13
2.3 ELECTRICAL CONNECTION OF THE UNIT
CAUTION: always disconnect the unit from the mains before carrying out any operation on electric parts.
Accomplish following recommendations:
•
Connect the unit to an efficient ground cable as required by the in force being norms.
•
Check the data on the unit’s name plate and select the correct cable section according to working amperage.
•
Dimension the power supply cable so that voltage drop at start-up does not exceed 10% of nominal voltage.
•
The on charge of the customer installed power supply cable must be a double insulated one.
•
Before unit’s start-up make sure that mains voltage and frequency correspond to those ones indicated on the unit’s
name plate.
2.4 WIRING PLAN
2.5 TECHNICAL DATA
MODEL
KCE34.00
KCE67.00
RATED VOLTAGE
110/240V 50HZ
110/240V 60HZ
110/240V 50HZ
110/240V 60HZ
230/1/50HZ
230/1/50HZ
MIN. CURRENT
0,2 A
0,4 A
MIN. POWER
40 W
80 W
MAX. CURRENT
0,8 A
1,6 A
MAX. POWER
180 W
360W
PROTECTION
FUSE 4gG
FUSE 4gG
EVAPORATIVE
CAPACITY
34 g/h
67 g/h
2.6 MAINTENANCE
CAUTION: ATTENTION: Before effecting any type of intervention disconnect the unit.
•
Cleaning operations and their frequency do depend on the specific working environment.
•
Check terminals and connections
½ year
L
PE
N