SPECIAL NOTE FOR LARGE AIR COOLED CONDENSING UNITS
: Vertical flow air cooled condensing units
are large and heavy pieces of mechanical equipment and must be handled as such. A fully qualified and
properly equipped crew with the necessary tackle and rigging should be engaged to locate the condensing unit
into location. The unit can be lifted by means of lifting holes located in the base frame of the unit. Spreader
bars should be used to prevent damage to the sides of the unit. Do not sling directly around the base of unit.
The unit should be placed on a base which is level and even.
Air Cooled Condensing Unit Minimum Clearance (For Vertical Air Flow Units)
Units equipped with spring-mounted compressors have shipping spacers that are designed to hold the
compressor rigidly during transit to prevent possible damage. Before operating the unit, it is necessary to
remove these spacers. To remove the shipping spacers, follow these steps:
(a)
Remove the upper nuts / washers.
(b)
Discard the shipping spacers.
(c)
Install the rubber cone washers (located in the electrical box).
(d)
Replace the upper mounting nuts / washers.
(e)
Allow 1/16 inch space between the mounting nuts / washers and the compressor foot.
On units equipped with rigid mounted compressors, check the compressor mounting bolts to insure they have
not vibrated loose during shipping.
WALLS OR OBSTRUCTIONS
All sides of the unit must be a minimum of 4 feet
(1.25 m) away from the wall or obstruction.
Overhead obstructions are not permitted. If
enclosed by three walls, the unit must be installed as
indicated for units in a pit.
MULTIPLE UNITS
A minimum of 8 feet (2.5 m) is required between
multiple units placed side by side. If placed end to
end, the minimum distance between units is 4 feet
(1.25 m)
UNITS IN PITS:
The top of the unit must be level with, or
above the top of the pit. In addition, a
minimum of 8 feet (2.5 m) is required between
the unit and the pit walls.
LOUVERS / FENCES:
Louvers/fences must have a minimum of 80% free
area and 4 feet (1.25 m) minimum clearance
between the unit and the louver/fence. Height of
louver/fence must not exceed top of unit.
4 ft
(1.25 m)
min.
8 ft
(2.5 m)
min.
8 ft
(2.5 m)
min.
8 ft
(2.5 m)
min.
4 ft
(1.25 m)
min.
4 ft
(1.25 m)
min.
Содержание K40-CU-IM-13
Страница 8: ...8 Electrical Wiring Diagram Horizontal Air Flow Condensing Units K Line ...
Страница 9: ...9 Electrical Wiring Diagram Horizontal Air Flow Condensing Units K Line ...
Страница 10: ...10 Electrical Wiring Diagram Horizontal Air Flow Condensing Units K Line ...
Страница 11: ...11 Electrical Wiring Diagram Horizontal Air Flow Condensing Units KE Line ...
Страница 12: ...12 Electrical Wiring Diagram Horizontal Air Flow Condensing Units KE Line ...
Страница 13: ...13 Electrical Wiring Diagram Horizontal Air Flow Condensing Units KE Line ...
Страница 14: ...14 Electrical Wiring Diagram Vertical Air Flow Condensing Units ...