Kelvinator KSV26CRE Скачать руководство пользователя страница 3

Kelvinator Air Conditioning

  Important safety instructions  3

caution

1   The unit must only be installed by a qualified refrigeration 

mechanic and electrical work carried out by a qualified 
electrician according to local or government regulations 
and in compliance with this manual.

2   Before installation, please contact a qualified air 

conditioner installer. If the unit is not installed by a 
qualified air conditioner installer, the malfunction may 
not be solved due to faulty installation.

3   If the supply cord is damaged, it must be replaced by 

the manufacturer, its service agent or similarly qualified 
persons in order to avoid a hazard.

4   The appliance must be positioned so that the plug 

is accessible.

5   The temperature of the refrigerant circuit will be high, 

please keep the interconnection cable away from the 
copper tube.

6    This appliance is not intended for use by persons 

(including children) with reduced physical, sensory 
or mental capabilities, or lack of experience and 
knowledge, unless they have been given supervision or 
instruction concerning use of the appliance by a person 
responsible for their safety.

 

 Children should be supervised to ensure that they do not 
play with the appliance.

7   For appliances with type Y attachment, the instructions 

shall contain the substance of the following. If the 
supply cord is damaged, it must be replaced by the 
manufacturer, its service agent or similarly qualified 
persons in order to avoid a hazard.

warning

Before obtaining access to terminals, all supply circuits 
must be disconnected.

Please read this installation manual and the user manual 
before installation and carefully store in a handy place for 
later reference. Inside you will find many helpful hints on how 
to install and test the air conditioner properly. 
Electrical work must be installed by a licensed electrician. 
Be sure to use the correct rating of the power plug and main 
circuit for the model to be installed.
Incorrect installation due to ignoring this instruction will 
cause harm or damage, and the seriousness is classified by 
the use of the 'warning' and 'caution' symbols.

refrigerant warning

Warning Refrigerant R32, mildly flammable. This product 
uses Refrigerant R32, Difluoromethane which is a mildly 
flammable gas class 2.2, based on AS1677 and must be 
handled by a Refrigeration Mechanic with an appropriate 
Australian Refrigerant Gas handling license

caution

•    The air conditioner is not intended for use by young 

children or infirm persons without supervision.

•    Young children should be supervised to ensure that 

they do not play with the air conditioner. 

•    Contact an authorised installer for installation of this unit.
•    Contact an authorised service technician for repair or 

maintenance of this unit.

•    If the power cord is to be replaced, replacement work  

shall be performed by authorised personnel only.

•    Installation work must be performed in accordance  

with the national wiring Standards by authorised 
personnel only.

environmental tip 

Information on disposal for users

•    Most of the packing materials are recyclable.  

Please dispose of those materials through your local 
recycling depot or by placing them in appropriate 
collection containers.

•    If you wish to discard this air conditioner, please contact 

your local authorities and ask for the correct method  
of disposal.

Important safety instructions

Notice for installation

Содержание KSV26CRE

Страница 1: ...Inverter Room Air Conditioner Installation Manual KSV26CRE KSV26HRE KSV35CRE KSV35HRE KSV53HRE KSV62HRE KSV70CRE KSV70HRE KSV80HRE Refrigerant R32 ...

Страница 2: ... but contact your local Electrolux Customer Care Centre Meanings of symbols used in this manual are shown below warning This symbol indicates information concerning your personal safety caution This symbol indicates information on how to avoid damaging the appliance tips and information This symbol indicates tips and information about use of the appliance environmental tip This symbol indicates ti...

Страница 3: ...nual and the user manual before installation and carefully store in a handy place for later reference Inside you will find many helpful hints on how to install and test the air conditioner properly Electrical work must be installed by a licensed electrician Be sure to use the correct rating of the power plug and main circuit for the model to be installed Incorrect installation due to ignoring this...

Страница 4: ...ge Screw driver Electric drill Hole core drill 55mm 70mm Flaring tool specifically designed for R32 or R410a refrigerant Specified torque wrenches Spanner half union A glass of water Hexagonal wrench 6mm Gas leak detector Vacuum pump Gauge manifold Users manual Thermometer Multimeter Pipe cutter Measuring tape Number Description Quantity 1 Indoor unit mounting plate 1 fan 2 Clip anchor not supplie...

Страница 5: ...tdoor unit space to obstruction air inlet side space to the wall space to the wall space to the ceiling space to the floor air outlet side 15cm or more 200cm or more 15cm or more 2 5 0 c m o r m o re 15cm or more space to the wall air outlet side 30cm or more 50cm or more space to the wall 50cmormore 20cm orm ore 150cm orm ore 1 8 9 10 11 12 13 14 15 16 17 7 6 5 4 ...

Страница 6: ...cessible without special equipment Has the appropriate size circuit and fuse circuit breaker been fitted Has the unit been tested and confirmed to operate correctly Has the user of the air conditioner been shown how to use the air conditioner CUSTOMER PLEASE RETAIN WITH YOUR PURCHASE DOCUMENTS IN A SAFE PLACE Model Number ____________________________________________________________________________...

Страница 7: ...unit Avoid the following sites where strong heat sources vapour flammable gas or volatile liquids are emitted high frequency electro magnetic waves are generated by radio equipment welders or medical equipment salt laden air prevails such as close to coastal areas the air is contaminated with industrial vapours and oils the air contains sulphurous gas such as in hot spring zones corrosion or poor ...

Страница 8: ...n reliability Exceeding the maximum may cause poor performance or malfunction When the level difference between indoor and outdoor units is greater than the maximum height of 10 metres or when the outdoor unit is installed above the indoor unit an oil trap should be installed every 5 7 metres Pipe Length Elevation and Additional Quantity of Gas Model Number Suction Pipe Diameter Discharge Pipe Dia...

Страница 9: ...xing the 4 holes existent in its base with 4 bolts and nuts of φ10 mm tightly not included Place the outdoor unit over a horizontal concrete or rigid surface never directly over grass or earth A B air inlet air inlet air outlet Model Outdoor unit dimensions W x D x H mm Dimension A mm Dimension B mm KSV26HRE CRE 776 x 320 x 540 510 286 KSV35HRE CRE 842 x 320 x 596 540 286 KSV53HRE KSV62HRE KSV70CR...

Страница 10: ... the indoor unit has two way drainage design During installation the indoor unit should slightly slant to water tray s outlet for smooth drainage of condensate water Fit the mounting plate and drill holes in the wall according to the wall structure and corresponding mounting points on the mounting plate dimensions are in mm unless otherwise stated Model no Indoor unit dimension W x D x H mm Mounti...

Страница 11: ...Installation instructions 11 Mounting plate type C Mounting plate type D Indoor unit installation 70 70 36 67 67 36 146 90 65 575 left right indoor unit indoor unit 172 253 179 746 1073 183 685 149 326 337 65 65 50 163 90 6 74 105 ...

Страница 12: ...hrough the hole 4 Always use a wall hole conduit when drilling metal grids metal plates or the like 5 For models with a cooling capacity greater than 4500W remove and dispose the two polystyrene lateral rear supports from the indoor unit before the installation remove both supports Installation of drain hose 1 Connect the drain hose to the outlet pipe of the indoor unit Bind the joint with vinyl t...

Страница 13: ... routing the wiring only Cut off the tailings 1 and tailings 2 when routing both the wiring and piping indoor unit outline connection piping 43 2 The drain hose can be connected at two different positions Use the most convenient position and if necessary exchange the position of drain cap and drain hose The drain hose is connected at the rear left side of the indoor unit when you receive the produ...

Страница 14: ... hose from the right side piping on the right side drain hose from the left side piping on the right side drain hose from the right side piping on the left rear side drain hose from the left side piping on the left side drain hose from the left side caution When refrigerant pipes and the drain pipe are fitted to the same side ensure that the bulk does not push the unit away from the wall when in i...

Страница 15: ... the bundle Locating at the upper side can cause drain pan to overflow inside the unit Never cross connect or interwind the power wire with any other wiring Do not allow the piping to be exposed out from the back of the indoor unit If part of the drain hose is positioned inside the room wrap it with insulating materials so as to prevent condensed water from dropping 5 Hang the mounting slots of th...

Страница 16: ... cross section of pipe tube Face the end of the copper pipe tube in a downward direction as you remove burrs in order to avoid burrs dropping into the tubing pipe reamer face down c Put the flare nut on Remove flare nuts attached to indoor and outdoor unit then put them on pipe tube having completed burr removal flare nut copper tube caution It is not possible to put them on after flaring work d F...

Страница 17: ...rtion Cover the indoor unit pipe and the connection pipe with the heat insulation material Bind them together with vinyl tape so that there is no gap insulating material Isolate the suction pipe from the liquid pipe heat insulation suction line pipe liquid line pipe Wrap the insulated pipes with vinyl tape in the rear section for pipe housing Fasten the power cable to the pipes with vinyl tape con...

Страница 18: ...ge pipe for KSV53HRE and KSV62HRE Make sure to follow the torque table value as below Outer diameter mm Torque N m 6 35 1 4 15 16 9 52 3 8 31 32 12 70 1 2 40 41 15 88 5 8 45 46 Piping formation a Form the piping by wrapping the connecting portion of the indoor unit with insulation material and secure it with narrow vinyl tape and wide vinyl tape If you want to connect an additional drain hose the ...

Страница 19: ...ional wiring regulations 4 A circuit breaker with proper capacity must be installed according to AS3000 and applicable local electrical safety regulations 5 In case of problems in power supply the air conditioner must not be installed before the customer fixes the problem 6 Be sure the power supply matches the air conditioner 7 Ensure the live wire neutral wire and earth wire in the power socket a...

Страница 20: ...es that are not connected with insulating tape so that they do not touch any electrical or metal parts 5 Secure the wires firmly with the cable clamp 6 Put the wiring cover back and screw it 7 Reinstall the front panel warning All wires between indoor and outdoor units must be connected by a qualified electric contractor If the length of the power cord is not enough please contact your installer f...

Страница 21: ...ng the above conditions prepare the wiring as follows The screws which fasten the wiring to the terminal block may come loose from vibrations during transportation Check and make sure all screws are well fixed Otherwise it could cause burn out of the wires Be sure the circuit capacity is sufficient Ensure the starting voltage is maintained at over 90 of the rated voltage marked on the nameplate Co...

Страница 22: ...igeration circuit may freeze and block the capillary tubing Water may lead to corrosion of parts in the refrigeration system Therefore the indoor unit and tubing between the indoor and outdoor units must be tested for leakage and evacuated to remove any non condensables and moisture from the system Air purging with a vacuum pump Preparation Check that each tube both liquid and gas side tubes betwe...

Страница 23: ... the flare nut of the low pressure valve to check if there is air coming inside if operation noise of the vacuum pump has been changed the reading of multimeter is 0 instead of minus Then tighten the flare nut 5 Keep vacuuming for more than 15 minutes and make sure the reading of multimeter is 1 0 x 10 Pa 76cmHg Then fully close the low handle of manifold valve and stop the operation of the vacuum...

Страница 24: ...st Do not switch on power before installation is finished completely Electric wiring must be connected correctly and securely Stop valves of the connection pipes should be fully opened All the impurities such as scraps and waste must be cleared from the unit Operation test method Switch on power and press ON OFF button on the remote controller to start the operation Press MODE button to select the...

Страница 25: ...ge Is the voltage in accordance with the rated voltage marked on the nameplate It may cause electric malfunction or damage the unit Is the electric wiring or piping connection installed correctly and securely It may cause electric malfunction or damage the parts Has the unit been securely earthed It may cause electrical leakage Is the power cord specified It may cause electric malfunction or damag...

Страница 26: ...26 Notes Kelvinator Air Conditioning Notes ...

Страница 27: ...nless the defect claimed is due to faulty or defective parts or workmanship Electrolux is not liable in the following situations which are not exhaustive a the Appliance is damaged by i accident ii misuse or abuse including failure to properly maintain or service iii normal wear and tear iv power surges electrical storm damage or incorrect power supply v incomplete or improper installation vi inco...

Страница 28: ...about Kelvinator appliances please visit your retailer phone or email our Customer Care team or visit our website telephone 1300 363 640 fax 1800 350 067 email customercare electrolux com au web www kelvinator com au Kelvinator We are part of the Electrolux family Share more of our thinking at www electrolux com au ...

Отзывы: