INSTALLATION INSTRUCTIONS

MRIPS312_F-2846_110113

Content of specification sheets is subject to change; please consult www.kenall.com for current product details. © 2013 Kenall  Mfg. Co.  All rights reserved.

 www. kenall.com 

P: 800-4-Kenall            F: 847-360-1781           1020 Lakeside Drive Gurnee, Illinois 60031    

CUSTOMER ACKNOWLEDGEMENT

Customer acknowledges that these Installation Instructions are part of the product specification, and that the

attached Installation Registration Form will be provided to the installer to sign and return to Kenall after

installation is complete. This signed release is required by Kenall before order will be released into production.

Signature: _________________________________      Date: _________________________________ 

Print Name: _______________________________       Company Name:__________________________

• Disconnect power to all circuits before wiring system.
• Install in accordance with all national, state, and local codes.
• Do not connect to an ungrounded supply.
• Wiring connections must be made internal to the enclosure.
• Failure to install unit on a mechanically-sound surface may result in personal injury, physical damage, or potential 

fire hazard.

• Use installation procedures appropriate for an environment involving MRI and sensitive electronic equipment.
• Read all markings and labels to ensure correct installation of the power supply. Supplemental instructions may be 

located on the enclosure, in addition to this instruction sheet, regarding orientation, or mounting restrictions.

• Read instructions provided with the MedMaster

 MRIPS-312 external power supply for proper installation and 

electrical connection to the lighting system.

IMPORTANT SAFEGUARDS

To prevent 

MRI

 machine interference, all DC power and dimming signal wiring must be completely shielded within 

grounded aluminum conduit and a suitable 

MRI 

room 

EMI 

filter must be installed on each line.

When using electrical equipment, basic safety precautions should always be followed, including the following:

THIS PRODUCT MUST BE INSTALLED IN ACCORDANCE WITH THE APPLICABLE INSTALLATION CODE BY A PERSON FAMILIAR WITH THE 

CONSTRUCTION AND OPERATION OF THE PRODUCT AND THE HAZARDS INVOLVED. 

SAVE THESE INSTRUCTIONS