1  Specifications 

Mechanical 

Chassis Construction 

Robust 18 Ga. Grey powder-coated steel. Hinged & Pad-lockable, or 
screw-on cover style available. 

Weight 

2.0 Lbs. 

Operating Temperature 

-20 to 50°C  (-4 to 122°F) 

Operating Humidity 

15 – 90 %RH 

Storage Temperature 

0 to 20°C  (32 to 68°F)  to minimize sensor degradation. 

Case Dimensions (H x W x D) 

6.4” x 5.9” x 2.4”   (163.5 x 150.8 x 60.7 mm) 

Sensor Vents 

Natural Ventilation through 18  0.1” diameter (2.54 mm) vents. 

Recommended calibration cap diameter 

20.5 mm (.807”) 

External Indicators 

Separate tri-color LEDs indicates operational status of each senor. 

Knockouts 

4 trade ½” knockouts (1 per side) 

 

Electrical 

Operating Power Voltage 

14 to 30 VAC (RMS) or 15 to 45 VDC 
polarity independent, isolated power supply 

Power Consumption 

< 5W 

Control Relays  

Two separate SPDT relays for warning and alarm outputs. 
UL rated: 10 Amps max at 277 VAC (RMS) or 30 VDC. 

Concentration Reporting Outputs 

Two powered 4–20 mA current loop outputs (one for each sensor). 
4 mA output => 0 ppm,  •  20 mA => full scale output. 
Maximum loop resistance:  510Ω 

Termination 

Pluggable  screw-terminals  for  use  with  12  AWG  or  thinner  wire.   
Stranded wire recommend for 18 AWG or heavier wire. 

 

Carbon Monoxide Sensor (CO) 

Sensor Type 

Electrochemical 

Measurement Range 

0 – 200 ppm 

Analog Output Range 

4mA to 20mA (corresponds to 0 to 200 ppm) 

Accuracy 

±5% of Full Scale  (typical) 

Calibration Interval 

6 Months;  factory calibrated when new 

Sensor Life 

2 Year typical 

Calibrated Field-Replaceable Sensor 

KMOD-CO  

 

Nitrogen Dioxide (NO

2

Sensor Type 

Electrochemical 

Measurement Range 

0 –10 ppm 

Maximum Permissible Exposure 

150 ppm  

Analog Output Range 

4mA to 20mA (corresponds to 0 to 10ppm) 

Accuracy 

± 0.75 ppm  (typical) 

Calibration Interval 

6 Months;  factory calibrated when new 

Sensor Life 

2 Year typical 

Calibrated Field-Replaceable Sensor 

KMOD-NO2 

Содержание KCO-NO2

Страница 1: ...PRELIMINARY KCO NO2 Sensor User s Manual 90 0201 01 ...

Страница 2: ... Manual 90 0201 01 Kele 3300 Brother Blvd Memphis TN 38133 Page 2 WWW KELE COM Revision History Revision Date Changes 90 0201 00 3 18 21 Original Issue 90 0201 01 4 12 21 Change CO sensor ToS to 200 ppm from 100 ppm ...

Страница 3: ...n 7 4 Operational Description 8 4 1 Normal operation 8 4 2 Startup 9 4 3 Setting Warning and Alarm Threshold 10 4 4 Warning and Alarm Conditions 10 4 5 Abnormal operation 10 5 Sensor Calibration 11 5 1 Calibration Gases 11 5 2 Calibration Procedure 13 6 Sensor Module Replacement 14 6 1 Sensor Errors 14 6 2 Replacement Sensors 14 6 3 Field Replacement of Sensor Modules 14 7 Warranty 15 7 1 Duration...

Страница 4: ...W Control Relays Two separate SPDT relays for warning and alarm outputs UL rated 10 Amps max at 277 VAC RMS or 30 VDC Concentration Reporting Outputs Two powered 4 20 mA current loop outputs one for each sensor 4 mA output 0 ppm 20 mA full scale output Maximum loop resistance 510Ω Termination Pluggable screw terminals for use with 12 AWG or thinner wire Stranded wire recommend for 18 AWG or heavie...

Страница 5: ...ibration free surface near the middle of the area to be monitored about 5 feet above the floor It should be located where there is free airflow avoid corners or recesses The air vents on the sides of the enclosure should not be closer than 1 foot from the nearest perpendicular wall and must not be obstructed or painted over May be mounted in any orientation but hinge on the left side is most commo...

Страница 6: ...igure 6 2 Unplug the desired analog output screw terminal either the NO2 or CO terminal 3 Connect the signal wires paying close attention to the polarity 4 Plug the analog output screw terminal back into the controller 5 Repeat this process for both analog outputs then reconnect power 3 2 Relay Connections The controller has two SPDT dry contact relay output terminals shown in Figure 4 The relays ...

Страница 7: ...ed to the controller s relay output to the COM location of screw terminal 5 Plug the relay output screw terminal back into the correct location on controller board 3 3 Power Connection Power connection to the controller is made at the two terminal screw connector located at the bottom right side of the board highlighted in Figure 6 Power to the controller can be either AC or DC voltage DC voltage ...

Страница 8: ...unciator when elevated levels of carbon monoxide generated by gasoline engines and abbreviated CO or nitrogen dioxide from diesel engine exhaust and abbreviated NO2 are detected If the concentration of either gas exceeds its programmed alarm value a second set of alarm contacts is operated to trigger an alarm The controller has two independent sensor modules one for sensing carbon monoxide CO the ...

Страница 9: ...reshold the WARNING relay is deactivated the same action occurs for the ALARM relay The front cover has two LEDs indicators one for the CO and the other for the NO2 sensor module These LEDs illuminate different colors to indicate normal green warning yellow alarm red and error blinking red conditions see Table 3 The concentrations of CO and NO2 in the ambient air are reported at each senor s analo...

Страница 10: ...s change color to indicate the controller s current operational status Table 3 shows the behavior of the front panel LEDs during normal operation Two dry contact SPDT relays are provided on the controller these relays activate during warning and alarm conditions Refer to Section 3 3 for location and wiring information Readings for the two sensors are independently reported on the controller s two ...

Страница 11: ...or instructions on how to assemble and operate its gas supply components Each sensor must be sequentially calibrated with two different gases The Zero gas is the same for both sensors and is used for the zero calibration which must be done first The span gas is different for each sensor and used for the span calibration which MUST be done ONLY AFTER a successful zero calibration Each calibration i...

Страница 12: ...KCO NO2 User s Manual 90 0201 01 Kele 3300 Brother Blvd Memphis TN 38133 Page 12 WWW KELE COM FIGURE 10 Calibration Flowchart This procedure must be done twice first as Zero then as Span for each sensor ...

Страница 13: ...f not If successful blinking GREEN The sampling completed successfully Disconnect the gas and press the same button that started the calibration again for 3 seconds indicating the cal gas has been removed The LED then blinks GREEN YELLOW for 2 minutes indicating that the calibration was accepted If NOT successful blinking RED The sampling can be re started while the LED is blinking RED by pressing...

Страница 14: ...or has failed When front panel status LED is blinking red the sensor is no longer operational and must be replaced 6 2 Replacement Sensors Calibrated sensor modules are available from Kele Carbon Monoxide CO Nitrogen Dioxide NO2 Cal Kit KMOD CO KMOD NO2 UCK 3 kit 6 3 Field Replacement of Sensor Modules Sensor modules must be replaced when they reach their End of Life To replace a sensor module 1 O...

Страница 15: ...r ensuring that any product into which Products are incorporated other components used with DCS Products and the purposes for which DCS Products are used are appropriate and compatible with those Products If Kele determines that a returned Product does not conform to this warranty it will at Kele s discretion either repair or replace that Product and will ship the Product back to Buyer free of cha...

Страница 16: ...he sensor has reached the end of its operating life and must be replaced Contact Kele for a calibrated replacement module In harsh environments a sensor may fail prematurely During normal operation the sensor is regularly tested to detect common failures If a failure is detected the front panel status LED for that sensor will blink red and its concentration reporting analog output will stay at 20 ...

Отзывы: