background image

 

AAF, OAF, GSM, VMF 

 

 

Slab Element Replacement (OAF 11/2) 

 

See section 5.2 - wearing a face mask is recommended. 

 

The twin chamber contains two slab elements which form the heated floors of the upper and lower 
sections. The elements are made of refractory cement in which coiled heating wire s embedded. 

 

Disconnect the furnace from the electrical supply. Remove the furnace back panel and make a 
simple drawing of how the wires are connected to the elements. 

 

Release the screws which secure the element terminal blocks on the faulty elements. (Element tails 
become brittle with use, so care must be taken during removal, unless you intend to replace them 
all.) 

 

Open the furnace door. With a hacksaw blade cut grooves in the front brick sides sufficient only to 
enable the elements to slide out forwards. Remove the elements and tidy these grooves with a file. 

 

Check the condition of the insulation adjacent to the faulty element(s). Replace the insulation if it 
is excessively cracked of has radically changed colour or texture. 

 

Slide in the new element(s). Guide the tails through the existing holes in the insulation and re-
connect the element terminal blocks. 

 

Cut off any excess tail wire, replace the back panel and reconnect the electrical supply. 

 

Switch the furnace ON and heat to 900°C without interruption, then soak for 1 hour. 

 

Check that the furnace is controlling properly to rule out the possibility that the previous element 
failed because of a fault elsewhere in the control circuit. 

5.9  VMF 10/6 Element Replacement 

 

See section 5.2 - wearing a face mask is recommended. 

 

The heating elements are vacuum formed modules; they are fragile, so spare elements are supplied 
complete in an insulation box to avoid damage. 

 

Disconnect the furnace, remove the back panel, make a plan of all the internal connections to the 
back of the heating chamber and disconnect. Remove the thermocouple(s) and support tube(s). 

 

Using a socket spanner undo the four bolts that fasten the insulation box. These are located under 
the insulation box in the two cross supports. 

 

Remove the insulation box by carefully sliding it out through the back of the furnace case. 

 

Carefully slide in the new insulation box, and fasten the four bolts. DO NOT support the element 
by putting your hand inside the chamber – the element is fragile. 

 

As necessary, shorten the element tails by clipping to length. Remake all the thermocouple and 
element connections according to the individual plan. 

 

Refit the back panel and run the furnace for 30 minutes at 800°C without interruption to ensure 
complete burn-off of any organic binders, Some smoke may be observed during this process, 
which should be carried out in a well ventilated area. 

 

Check that the furnace is controlling properly to rule out the possibility that the previous element 
failed because of a fault elsewhere in the control circuit. 

5.10 

12 

MF06 

Содержание CARBOLITE AAF 11/18

Страница 1: ...d to the electricity supply CONTENTS Section page 1 0 Descriptions 2 2 0 Installation 3 3 0 Operation 4 4 0 Maintenance 7 5 0 Repairs Replacements 8 6 0 Fault Analysis 14 7 0 Circuit Diagrams 15 8 0 F...

Страница 2: ...r flow through the chamber 1 3 GSM 11 7 This is a conventional muffle furnace with a Silica chamber This gives a cleaner environment than a standard ceramic muffle 1 4 VMF 10 6 The Volatile Matter Fur...

Страница 3: ...models and AAF 11 7 may alternatively be ordered for use on two phases out of a 3 phase with neutral supply The model AAF 11 18 may also be ordered for 3 phase supply see section 2 4 Check the furnace...

Страница 4: ...perature controller see the controller manual OAF 11 2 the slave controller should be set to an offset temperature of zero see 3 2 Overtemperature option only If the overtemperature controller has not...

Страница 5: ...AAF OAF GSM VMF 3 3 MF06 5...

Страница 6: ...used to heat materials which emit smoke or fumes regularly heat it up to maximum temperature for one hour without load to burn away the soot Materials such as case hardening compounds and other react...

Страница 7: ...respondence please quote the serial number model type and voltage given on the rating label of the furnace The serial number and model type are also given on the front of this booklet when supplied wi...

Страница 8: ...Guidance Note EH46 We can provide further information on request Alternatively our service division can quote for any repairs to be carried out at your premises or ours 5 3 Temperature Controller Rep...

Страница 9: ...AAF OAF GSM VMF 5 5 MF06 9...

Страница 10: ...section above which refers to the thermocouple colour coding Unfasten the electrical connections to the inner chamber brick box and remove the thermocouple and sheath see thermocouple replacement ins...

Страница 11: ...ermocouple cables from their terminal blocks Straighten all the element tails Note that these become brittle with use Unscrew the screws fixing the metal back piece from the inner chamber and withdraw...

Страница 12: ...at the furnace is controlling properly to rule out the possibility that the previous element failed because of a fault elsewhere in the control circuit 5 9 VMF 10 6 Element Replacement See section 5 2...

Страница 13: ...s good emission of some fumes may be expected 5 11 Fuse Replacement Fuses are marked on the circuit diagram section 7 0 with type codes e g F1 F2 A list of the correct fuses is given in section 8 1 De...

Страница 14: ...o lights glowing on the controller The SUPPLY light is ON The controller may be faulty or not receiving a supply due to a faulty switch or a wiring fault The SUPPLY light is OFF Check the supply fuses...

Страница 15: ...d PE L N F2 F1 SSR F3 F3 safety switches A heat on e l e m e n t s for AAF 11 18 see diagram 7 4 7 2 OAF 11 2 single phase 7 3 Higher Voltages e g 254V For single phase models of 254V or above a contr...

Страница 16: ...AAF OAF GSM VMF 7 4 16 MF06...

Страница 17: ...n t s e l e m e n t s N L L N L N thermocouple Fuses or EMC filters Supply Terminals Circuit no 3 Circuit no 2 N L N L N L3 L2 L1 N PE L Circuit no 1 3 phase neutral A model made to this diagram can...

Страница 18: ...Customer fuses Required if no supply cable fitted Recommended if cable fitted See rating label for amperage see table below for fuse rating Model Phases Volts Supply Fuse rating AAF 11 3 1 phase 200 2...

Страница 19: ...l 41 41 541 5877 Fax 41 41 541 5878 Email General Information Sales info kesn ch Accounts Department accounts kesn ch USA O ce 233 Rogue River Highway 425 Grants Pass Oregon 97527 5429 USA Tel 1 503 2...

Отзывы: