background image

Description of the module

The TM 240/A is an temperature measurement module with 6 thermocouples.

3.1 

Front view

Fig.3-1:

TM 240/A Front view

1

... 6 Temperature inputs TI0 ... TI5

2

... Sensor interface (optional)

Information

The type plate is stored on the module in an EEPROM and can be read out
by the application.

TM 240/A, TE 220/A for KeStudio U3

Description of the module

© KEBA 2011

Project engineering manual V1.10

11

Содержание Kemro TM 240/A

Страница 1: ...Kemro TM 240 A TE 220 A for KeStudio U3 Temperature Module Project engineering manual V1 10 Translation of the original manual...

Страница 2: ...10 E Mail keba keba com D KEBA GmbH Automation Leonhard Weiss Stra e 40 D 73037 G ppingen Tel 49 7161 9741 0 Fax 49 7161 9741 40 E Mail keba keba com US KEBA Corp 100 West Big Beaver Road Troy MI 480...

Страница 3: ...2008 Safety notes techni cal data functional description stand ards declaration of conformity Chapter updated kalt 1 06 11 2008 New structuring of the project engineering manual bhm 1 07 04 2009 New m...

Страница 4: ......

Страница 5: ...face SENSOR 15 4 2 1 Connection example 15 4 2 2 Cable specification 15 4 2 3 Plug specification 15 4 3 EMC and wiring guidelines 15 5 Configuration 16 5 1 Setting the K Bus address 16 6 Functional de...

Страница 6: ...s 25 10 2 1 General procedures and safety principles 25 10 2 2 EMC guideline 25 10 2 3 Electrical safety and fire protection 25 10 2 4 Environmental and surrounding conditions 25 10 3 Standards for th...

Страница 7: ...al functions of the application system analysis and troubleshooting setting options at the operating installations Service technician Basic technical training Vocational high school engineering degree...

Страница 8: ...otes on this document This manual is integral part of the product It is to be retained over the entire life cycle of the product and should be forwarded to any subsequent owners or users of the produc...

Страница 9: ...t bodily injury CAUTION CAUTION used without the safety alert symbol indicates a potentially haz ardous situation which if not avoided may result in damage to property This symbol reminds you of the p...

Страница 10: ...le dam age Turn off the power supply before inserting or removing the module Other wise the module can be destroyed or undefined signal states can lead to damage of the control system Safety notes TM...

Страница 11: ...ont view Fig 3 1 TM 240 A Front view 1 6 Temperature inputs TI0 TI5 2 Sensor interface optional Information The type plate is stored on the module in an EEPROM and can be read out by the application T...

Страница 12: ...Weidm ller 2 pole sw BLZF 5 08 2 SN SW 170769 4 pole sw BLZF 5 08 4 SN SW 170771 6 pole sw BLZF 5 08 6 SN SW 170773 8 pole sw BLZF 5 08 8 SN SW 170775 Information Larger terminal blocks may be used t...

Страница 13: ...The thermocouple type must be software configured Information A thermocouple type that is incorrectly entered in the configuration can cause measurement errors The resolution of the measuring procedur...

Страница 14: ...al temperature sensor may be connected in this case Information With thermo compensation lines the possible temperature measurement range can be reduced e g to 0 C to 200 C Extension using Cu wire If...

Страница 15: ...t be used Max length 60 m 4 2 3 Plug specification RJ45 connector Modular 8 pole plug shielded The cable shielding must be connected plane with the shield cover of the plug An additional connection of...

Страница 16: ...ation tool 5 1 Setting the K Bus address The module is addressed via the address switch A maximum of 12 modules of the same type can be distinguished on one line The address switch is located on the r...

Страница 17: ...e address switch must remain locked at the last module in the line to protect against dirt and damage through elec trostatic discharge on contact TM 240 A TE 220 A for KeStudio U3 Configuration KEBA 2...

Страница 18: ...tware executes the linearization To enable evaluation of the temperature at the measuring point the tempera ture of the comparison point must be known The latter is measured by a terminal temperature...

Страница 19: ...ted to the TM 240 A The compensation of the terminal temperature is achieved with an internal temperature measurement sensor The measurement value is linearized and forwarded to the CPU in C No temper...

Страница 20: ...ommended to install the terminal point in a calm air environment and away from power electronics heating and ventilation elements that the temperature measurement sensor is directly attached to the te...

Страница 21: ...sor failure is recognized by the firmware An appropriate message is issued to the application Information The sensor failure is either triggered by a cable break in the thermocouple line or by a measu...

Страница 22: ...at electrical and electronic devices including their accessories must not be disposed of in the household garbage The materials are recyclable in accordance with their labeling You can make an importa...

Страница 23: ...ent process 14 Bit Thermocouple types J K L Measurement ranges Type J FE CuNi 100 C to 700 C Type K NiCr Ni 100 C to 1 000 C Type L Fe CuNi 100 C to 700 C Measurement principle Integrating Measuring t...

Страница 24: ...em perature sensor the error of the measurement system can be minimized to 0 5 C 9 4 Interface System bus interface Parallel bus interfaces plug in on side 9 5 Dimensions Footprint Module height 120 m...

Страница 25: ...uct was developed for the use in industrial areas and can cause radio interference when used in residential areas 10 2 2 EMC guideline EN 61131 2 2007 Programmable controllers Part 2 10 2 3 Electrical...

Страница 26: ...11 Declaration of conformity Fig 11 1 TM 240 A declaration of conformity Declaration of conformity TM 240 A TE 220 A for KeStudio U3 KEBA 2011 Project engineering manual V1 10 26...

Страница 27: ...Fig 11 2 TE 220 declaration of conformity TM 240 A TE 220 A for KeStudio U3 Declaration of conformity KEBA 2011 Project engineering manual V1 10 27...

Отзывы: