CAUTION
Destruction of the operating panel for improper handling!
●
Install or remove the operating panel only while the power supply is switched
off!
●
The device is defined as "open type" equipment (UL508) or as "offenes Be-
triebsmittel" (according to EN 61131-2) and must therefore be installed in a
control cabinet or in a suitable housing. After mounting the front side rates
as part of the final casing to a "type 1" indoor use (according to UL 508) or
the protection type IP65 or IP 54 (according to EN) depending on operating
panel version.
●
In principle, the operating panel may not be opened since this results in loss
of the warranty.
Exception:
Excluded from this is maintenance work that is expressly allowed by KEBA.
Any other manipulations to the operating panel will also result in loss of
warranty.
2.3
Safety instructions for personal safety
WARNING!
Danger of personal injury due to electric shock!
●
Supply the device exclusively from power sources that have a safety extra-
low voltage or protective low voltage (e.g. SELV or PELV according to
EN 61131-2).
●
Connect only voltages and power circuits to connections, terminals and in-
terfaces up to 50 V rated voltage that have a secure disconnect for hazardous
voltages (e.g. with sufficient isolation).
WARNING!
The modules present on the operating panel are not designed for safety-relevant
control tasks (e.g.: shutdown in case of an emergency). For safety-relevant con-
trol tasks and personnel security, additional external safety measures must be
implemented to ensure the system remains in a safe operating condition even
in the event of a fault. For further information, see EN ISO 13849-1.
CAUTION!
Fire hazard during module failure!
●
Provide suitable fuses for the 24 V DC power supply of the operating panel
for the final application. The max. permitted fuse is 10A.
Operating panel
Safety notes
© KEBA 2009
Project engineering manual V2.00
11