Technical data
KEMPER Figures
130, 131, 540 02, 544 02
134, 136, 540 62
Adjustable
regulating range
56°C - 58°C
62°C - 64°C
Factory setting
58°C
64°C
Temperature range for
Thermal disinfection
≥ 70°C
≥ 70°C
Max. permissible opera
-
ting temper- ature
90°C
90°C
K
v
values
max.
0,4 m³/h | min. 0,05 m³/h | k
vTD
0,1 m³/h
Nominal pressure
PN 16
PN 16
Nominal sizes
DN 15
DN 15
Design
concealed or surface
installation
concealed or surface
installation
Noise protection
The pressure difference Δp across the regulat- ing
valve should always be above ≤ 400 mbar.