30
System Troubleshooting
The following System Troubleshooting Guide lists the most common types of malfunctions encountered with
refrigeration systems. These simple troubleshooting techniques can save time and money minimizing
unnecessary downtime and end-user dissatisfaction.
Contact the factory or your local sales representative for further information or assistance.
System Troubleshooting Guide
Condensing Unit Problem
Possible Causes
Compressor will not run. Does not try to start.
1. Main power switch open.
2. Fuse blown or tripped circuit breaker.
3. Thermal overloads tripped.
4. Defective contactor or coil.
5. System shut down by safety devices.
6. Open thermostat or control. No cooling required.
7. Liquid line solenoid will not open.
8. Loose
wiring.
Compressor hums, but will not start. 1.
Improperly
wired.
2. Low line voltage.
3. Loose
wiring.
4. Defective start or run capacitor.
5. Defective start relay.
6. Motor windings damaged.
7. Internal compressor mechanical damage.
Compressor starts, but trips on overload
protector.
1. Improperly
wired.
2. Low line voltage.
3. Loose
wiring.
4. Defective start or run capacitor.
5. Defective start relay.
6. Excessive suction or discharge pressure.
7. Tight bearings or mechanical damage in compressor.
8. Defective overload protector.
9. Motor windings damaged.
10. Overcharged system.
11. Shortage of refrigerant.
12. Suction or discharge pressure too high.
13. Inadequate ventilation.
14. Operating system beyond design conditions.
Compressor short cycles.
1. Low pressure control differential set too low.
2. Shortage of refrigerant.
3. Low airflow at evaporator(s).
4. Discharge pressure too high.
5. Compressor internal discharge valves leaking.
6. Incorrect unit selection (oversized).
Start relay burns out.
1. Improperly wired.
2. Low or high line voltage.
3. Short
cycling.
4. Improper mounting of relay.
5. Incorrect start or run capacitor.
6. Incorrect
relay.
Contact welded stuck on start relay
1. Short cycling.
2. No bleed resistor on start capacitor.
Start capacitor burns out
1. Improperly wired.
2. Short
cycling.
3. Low line voltage.
4. Relay contacts sticking.
5. Incorrect
capacitor.
6. Start winding remaining in circuit for prolonged period.
Содержание K40-CU-IM-13
Страница 8: ...8 Electrical Wiring Diagram Horizontal Air Flow Condensing Units K Line ...
Страница 9: ...9 Electrical Wiring Diagram Horizontal Air Flow Condensing Units K Line ...
Страница 10: ...10 Electrical Wiring Diagram Horizontal Air Flow Condensing Units K Line ...
Страница 11: ...11 Electrical Wiring Diagram Horizontal Air Flow Condensing Units KE Line ...
Страница 12: ...12 Electrical Wiring Diagram Horizontal Air Flow Condensing Units KE Line ...
Страница 13: ...13 Electrical Wiring Diagram Horizontal Air Flow Condensing Units KE Line ...
Страница 14: ...14 Electrical Wiring Diagram Vertical Air Flow Condensing Units ...