NET DRY WEIGHT – LBS. (Kg.) 

 

 

Model Number 

 

Module Weight 

 

Total Weight 

 

RH015 

 

RH025 

 

RH035 

 

RH045 

 

RH055 

 

RH070 

 

RH085 

 

RH105 

 

                  475  (215) 

 

                  950  (432) 

 

 1200  (544) 

 

1475  (669) 

 

                  950  (431) 

 

1200  (544) 

 

1475  (669) 

 

1200  (544) 

                 475  (215) 

 

                 950  (432)  
 
               1200  (544) 

 

               1475  (669) 

 

               1900  (862) 

 

               2400  (1089) 

 

               2950  (1338) 

 

               3600 (1636) 

 

 

LOCATION 

 

 

The RH Models are designed for outdoor use and if installed indoors precautions 

should be taken to ensure a free flow of air to and from the unit and to prevent recirculation of 
the heated exhaust air from the unit back into its intake stream.  It is also important to locate the 
unit no closer than one unit width from a wall, another unit, or any other obstruction which 
would restrict air movement. 

 

ASSEMBLY OF UNIT 

 

RH Models are shipped completely assembled, except for the mounting legs.  Mounting 

legs are furnished with the necessary bolts, nuts and washers.  The legs are not adjustable and are 
most easily assembled to the unit when the unit is still laying on its side as shipped.  Each leg is 
fastened to the bottom of the coil plenum by four bolts furnished with the unit, Reference  
Figure 2.  
 

The larger RH Models (RH055 and up) are delivered as two separate modules which 

must be joined together to make the total unit.  After the legs have been attached to each module, 
the modules should be moved as close as possible to each other side by side on the mounting 
pad; moving the modules in accordance with the instructions given under Handling and Moving.  
The modules should then be placed together with the joining channel placed between the inside 
legs and bolted in place, Figure 3.  The joining channel and necessary bolts, nuts and washers are 
supplied with the unit. 
 
 
 

Содержание RH015

Страница 1: ...1 INSTALLATION OPERATION AND MAINTENANCE MANUAL FOR MODEL RH REMOTE HORIZONTAL AIR COOLED HEAT EXCHANGERS 5050 South National Dr Knoxville TN 37914 Telephone 317 227 2929 ...

Страница 2: ...D HEAT EXCHANGERS TABLE OF CONTENTS TOPIC PAGE Model Nomenclature 2 Inspection 2 Handling and Moving 2 Location 3 Assembly of Unit 3 Electrical Wiring 5 Piping 5 Start Up and Operation 5 Freeze Protection 5 Maintenance 6 Replacement Parts 7 ...

Страница 3: ... each unit is made and shipped in modules one module for the RH 035 and RH 045 two modules for the RH 055 RH 070 and RH 085 And as a preventative measure to guard against transportation damage each module is shipped on its side with the legs removed and crated on heavy duty skids It is advisable to move the modules as close as possible to its final location before uncrating It is up to the unit ri...

Страница 4: ...4 Fig 1b Lifting an RH module with slings ...

Страница 5: ...assembled except for the mounting legs Mounting legs are furnished with the necessary bolts nuts and washers The legs are not adjustable and are most easily assembled to the unit when the unit is still laying on its side as shipped Each leg is fastened to the bottom of the coil plenum by four bolts furnished with the unit Reference Figure 2 The larger RH Models RH055 and up are delivered as two se...

Страница 6: ...ctions should be made to the higher of the two openings supplied per module the outlet connection is made with the lower of the openings This piping arrangement is necessary to insure a cross counterflow coolant passage thru the unit for maximum heat transfer In most RH applications a surge tank is recommended to maintain a safe coolant level in the system and allow entrained air to escape from th...

Страница 7: ...mps fans Every 6 months Lubricant Use high grade ball bearing grease Use consistency of grease suitable for class of insulation stamped on nameplate as follows Insulation Class Consistency Type Typical Grease B or F 3 Lithium Base Shell Cyprina 3 Procedure If motor is equipped with Zerk fitting clean tip of fitting and apply grease gun Use one to two full strokes on motors CAUTION Keep grease clea...

Страница 8: ...8 REPLACEMENT PARTS If it becomes necessary to order parts please mention all identifying numbers such as model number or part number as found on the Kelvion nameplate ...

Отзывы: