EN
20/ 64 –
K410061100000-00
– 07.2020 –
©
www.kemper-olpe.de
Status LED
4.3
MicroSD card
5.2
The 2-colour LED displays the operation and
status of the data logger.
LED
Status
LED lamp lights up green
Everything OK (default state, if no data are transmitted) – microSD card
OK and CAN bus available
LED lamp lights up red
MicroSD card not OK or none inserted
LED lamp flashes red
CAN bus not OK – CAN not connected
LED lamp rapidly flashes green
Data are being copied to the SD card (every minute or the first time it is
connected, when the memory contents are transferred from the control-
ler)
LED lamp slowly flashes green
At start – CAN is being initialised
Operation
5
Reset button
5.1
Restarting the data logger:
Press and hold reset button for 5 seconds..
After the microSD card is inserted for the
first time, the data from the controller‘s flash
memory (8MB) are automatically copied to the
microSD card when the controller is switched
on.
Thereafter, all data are stored on the microSD
card.
If necessary, a firmware update can also be
imported from the microSD card (see 5.4.
Firmware update).
Only remove the SD card when the
device is switched off.
Содержание 6110000000
Страница 7: ...www kemper olpe de 07 2020 K410061100000 00 7 64 1 4 2 5 3 6...
Страница 19: ...www kemper olpe de 07 2020 K410061100000 00 19 64 1 4 2 5 3 6...
Страница 31: ...www kemper olpe de 07 2020 K410061100000 00 31 64 1 4 2 5 3 6...
Страница 43: ...www kemper olpe de 07 2020 K410061100000 00 43 64 1 4 2 5 3 6...
Страница 55: ...www kemper olpe de 07 2020 K410061100000 00 55 64 1 4 2 5 3 6...
Страница 62: ...NL 62 64 K410061100000 00 07 2020 www kemper olpe de...
Страница 63: ...www kemper olpe de 07 2020 K410061100000 00 63 64...