Information
The LEDs of the membrane keys blink as long as no connection between the
operating panel and control was established.
Fig.3-5:
Button and LED codes of the operating panel
1
... Power-LED
3.5.2
Power-LED
The green power LED is located on the front side of the operating panel. The
activation of the power LED occurs via the firmware of the operating panel and
is not parameterizable.
Power LED, green
Significance
Cause of fault/Remedy
Off
Operating panel not ready for
operation.
●
Firmware not present or
damaged
→
Perform firm-
ware update
●
Power supply not present
→
Check power supply.
Continuous light
Operating panel ready for op-
eration
→
Connection to con-
trol ok and hardware started
up.
-
flashing
Connection to the control
failed.
Check connection to the con-
trol.
flashing slowly (2 s period du-
ration)
Connection to the touch con-
troller failed.
Internal error
→
Contact serv-
ice technician
flashing quickly (1 s period du-
ration)
Touch defect
Internal error
→
Contact serv-
ice technician
Operating panel description
OP 350/C-1100
© KEBA 2009
Project engineering manual V2.00
16