5/2004                                    Manual for connection and operation of the EV-94 EB                         page 17 of 28

-

Use button 2 or button3 (middle resp. right button) to select the desired signal edge.

Display

Signal edge

Note

PoS

Positive

The counter is triggered on the positive (ris-
ing) edge.

nEG

Negative

The counter is triggered on the negative (fal-
ling) edge.

-

Press button 1 to validate your selection, the display shows “

EdGE

“ again.

-

When pressing button 1 again, the display will show “

diu

“ (divisor = pre-scaling factor).

-

Use button 2 and button 3 to select the desired pre-scaling factor.

The incoming pulses will be divided with the selected pre-scaling factor, after that they will be transmitted to the de-
vice for further processing.
By this factor you can adapt the device to your transmitter or select a pre-scaling factor for large values
Example 1: Your flow rate transmitter supplies 165 pulses per litre. When setting a pre-scaling factor of 165 every
165th pulse (so 1 pulse per litre) will be used for further processing.

     

Example 2: Your transmitter is supplying about 5 000 000 pulses during the measurement, which exceeds the limit
of the GIA20EB. But when setting a pre-scaling factor of 1000 only every 1000th pulse is used for further process-
ing. So you only got a value 5000 which won’t exceed the limit of the EV-94 EB

.

-

Press button 1 to validate your selection. The display shows “

diu

“ again.

-

Press button 1 again. The display shows “

Co.Hi

“ (counter high 

= upper counting range limit

).

-

Use button 2 and button 3 to select the maximum pulse-count (after pre-scaling factor) for the counting
process.

Example: Your flow rate transmitter is supplying 1800 pulses per litre, you selected a pre-scaling factor of 100 and
you are expecting a maximum flow rate of 300 litres during the measurement. With a pre-scaling factor of 100 se-
lected, you will get 18 pulses per litre. With a maximum flow rate of 300 litres you will be getting a pulse count of 18
* 300 = 5400.

-

Press button 1 to validate your selection. The display shows “

Co.Hi

“ again.

-

When pressing button 1 again, the device will be displaying “

dP

“ (decimal point).

-

Use button 2 and button 3 to select the desired decimal point position.

-

Press button 1 to validate your selected decimal point position. The display shows “

dP

“ again.

-

Press button 1 again. The display shows “

di.Hi

“ (display high 

= upper display range limit

).

-

Use button 2 and button 3 to set the value to be displayed when the maximum pulse (setting of co.Hi)
count is reached.

Example: Your flow rate transmitter is supplying 1800 pulses per litre and you are expecting a maximum flow rate of
300 litres. You selected a pre-scaling factor of 100 and a counter range limit of 5400.  When wanting a resolution of
0.1 litres shown in the display of the device you would have to set the decimal point position to ---.- and a display
range limit of 300.0.

-

Press button 1 to validate your selection. The display shows “

di.Hi

“ again.

-

Press button 1. The display will show “

Li

“ (Limit 

= measuring range limit

).

-

Use button 2 and button 3 to select the desired measuring range limit (counter range limit).

Display

Measuring range limit

Note

off

Inactive

Exceeding of the counter range is tolerable
until you reach the maximum measuring
range limit.

on.Er

active, 

(error indicator)

The measuring range is exactly bounded by
the selected counter-range-limit. When ex-
ceeding or shortfalling of the limit the device
will display an error message.

on.rG

active, 

(measuring range limit)

The measuring range is exactly bounded by
the selected counter-range-limit. When ex-
ceeding or shortfalling of the limit the device
will display the upper counter-range-limit or 0

Hint:

The lower counter-range-limit (for configured downwards counter) is fixed to 0

Содержание EV-94 EB

Страница 1: ...nual for connection and operation of the EV 94 EB page 1 of 28 Manual for connection and operation of EV 94 EB Version 2 0 KELLER AG f r Druckmesstechnik St Gallerstr 119 CH 8404 Winterthur www keller...

Страница 2: ...ND 9 3 3 2 Connection with configured high side switching output PNP output switching to Uv 9 3 4 3 Connection with configured push pull switching output 10 3 5 Commen wiring of several GIA20EB 10 4 C...

Страница 3: ...ce must be switched off and must be marked against using again in case of obvious malfunc tions of the device which are e g visible damage no prescripted working of the device storing the device under...

Страница 4: ...ne EASYBUS interface for communicating with a host computer that makes the device to a full functions EASYBUS module When leaving our factory the EV 94 EB has been subjected to various inspection test...

Страница 5: ...ge 4 and 5 9 V 28 V 0 V 30 V NPN 30V I 1A Not short circuit pro tected Switching output 1 and 2 PNP 1 and 3 2 and 3 I 200mA Not short circuit pro tected Input mA 0 mA 20 mA 0 mA 30 mA Input 0 1 2 V Fr...

Страница 6: ...individual transmitter supply without individual transmitter supply Note Sig and Uv of the Transmitter must be the same potential _ Supply 9 28 VDC 4 20mA Transmitter Uv Uv _ Supply for Transmitter 4...

Страница 7: ...reated like an active signal and you have to configure the de vice as TTL Hint when connecting the device You have to take care not to exceed the limits of the input voltage respective the input curre...

Страница 8: ...counter When connecting contact 8 with GND e g contact 7 the counter will be reset You can do this manually e g with the help of a push button or automatically with one switching output of the device...

Страница 9: ...voltage and of the maximum current of the switching outputs not even for a short period of time Please take extreme care when switching inductive loads like coils or relays etc because of their high...

Страница 10: ...sure to observe the following points When several EV 94 EB s are connected to the same power supply unit it is highly recommended to isolate the sensors measuring transducers etc When the sensors mea...

Страница 11: ...displays InP INPUT Use button 2 or button 3 middle resp right button to select the input sig nal see table below Validate the selection with button 1 the left button The display will show InP again De...

Страница 12: ...ould display when a 0mA 4mA resp 0V input signal is attached Validate the selected value by pressing button 1 The display shows di Lo again Press button 1 again the display will show di Hi Display Hig...

Страница 13: ...essing button 1 the display shows SEnS Use button 2 or button 3 middle resp right button to select your desired input signal Display Input signal RTD Notes Pt0 1 Pt100 3 wire Meas range 50 0 200 0 C 5...

Страница 14: ...al circuitry you have to select TTL as your desired input signal Validate your selected input signal by pressing button 1 The display shows SEnS again When pressing button 1 again the display will sho...

Страница 15: ...e your selection The display shows FiLt again Now your device is adjusted to your signal source The only thing you left do is to adjust the outputs of the device When pressing button 1 again the displ...

Страница 16: ...ter starts counting upwards from 0 according to its settings The downwards counter starts counting downwards from the upper value that had been selected Feature The current value of the counter can be...

Страница 17: ...g the measurement With a pre scaling factor of 100 se lected you will get 18 pulses per litre With a maximum flow rate of 300 litres you will be getting a pulse count of 18 300 5400 Press button 1 to...

Страница 18: ...s to display InP When pressing button 1 again the device will display Adr address Use button 2 and button 3 to select the desired address 0 239 of the device Press button 1 to validate the selected de...

Страница 19: ...ready made for output 1 2 dEL delay of output 2 2 out kind of output 2 2 Err preferred state of output 2 When pressing button 1 again only if you configured the device with min max alarm the device wi...

Страница 20: ...2 point controller with min max alarm digital 2 point controller min max alarm 2P AL 5 2 min max alarm common min max alarm AL F1 5 3 min max alarm individ ual max alarm min alarm AL F2 5 3 5 1 2 poin...

Страница 21: ...1 off When the temperature rises above 20 C the device turns its output 1 on when falling below 22 C the device will turn its output 1 off Note Depending on the inertia of your cooling circuit an ove...

Страница 22: ...tton 1 again the device will be displaying A dEL delay of the alarm function Use button 2 and button 3 to set the desired delay of the alarm function Note The unit of the value to be set is in sec The...

Страница 23: ...FFS again When pressing button 1 again the device will be displaying SCAL scale slope Use button 2 and button 3 to select the desired slope adjustment The slope adjustment will be entered in The value...

Страница 24: ...PC e g EBW1 EBW64 EB2000MC Software for communication with the device EBS9M 9 channel software for displaying a measured value EASYCONTROL multi channel software for real time recording and displayin...

Страница 25: ...low and should be increased Err 7 System error The device features an integrated self diagnostic function which checks essential parts of the de vice permanently When detecting a failure error messag...

Страница 26: ...0 200 0 C resp 58 0 392 0 F 0 1 C resp F 3 wire connection max perm line resistance 20 Ohm Pt100 1 C 200 850 C resp 328 1562 F 1 C resp F 3 wire connection max perm line resistance 20 Ohm RTD probes...

Страница 27: ...4 Hz Output functions 2 point 3 point 2 point with alarm min max alarm common or individual Switching points arbitrary Display approx 10 mm height 4 digit red LED display Handling 3 push buttons acces...

Страница 28: ...di Hi Acknowledge high input value Press button 1 Li Measuring range limit Limit button 2 or 3 off on Er on rG Select measuring range limit off button 1 Li Acknowledge measuring range limit button 1...