List of p

Degrees 0.1 to 99.9

0.1

r1

Degrees -200 to r2

-200

r2 Higher value for SP

Degrees r1 to 600

600

r4 Set Point variation

Degrees 0.1 to 200

d0 Cooling or heating control

Option

Co/Ht

Co

c0 Minimum stopping time

Seconds 0 to 999

0

c2 Output status with probe error Option

On/OFF

On

P1 Ambient probe adjustment

Degrees -99.9 to 99.9

0

P4 Decimal point

Option

no/yes

yes

P5 3 wires Pt100

Option

no/yes

yes

E0 Digital input configuration

Option

OFF/Al/ES/HC  OFF

H5 Access code to parameters

Numeric 0 to 255

0

A0 Alarm 1 hysteresis

Degrees 0.1 to 99.9

1.0

A1 Alarm 1 threshold

Degrees 0.0 to 999

0

A2 Alarm 1 exclusion time

Seconds 0 to 999

0

A3 Alarm 1 type

Option

OFF/HI/LO

OFF

A4 Alarm 2 hysteresis

Degrees 0.1 to 99.9

1.0

A5 Alarm 2 threshold

Degrees 0.0 to 999

0

A6 Alarm 2 exclusion time

Seconds 0 to 999

0

A7 Alarm 2 type

OFF/HI/LO

OFF

A8 Alarm verification time

Seconds 0 to 999

0

r1

 = 

r2

 = Higher value for SP

r4

 = Set point variation for 

 If digital input 

configuration E0  ES this value modify the set point as follows

If d0 
If d0 

Cooling or heating control

c0 

=

 

Minimum stopping time of the load

c2 

= Output status with probe error

P1 

= Ambient probe adjustment

P4 

= Decimal point

P5 

= 3 wires Pt100. 

E0

 = Digital input configuration

H5 

= Access code to parameters (it is set to 00 from factory)

A0, A1, A2, A3

 = Alarm 1 parameters

arameters

  

Description

Units

Range

Factory

SP  Set Point

Degrees r1 to r2

0

r0

Parameter descriptions

Differential or hysteresis
Lower value for SP

(energy saving)

SP 

=

 

Set point. Temperature we wish to regulate the machine 

(variable from r1 to r2)

r0 

=

 

Differential or hysteresis
Lower value for SP

energy saving.

= :

= Ht new SP = SP - r4
= Co new SP = SP + r4

d0

 =

If d0 = Ht and TS is the temperature of ambient probe:

If TS >= SP the load is disconnected
If TS <= SP - r0 the load is connected

If d0 = Co   then:

If TS <= SP the load is disconnected
If TS >= SP + r0 the load is connected

no = 2 wires, yes = 3 wires

OFF = Digital input disabled
Al = External alarm (if input is short-circuited)
ES = Energy Saving. Set Point value is modified in r4.
HC = if input is short-circuited, it changes to Heat or Cold 
depending of d0 value. 

if d0 = Heat it changes to Cold mode.  
if d0 = Cold it changes to Heat mode.

If A3=OFF alarm 1 disabled
If A3=HI then a high-temperature alarm is set:

if TS   >= SP+A1 the alarm 1 is activated
if TS   <= SP+A1-A0 the alarm 1 is de-activated

If A3=LO then a low-temperature alarm is set:

if TS   <= SP-A1 the alarm 1 is activated
if TS   >= SP-A1+A0 the alarm 1 is de-activated

The alarm 1 is not activated until the time since instrument is turn 
on is higher than A2

Option

A4, A5, A6, A7

 = Alarm 2 parameters (similar to alarm 1)

A8

 = Alarm verification time. Time since the alarm situation 

occurs until its signalling. 

Parameter programming

Led indication, buzzer and display messages

Alarm validation

(It affects to Alarm 1, Alarm 2 and 

External alarm)

Set Point (SP) is the only parameter the user can
access without code protection.

•Press SET. 

SP 

text will appear on the display.

•Press SET again. The real value is shown on the display.
•The value can be modified with the UP and DOWN arrows.
•Press SET to enter any new values.
•Press SET and DOWN at the same time to quit
programming or wait one minute and the display will
automatically exit programming mode.

Access to all code protected parameters.

•Press SET for 8 seconds. The access code value 00 is shown on 
the display (unit comes with code set at 00 from factory).
• With the UP and DOWN arrows, code can be set to user needs.
•Press SET to enter the code. If the code is correct, the first 
parameter label   is shown on the display (SP).
• Move to the desired parameter with the UP and DOWN
Keys.
•Press SET to view the value on the display.
• The value can be modified with the UP and DOWN arrows.
•Press SET to enter the value and exit.
• Repeat until all necessary parameters are modified.
•Press SET and DOWN at the same time to quit programming or 
wait one minute and the display will automatically exit programming 
mode.

*The keyboard code can be reset to ZERO by turning off the 
controller and turning it on again while keeping the SET key 
depressed.

The led OUT

 

indicates if the load is connected or not.

In normal operation, the probe temperature will be shown on the 
display.
In case of alarm or error, the following messages can be shown (the 
alarm led is ON and buzzer sounds):
• 

Err 

= Memory Error.

• 

ooo 

= Open Probe Error.

• --- = Short-circuit Probe Error.
• A1H = High temperature alarm 1.
• A1L = Low temperature alarm 1.
• A2H= High temperature alarm 2.
• A2L = Low temperature alarm 2.
•ALE = External alarm.

In case of alarm the internal buzzer and alarm led is activated. The 
display shown the corresponding message. The buzzer and display 
message can be silenced pressing the SET and DOWN arrows at 
the same time. If alarm continues after A8 it is signalling again. 