Installation instructions

Tightening Connection

• 

Align the center of the pipes.

• 

 Sufficiently tighten the flare nut with fingers, and 
then tighten it with a spanner and torque wrench 
as shown below.

Spanner

Torque

wrench

Piping

Taper nut

Indoor unit piping

Model 

Discharge 

(mm)

Suction 

(mm)

Maximum 

length

Maximum 

Height

KSV25HRD

6.4 (1/4")

9.5 (3/8")

15

10

KSV35HRD

6.4 (1/4")

9.5 (3/8")

20

10

KSV52HRD

6.4 (1/4")

16.0 (5/8")

25

10

KSV70HRD

6.4 (1/4")

16.0 (5/8")

25

10

KSV80HRD

6.4 (1/4")

16.0 (5/8")

30

10

NOTE: Connect the connection pipe to indoor unit at first and then 
to outdoor unit. Handle piping bending with care. Do not damage 
the connection pipe. Ensure that the joint nut is tightened firmly, 
otherwise, it may cause leakage.

Installation of outdoor unit

Electric wiring

1.   Remove the handle on the right side plate of 

outdoor unit.

2.   Take off wire cord anchorage. Connect and fix power 

connection cord to the terminal board. Wiring should fit that of 
indoor unit.

3.   Fix the power connection cord with wire clamps and then 

connect the corresponding connector.

4.   Confirm if the wire has been fixed properly.

5.  Reinstall the handle.

 

Handle

yellow-

brown

black

blue

2

N(1)

3

indoor unit

outdoor unit terminal block

green

Air Purging and Leakage Test

1.  

Connect charging hose of manifold valve to charge end of low 
pressure valve (both high/low pressure valves must be tightly shut).

2.  Connect joint of charging hose to vacuum pump.

3.  Fully open the handle of Lo manifold valve.

4.   Open the vacuum pump for vacuumisation. At the beginning, 

slightly loosen joint nut of low pressure valve to check if there 
is air coming inside. (If noise of vacuum pump has been 
changed, the reading of multimeter is 0) Then tighten the nut.

5.   Keep vacuuming for more than 15mins and make sure the 

reading of multi-meter is -1.0 10

5

pa (-76cmHg).

6.  Fully open high/low pressure valves.

7.  

Remove charging hose from charging end of low pressure valve.

8.  Tighten lid of low pressure valve. (As shown in below)

Multimeter

-76cmHg

Lo Handle

Charging hose

Hi handle

Charging hose

Low pressure valve

Manifold

Valve

Vacu um pump

Outdoor Condensate Drainage

During heating operation, the condensate and defrosting water 
should be drained out reliably through the drain hose.

Install the outdoor drain connector in a  25mm hole on the base 
plate and attach the drain hose to the connector so that the waste 
water formed in the outdoor unit can be drained out. The hole 
diameter 25mm must be plugged.

Whether to plug other holes will be determined by the installer 
according to actual conditions.

Drain-water hole

Bottom frame

Drain plug

Hose (available commercially,

inner diameter 16mm)

Drain connecter

Содержание KSV25HRD

Страница 1: ...Inverter Split Room Air Conditioner Installation Manual KSV25HRD KSV35HRD KSV52HRD KSV70HRD KSV80HRD Refrigerant R410A ...

Страница 2: ...your local Electrolux Customer Care Centre ENVIRONMENTAL TIPS environment Information on disposal for users Most of the packing materials are recyclable Please dispose of those materials through your local recycling depot or by placing them in appropriate collection containers If you wish to discard this air conditioner please contact your local authorities and ask for the correct method of dispos...

Страница 3: ...responsible for their safety 7 Children should be supervised to ensure that they do not play with the appliance WARNING warning Before obtaining access to terminals all supply circuits must be disconnected Please read this installation manual and the user manual before installation and carefully store in a handy place for later reference Inside you will find many helpful hints on how to install an...

Страница 4: ...ent welders or medical equipment salt laden air prevails such as close to coastal areas the air is contaminated with industrial vapours and oils the air contains sulphurous gas such as in hot spring zones corrosive or poor air quality exists Installation Site of Indoor Unit 1 The air inlet and outlet should be away from the obstructions Ensure the air can be blown through the whole room 2 Select a...

Страница 5: ... adhered to the air conditioner will not perform to specification may not be able to be serviced and the warranty may be voided The installation must allow for reasonable access by a service technician space necessary for proper installation of the unit with respect to existing building structure Space to the wall 150cm horizontally in front Space to the obstruction Air outlet side e v o b 50cm A ...

Страница 6: ...he outlet in the water Installation of indoor unit Installation of Mounting Plate 1 The mounting plate should be installed horizontally As the water tray s outlet for the indoor unit is two way type during installation the indoor unit should slightly slant to water tray s outlet for smooth drainage of condenser water 2 Fix the mounting plate on the wall with screws 3 Be sure that the mounting plat...

Страница 7: ... of indoor unit cut off the tailings from the chassis when necessary As shown in Fig 1 a Cut off the tailings 1 when routing the wiring only b Cut off the tailings 1 and tailings 2 when routing both the wiring and piping 2 Take out the piping from body case wrap the piping power cords drain hose with the tape and then make them pass through the piping hole As shown in Fig 2 3 Hang the mounting slo...

Страница 8: ...move flare nuts attached to indoor and outdoor unit then put them on pipe tube having completed burr removal Note It is not possible to put them on after flaring work Flare nut Copper tube D Flaring work Carry out flaring work using flaring tool as shown below Firmly hold copper pipe in a die according to the dimension shown in the table below Refrigerant pipe connection Outer diam mm A mm Max Min...

Страница 9: ...kage Test 1 Connect charging hose of manifold valve to charge end of low pressure valve both high low pressure valves must be tightly shut 2 Connect joint of charging hose to vacuum pump 3 Fully open the handle of Lo manifold valve 4 Open the vacuum pump for vacuumisation At the beginning slightly loosen joint nut of low pressure valve to check if there is air coming inside If noise of vacuum pump...

Страница 10: ...t accurate Operation Test 1 Before Operation Test a Do not switch on power before installation is finished completely b Electric wiring must be connected correctly and securely c Cut off valves of the connection pipes should be opened d All the impurities such as scraps and waste must be cleared from the unit 2 Operation Test Method a Switch on power and press ON OFF button on the remote controlle...

Страница 11: ...hown in the fig For 5 2kW is as below Clasp of RJ45 plug of network cable shall aim at the notch of RJ45 terminal to be installed The clasp shall be towards inside as shown in the fig For 7 0kW and 8 0kW is as below Clasp of RJ45 plug of network cable shall aim at the notch of RJ45 terminal to be installed The clasp shall be towards left as shown in the fig Bundle the Dred network cable at the wir...

Страница 12: ...12 Notes Notes ...

Страница 13: ...13 Notes Notes ...

Страница 14: ...14 Notes Notes ...

Страница 15: ...ct claimed is due to faulty or defective parts or workmanship Electrolux is not liable in the following situations which are not exhaustive a the Appliance is damaged by i accident ii misuse or abuse including failure to properly maintain or service iii normal wear and tear iv power surges electrical storm damage or incorrect power supply v incomplete or improper installation vi incorrect improper...

Страница 16: ...nator com au NEW ZEALAND phone 0800 436 245 fax 0800 225 088 email customercare electrolux co nz web kelvinator co nz For more information on all Kelvinator appliances or for dimension and installation information call into your retailer phone or email our customer care team or visit our website Kelvinator We are part of the Electrolux family Share more of our thinking at electrolux com au ...

Отзывы: