Keltech KRAD M Series Скачать руководство пользователя страница 60

Page 

60

 

Problem

Possible Cause

Repair

Comments

Dryer is
switched on,
indicator light
is lit but the
refrigerant
compressor
does not turn on.

The connection has 
inverted phases

Invert two phases

3-phase dryers are equipped with a phase controller
to  avoid  the  fans  from  turning  in  the  opposite
direction.

Refrigeration unit is not 
functioning

Check refrigeration comp-
ressor

Several  factors  can  cause  compressor  failure.
A  qualified  refrigeration technician needs to check
all the electrical and refrigerant circuit and controls.

The refrigerant highpressure
protection has tripped

The refrigerant safety high
pressure switch has tripped.

The  dryer  is  protected  against  excessively  high
refrigerant pressure. If the condenser efficiency has
reduced, the switch will trip. Manually reset the
switch.

In case of water cooled con-
densers, check the water
control valve

Excessive ambient tempe-
rature

Be sure that dryer is working
in temperatures lower than 
the
design conditions.
Designed conditions and
correction factors are desc-
ribed
in this manual.

A  high  ambient  temperature  may  cause  the
refrigerant system to operate at higher than normal
pressures.  Results  will  be  higher  than  normal
evaporator temperature.
lmportant: adequate air circulation around the dryer,
and proper ventilation in the equipment room should
guarantee  a  low  enough  ambient  temperature.

Dryer is
switched on,
but the refrigerant
compressor
does not turn on.

Excessive temperature on
crankcase of compressor.

Allow time to compressor to
cool down. Reason may be a
possible incorrect adjustment
of hot gas bypass valve or
shortage of refrigerant

Compressor  is  protected  against  overly  high
temperatures of the crankcase by a thermal switch.

Excessive compressed
air inlet temperature.

Be sure that dryer is working
in temperatures lower than
design conditions.

The  dryer  is  designed  for working  in  calculated
conditions  (see  description  in  this  manual).
If  conditions  are  exceeded,  the  dryer  will  be
overflowed, dew point will go up and protecting
devices can switch off.

Clogged condenser fins or
clogged water condenser.
Possible high crankcase
temperature
Possible loss of phase
Possible low voltage causing
overload trip Possible failed
compressor

Clear fins or water condenser
of all obstructions.

The clogged fins in the condenser will restrict the
air passage and reduce the refrigeration capacity,
causing  high  temperature  in  the  evaporator.
Same will occur if water condenser is clogged with
mud or  dirt. Air condenser and water condenser
should  be  periodically  checked  and  cleaned.
Protect  water  circuit  by  an  adapted  filter.

Too much compressed air 
flow.

Check actual flow
through the dryer.

This  dryer  is  designed  for a maximum air  flow  at
design  conditions.  If  too  much  air  is  pumped
into the dryer, water removal capacity may not be
sufficient, resulting in liquid carryover down stream.
Check  the  rated  output  the  air  compressor.

Faulty electrical wiring

Inspect the circuit

The compressor-on light should be wired into the
refrigerant compressor circuit. See wiring diagrams
in this manual.

One electrical protection
has tripped.

Reset the protection or
replace the blown fuse.

The dryer  is  protected against high amp draw by
fuse and/or overload relay that can trip in case of
need. Reset or replace fuse once, but do not persist
if it trips again, request assistance from a qualified
refrigeration contractor.

Dryer is switched
on but fan is not
running.

Fan has to run if refrigerant 
high
pressure reaches upper set 
point.

Check that compressed air
flows through the dryer. 
Check
that fan blades are free to 
move.
Check the fan pressure 
switch.

Fan  operates  automatically  to  keep  refrigerant
pressure below the maximum value. The fan can
stop if pressure is under the recommended setting.

When compressor
starts, it vibrates
a lot and makes
mechanical noise.

Compressor is slugging
liquid refrigerant
at start up.

Be sure the pre-heating 
period
of at least 2 hours is
respected

Refrigerant  may move  between  receivers when
refrigerant compressor is stopped and not heated,
especially if stopped for a long time.
This migration may cause liquid shock (slugging) in
valves specially on large dryers containing more
refrigerant

Содержание KRAD M Series

Страница 1: ...ESSED AIR DRYERS KRAD M SERIES KRAD 30M to KRAD 250M INSTRUCTION MANUAL WARRANTY NOTICE Failure to follow the instructions and pirocedures in this manual or misuse of this equipment will VOID its warr...

Страница 2: ...Page 2...

Страница 3: ...nnel 8 1 6 Maintenance by the user 8 2 INTRODUCTION TO THE KRAD DRYER 8 3 OPERATION 13 4 ELECTRICAL CONTROLLER 15 4 1 Digi Pro 15 4 2 ESD 3 18 5 TECHNICAL SPECIFICATIONS 26 6 DIAGRAMS 27 6 1 Air Flow...

Страница 4: ...ch liter sec under ISO 7183 A condition or 18 watts for each SCFM under ISO 7183 B condition D There should be no chemicals in the atmosphere that will damage the copper source Ammonia gas etc 1 3 Ins...

Страница 5: ...e dryer clean B Regularly check the correct operation of the condensate drain trap C Every six months check and clean the drain strainer by undoing the access screw and rinsing the filter with tap wat...

Страница 6: ...exchanger and evaporates by taking out the calories from the compressed air The gaseous refrigerant is sucked in the compressor and the cycle carries on E In order to keep the evaporation pressure ste...

Страница 7: ...ned to dissipate the heat to a water flow A shell and tube heat exchanger is used for this purpose 2 1 Points to Condenser in the Protection of Water Cooled Condenser The most common problem is the cl...

Страница 8: ...uring assembly E Water cooled dryers have a safety high pressure switch In case of cooling water failure the safety switch stops the dryer When the safety switch has tripped out it has to be manually...

Страница 9: ...n of the circuit 9 Condensate drain trap assembly Dismantling the drain is easy because it can be isolated from the air circuit under pressure with a ball valve The drain has to be depressurized befor...

Страница 10: ...ed Dewpoint value periodic maintenance interval display status report run time meter temperature unit selection F or C Digital Controller ESD3 Energy Saving Device ESD This device helps dryer save ene...

Страница 11: ...fficiency when the alarm status is active It is recommended to keep replacement filter elements in your stock in order to replace them when needed ATTENTION KRAD M range dryers have low pressure drop...

Страница 12: ...eheating period of minimum 4 hours before starting again to avoid any compressed air flow during preheating 3 Follow the daily starting and shut down preocedure 3 4 Daily starting and shut down A Push...

Страница 13: ...ance interval display Status report Run time meter Fahrenheit and Centigrade selection 4 1 2 Operation Using the Digi Pro controller as shown in the picture below 4 1 3 Menu Buttons To modify the para...

Страница 14: ...ndicates that Fahrenheit temperature unit is selected FAHRENHEIT UNIT MODE This mode shows that the dryer is ready for drying operation COMPRESSOR STANDBY MODE This mode shows that the dryer in the se...

Страница 15: ...ter Kit Serial No Warning Digit Code Note the 3 digit code on the website This is the solution code 5 Enter the solution code to the controller via COD parameter 6 Process is completed the alarm is to...

Страница 16: ...drain hose to be added must be connected to the drain system or atmosphere so that it does not create back pressure The drain hose that will be added should be connect directly to the drain system or...

Страница 17: ...5 19 85 6 1000 R513a 195 KRAD 125M 240 1 1 2 230V 1 50 Hz 1 07 6 38 7 98 28 85 8 1000 R513a 285 KRAD 150M 300 1 1 2 230V 1 50 Hz 1 19 5 46 7 23 30 85 8 1000 R513a 175 KRAD 200M 396 2 230V 1 50 Hz 1 23...

Страница 18: ...COMPRESSED AIR FLOW DRAIN FLOW M 2 AIR INLET AIR OUTLET S 3 4 5 6 7 8 DESCRIPTION POS QTY 1 2 3 4 5 6 7 8 9 10 11 COMPRESSOR 1 1 1 1 FAN MOTOR FAN SWITCH FILTER FILTER DRYER 1 1 1 2 1 1 EXPANSION VALV...

Страница 19: ...2 REFRIGERANT GAS FLOW COMPRESSED AIR FLOW DRAIN FLOW 4 5 9 DESCRIPTION POS QTY 1 2 3 4 COMPRESSOR 1 1 1 1 FAN MOTOR FAN SWITCH HIGH PRESSURE SWITCH FILTER FILTER DRIER 1 1 1 1 2 1 2 1 EXPANSION VALVE...

Страница 20: ...R 1 1 1 1 FAN MOTOR FAN SWITCH HIGH PRESSURE SWITCH FILTER FILTER DRIER 1 1 1 1 2 1 2 1 EXPANSION VALVE HEAT EXCHANGER 12 CHECK VALVE SOLENOID VALVE CONDENSER FILTERED DRAIN 13 1 BY PASS VALVE REFRIGE...

Страница 21: ...OW AIR INLET AIR OUTLET 11 DESCRIPTION POS QTY 1 2 3 4 5 6 7 8 9 10 11 COMPRESSOR 1 1 1 1 FAN MOTOR FAN SWITCH HIGH PRESSURE SWITCH FILTER FILTER DRIER 1 1 1 1 1 EXPANSION VALVE HEAT EXCHANGER 12 SOLE...

Страница 22: ...onnected to the point on the conducting body of the dryer specified by a sticker with the protective earth symbol next to it The size of the protective earth conductor should be minimum the size of th...

Страница 23: ...30 S16 NT 1 2 3 4 5 6 7 9 10 11 12 L N HP S10 M l M10 ELECTRICAL SUPPLY LINE SINGLE PHASE PROTECTION EARTH CABLES SIZE ELECTRICAL SPECIFICATIONS COMPRESSOR UN 230V 1 50Hz MKP 18 RLA 1 4A 0 190kW MKP 3...

Страница 24: ...kW MKP 240 RLA 0 68A 0 095kW S01 MAIN PROTECTION AND DISCONNECTING MEANS SHALL BE PROVIDED BY THE INSTALLER OF RESIDUAL CURRENT AUTOMATIC CIRCUIT BREAKER MKP 66 MKP 96 MKP 130 MKP 168 MKP 240 3x1 5mm2...

Страница 25: ...BY THE INSTALLER OF RESIDUAL CURRENT AUTOMATIC CIRCUIT BREAKER FIELD INSTALLED MAXIMUM SET 15 MKP 300 MKP 396 MKP 498 3x1 5mm2 3x1 5mm2 3x1 5mm2 EV3 Controller SP Power supply AL Alarm contact A20 Dr...

Страница 26: ...Page 26 6 3 KRAD M ID DIAGRAM DRAWINGS GENERAL ARRANGEMENTS...

Страница 27: ...46 1 in 241 50 2 00 9 51 1 in 50 83 50 2 00 0 in 270 00 2 00 10 63 1 in 51 17 2 01 in 0 5 02 in 270 09 10 63 in 2 00 08 in 347 00 13 66 in 264 29 10 41 in 12 50 49 in 21 35 84 in 38 29 50 1 51 0 in 38...

Страница 28: ...83 50 2 00 0 in 270 00 2 00 10 63 1 in 51 17 2 01 in 0 5 02 in 270 09 10 63 in 2 00 08 in 347 00 13 66 in 264 29 10 41 in 12 50 49 in 21 35 84 in 38 29 50 1 51 0 in 38 44 50 1 51 02 in 706 50 5 00 27...

Страница 29: ...8 in 38 65 2 00 1 52 1 in 130 91 5 15 in 2 00 08 in 340 91 13 42 in 2 00 08 in 693 11 2 00 27 29 1 in 770 60 2 00 30 34 1 in 80 20 2 00 3 16 08 in 207 20 2 00 8 16 08 in AIR OUTLET G 3 4 AIR INLET G 3...

Страница 30: ...8 in 38 65 2 00 1 52 1 in 130 91 5 15 in 2 00 08 in 340 91 13 42 in 2 00 08 in 693 11 2 00 27 29 1 in 770 60 2 00 30 34 1 in 80 20 2 00 3 16 08 in 207 20 2 00 8 16 08 in AIR OUTLET G 3 4 AIR INLET G 3...

Страница 31: ...8 in 38 65 2 00 1 52 1 in 130 91 5 15 in 2 00 08 in 340 91 13 42 in 2 00 08 in 693 11 2 00 27 29 1 in 770 60 2 00 30 34 1 in 80 20 2 00 3 16 08 in 207 20 2 00 8 16 08 in AIR OUTLET G 3 4 AIR INLET G 3...

Страница 32: ...0 5 94 in 2 00 08 in 140 50 50 5 53 02 in 410 00 50 16 14 02 in 38 55 50 1 52 02 in 701 30 2 00 27 61 08 in 796 30 2 00 31 35 08 in 107 90 2 00 4 25 08 in 278 90 2 00 10 98 08 in 140 50 50 5 53 02 in...

Страница 33: ...3 02 in 410 00 50 16 14 02 in 38 55 50 1 52 02 in 701 30 2 00 27 61 08 in 796 30 2 00 31 35 08 in 107 90 2 00 4 25 08 in 278 90 2 00 10 98 08 in 140 50 50 5 53 02 in 410 00 2 00 16 14 08 in 38 50 50 1...

Страница 34: ...0 5 94 in 2 00 08 in 140 50 50 5 53 02 in 410 00 50 16 14 02 in 38 55 50 1 52 02 in 701 30 2 00 27 61 08 in 796 30 2 00 31 35 08 in 107 90 2 00 4 25 08 in 278 90 2 00 10 98 08 in 140 50 50 5 53 02 in...

Страница 35: ...00 08 in 802 72 31 60 in 2 00 08 in 1046 92 41 22 in 2 00 08 in 199 00 2 00 7 83 08 in 351 30 2 00 13 83 08 in CONTROLLER 564 83 22 24 in 56 58 2 23 in 124 00 4 88 in 400 00 15 75 in M8 x 4pcs AIR OU...

Страница 36: ...00 08 in 802 72 31 60 in 2 00 08 in 1046 92 41 22 in 2 00 08 in 199 00 2 00 7 83 08 in 351 30 2 00 13 83 08 in CONTROLLER 564 83 22 24 in 56 58 2 23 in 124 00 4 88 in 400 00 15 75 in M8 x 4pcs AIR OU...

Страница 37: ...giPro 506 556 875 78 KRAD 125M ADFK3 REV1 DigiPro 506 556 875 83 KRAD 150M ADFK3 REV1 DigiPro 506 556 875 86 KRAD 200M ADFK4 REV1 DigiPro 648 678 1157 160 KRAD 250M ADFK4 REV1 DigiPro 648 678 1157 165...

Страница 38: ...Page 38 8 KRAD M EXPLODED DIAGRAMS SPARE PART LISTS...

Страница 39: ...Page 39 8 1 ED Spare Part List KRAD 15M 34 2 3 4 5 33 31 32 24 23 27 17 16 25 36 40 38 39 26 37 7 42 1 35 29 20 21 27 22 6 10 12 9 8 15 10 11 14 12 13 29 30 28 18 43...

Страница 40: ...31920100 AIR DRYER HANDLE 1039220100 1062760100 1057340100 1057350100 1 1 DPR0 INDICATOR 30A 230V DRYER FRONT PANEL SINGLE HOLE PASS UNION 6mm 1026290100 MK10 60 EXPANSION VALVE 1025980100 1 2 CORNER...

Страница 41: ...Page 41 8 1 ED Spare Part List KRAD 25M 34 2 3 4 5 33 31 32 24 23 27 17 16 25 36 40 38 39 26 37 7 42 1 35 29 20 21 27 22 6 10 12 9 8 15 10 11 14 12 13 29 30 28 18 43...

Страница 42: ...1 1037930100 1 1 1 1 1 2 1 1026100100 1023220100 AIR DRYER HANDLE 1039220100 MK10 60 EXPANSION VALVE 1025980100 1057340100 1057350100 1 1 DPR0 CONTROLLER 30A 230V DRYER FRONT PANEL PASS UNION 6mm 102...

Страница 43: ...Page 43 8 1 ED Spare Part List KRAD 40M 34 35 36 40 2 3 4 5 37 38 31 27 9 8 6 7 21 25 26 15 16 22 10 17 18 19 23 24 42 28 20 20 13 14 29 41 28 30 12 42 8 33 1 39 43 11 44 45...

Страница 44: ...GED GREY 1037460100 AIR DRYER HANDLE 1039220100 MK40 50 60 06 PANEL 7012 THICK RAGGED GREY 1042000100 MK40 50 60 05A PANEL GALVANIZED MK40 50 60 04 PANEL 7012 THICK RAGGED GREY 1000670600 1040160100 2...

Страница 45: ...Page 45 8 1 ED Spare Part List KRAD 60M 2 3 4 5 34 35 36 37 38 40 31 9 8 27 6 7 21 25 26 15 16 22 10 17 18 19 23 24 42 28 20 20 13 14 29 41 28 30 12 42 32 33 1 39 43 11 44 45...

Страница 46: ...E FITTINGS 1024990100 1038050100 1024420100 1045560100 1026430100 1026100100 1026750100 1029510100 1026770100 1040740100 1002090100 1037460100 1043740100 1047510100 1023220100 1031920100 1612250732 10...

Страница 47: ...Page 47 8 1 ED Spare Part List KRAD 80M 2 3 4 5 34 35 36 37 38 40 31 9 8 27 6 7 21 25 26 15 16 22 10 17 18 19 23 24 42 28 20 20 13 14 29 41 28 30 12 42 32 33 1 39 43 11 44...

Страница 48: ...1038050100 1024430100 1045560100 1026430100 1026100100 1026750100 1029510100 1026770100 1040740100 1002090100 1037460100 1043740100 1047510100 1023220100 1031920100 1034620100 1025270100 1057820100 10...

Страница 49: ...Page 49 8 1 ED Spare Part List KRAD 100M 2 3 4 5 6 10 11 40 41 42 8 21 23 25 24 26 27 30 31 34 28 29 32 12 37 38 39 1 20 19 22 15 15 33 17 43 35 12 36 16 32 18 9 13 7 44 14 45 46...

Страница 50: ...THICK RAGGED GREY 1044300100 MK70 80 90 05 PANEL GALVANIZED MK70 80 90 04A PANEL 7012 THICK RAGGED GREY 1047010100 1001310500 MK70 80 90 01 PANEL 7012 THICK RAGGED GREY 1047230100 1039220100 GKON 405...

Страница 51: ...Page 51 8 1 ED Spare Part List KRAD 125M 2 3 4 5 6 10 11 40 41 42 8 21 23 25 24 26 27 30 31 34 28 29 32 12 37 38 39 1 20 19 22 15 15 33 17 43 35 12 36 16 32 18 9 13 7 44 14 45 46...

Страница 52: ...0 90 08 PANEL 7012 THICK RAGGED GREY 1045220100 MK70 80 90 07 PANEL 7012 THICK RAGGED GREY MK70 80 90 02 PANEL 7012 THICK RAGGED GREY 1046660100 MK70 80 90 06 PANEL 7012 THICK RAGGED GREY 1044300100 M...

Страница 53: ...Page 53 8 1 ED Spare Part List KRAD 150M 2 3 4 5 6 10 11 40 41 42 8 21 23 25 24 26 27 30 31 34 28 29 32 12 37 38 39 1 20 19 22 15 15 33 17 43 35 12 36 16 32 18 9 13 7 44 46 14 45...

Страница 54: ...90 08 PANEL 7012 THICK RAGGED GREY 1045220100 MK70 80 90 07 PANEL 7012 THICK RAGGED GREY MK70 80 90 02 PANEL 7012 THICK RAGGED GREY 1046660100 MK70 80 90 06 PANEL 7012 THICK RAGGED GREY 1044300100 MK...

Страница 55: ...Page 55 8 1 ED Spare Part List KRAD 200M 2 4 6 7 13 16 17 23 24 25 26 33 34 35 36 37 38 39 40 19 20 3 5 22 47 18 15 14 27 27 8 21 10 5 43 11 22 9 44 41 46 30 32 28 1 29 31 45 42 12 48 49 50...

Страница 56: ...100 MK100 110 06 PANEL GALVANIZED 1001740700 AIR DRYER HANDLE 1039220100 BALL VALVE 1 4 Mini Metal Handle EXPANSION VALVE TUBE 5 MK100 110 120 130 CONNECTION KIT ALD 1 2 1057340100 1057350100 DPR0 CON...

Страница 57: ...Page 57 8 1 ED Spare Part List KRAD 250M 2 4 6 7 13 16 17 23 24 25 26 33 34 35 36 37 38 39 40 19 20 3 5 22 47 18 15 14 27 27 8 21 10 5 43 11 22 9 44 41 46 30 32 28 1 29 31 45 42 12 48 49 50...

Страница 58: ...9005 THIN RAGGED BLACK 1044400100 1049460100 MK100 110 05 PANEL 9005 THIN RAGGED BLACK 1044820100 MK100 110 06 PANEL GALVANIZED 1001740700 1038380100 MK100 110 08 PANEL 7012 THICK RAGGED GREY 10423701...

Страница 59: ...ty control S13 Low pressure security control S20 Refrigerant temperature control S21 Air temperature control Motors M01 Refrigerant compressor motor M10 Fan motor Thermal protections P01 Refrigerant c...

Страница 60: ...p and protecting devices can switch off Clogged condenser fins or clogged water condenser Possible high crankcase temperature Possible loss of phase Possible low voltage causing overload trip Possible...

Страница 61: ...ory should be contacted if the unit is in warranty Refrigeration system is not functioning Check to be certain refrigerant compressor is running To check if the compressor is running check compressor...

Страница 62: ...may cause pressure drop such as valves elbow tees etc on the drain connection Drain should be at atmospheric pressure at all times Any back pressure will result in failure and malfunction Warranty Sta...

Отзывы: