will energize (the contacts between (NC) and (C) should open). 
b.  2-wire Version -- The current in the Red wire will be 16.0mA ±1.0mA. 

5.  Remove the sensor from the liquid. 

a.  Relay Version – The relay will de-energize (the contacts between (NC) and (C) should close) 
b.  2-wire Version – The current in the Red wire will be 4.0mA ± 1.0mA. 

6.  Disconnect the wiring 

 

Mounting 

For threaded process connections, screw sensor into the opening using a wrench on the sensor mounting nut flats. Use 
thread tape or suitable pipe compound on the threads.  If flanged, bolt the sensor to the mating flange with the proper 
gasket. 
 
The sensor gap must protrude into the vessel / pipe being measured.  The sensor will not function properly if the detection 
tip is in a nozzle. 
 

Style   

 

              

Description 

Code 

1A SPDT 316LSS 

 

 

 

 
 

Отзывы: