8/ 32 – K410014100002-00 / 05.2018 –
©
www.kemper-olpe.de
Technical data
Adjustable control range
50 °C - 65 °C
Factory pre-setting
58 °C
Temperature range for thermal disinfection
≥ 70 °C
Max. permissible operating temperature
90 °C
Control accuracy
+/- 2 K
Nominal pressure
PN 16
Nominal sizes
DN 15 | DN 20 | DN 25
Type
Figur 141 - male thread with flat gasket, alternatively
incl. or excl. screw coupling
Figur 143 - with female thread
Noise protection
The pressure difference Δp across the regulating valve should
always be above ≤ 400 mbar.
+
Accessories
1
Drain Valve
2
Dial Thermometer or
Temperature Sensor Pt 1000
3
Flow diagrams Annex
5