18
Please download the instruction how to use Identification angle function from our website.
www.kellycontroller.com/support.php
4.1
Step 1
(1) Low Volt: The min voltage of reporting this fault - Range 18~105
Controller will not operate when battery voltage is near the value so as to protect battery.
Suggestion: Set according to the practical situation.By default,it is set at 18V.
(2) Over Volt: The max voltage of reporting this fault - Range 18~105
Controller will not operate when battery voltage is higher than the value so as to protect battery
and controller.
Suggestion: Set according to the practical situation.
Controller Rated voltage Under Voltage Range (V) Over Voltage Range(V)
60V
18~80
18~80
72V
18~90
18~90
84V
18-105
18-105
96V
18-120
18-120
Figure 4.1
(3) Current Percent: Phase Current Percent. Range: 20~100
Functional description: The max motor current is (The Value * Peak Current of the Controller).
Suggestion: Factory default is 100%.
(4) Battery Limit: Battery Limit Current, Limit the max value of Battery Current. Range: 20~100
Functional description: Set max battery current so as to protect battery. A lower value means a
lower battery output current and better protective effect. But excessively low value will affect
acceleration.
Suggestion: Factory default is 100%.
(5) Identification Angle: Please download the instruction to how to use Identification angle
function from the website.
www.kellycontroller.com/support.php
If you can read 85 in Identification Angle item,that is to say,the system is stable and
normal.Please fill in 170 for Identification Angle item in user program.Then
please click Write button in user program.Please wait a few seconds before restart the power
supply.You will see some info on Monitor screen after power supply is
reset.If you see Reset error on the Monitor screen,that is to say,the auto_Identification is
finished.You can see 85 in the Identification Angle item again.And the controller will
blink error code.This is normal.Please reset the power supply again.Then everything will be
fine.The motor is ready to be drived by the KLS controller.
Range: 85 or 170,nothing else.
Содержание KLS-H
Страница 2: ...Kelly KLS H Brushless Motor Controller User s Manual V1 10 Rev 1 10 Jun 2017 ...
Страница 3: ......
Страница 10: ...7 Figure 1 KLS7215H KLS7218H KLS6022H KLS6030H KLS7230H mounting holes dimensions dimensions in millimeters ...
Страница 11: ...8 Figure 2 KLS7245H mounting holes dimensions dimensions in millimeters ...
Страница 12: ...9 Figure 3 KLS7250H mounting holes dimensions dimensions in millimeters ...
Страница 13: ...10 Figure 4 KLS7275H mounting holes dimensions dimensions in millimeters ...
Страница 14: ...11 Figure 5 KLS72xxx 8080H KLS96xxx 8080H mounting holes dimensions dimensions in millimeters ...