9
Installation instructions
Tightening Connection
•
Align the center of the pipes.
•
Sufficiently tighten the flare nut with fingers, and
then tighten it with a spanner and torque wrench
as shown below.
Spanner
Torque
wrench
Piping
Taper nut
Indoor unit piping
Model
Discharge
(mm)
Suction
(mm)
Maximum
length
Maximum
Height
KSV25HRD
6.4 (1/4")
9.5 (3/8")
15
10
KSV35HRD
6.4 (1/4")
9.5 (3/8")
20
10
KSV52HRD
6.4 (1/4")
16.0 (5/8")
25
10
KSV70HRD
6.4 (1/4")
16.0 (5/8")
25
10
KSV80HRD
6.4 (1/4")
16.0 (5/8")
30
10
NOTE: Connect the connection pipe to indoor unit at first and then
to outdoor unit. Handle piping bending with care. Do not damage
the connection pipe. Ensure that the joint nut is tightened firmly,
otherwise, it may cause leakage.
Installation of outdoor unit
Electric wiring
1. Remove the handle on the right side plate of
outdoor unit.
2. Take off wire cord anchorage. Connect and fix power
connection cord to the terminal board. Wiring should fit that of
indoor unit.
3. Fix the power connection cord with wire clamps and then
connect the corresponding connector.
4. Confirm if the wire has been fixed properly.
5. Reinstall the handle.
Handle
yellow-
brown
black
blue
2
N(1)
3
indoor unit
outdoor unit terminal block
green
Air Purging and Leakage Test
1.
Connect charging hose of manifold valve to charge end of low
pressure valve (both high/low pressure valves must be tightly shut).
2. Connect joint of charging hose to vacuum pump.
3. Fully open the handle of Lo manifold valve.
4. Open the vacuum pump for vacuumisation. At the beginning,
slightly loosen joint nut of low pressure valve to check if there
is air coming inside. (If noise of vacuum pump has been
changed, the reading of multimeter is 0) Then tighten the nut.
5. Keep vacuuming for more than 15mins and make sure the
reading of multi-meter is -1.0 10
5
pa (-76cmHg).
6. Fully open high/low pressure valves.
7.
Remove charging hose from charging end of low pressure valve.
8. Tighten lid of low pressure valve. (As shown in below)
Multimeter
-76cmHg
Lo Handle
Charging hose
Hi handle
Charging hose
Low pressure valve
Manifold
Valve
Vacu um pump
Outdoor Condensate Drainage
During heating operation, the condensate and defrosting water
should be drained out reliably through the drain hose.
Install the outdoor drain connector in a 25mm hole on the base
plate and attach the drain hose to the connector so that the waste
water formed in the outdoor unit can be drained out. The hole
diameter 25mm must be plugged.
Whether to plug other holes will be determined by the installer
according to actual conditions.
Drain-water hole
Bottom frame
Drain plug
Hose (available commercially,
inner diameter 16mm)
Drain connecter